Delta DVP40EC00R3 | PLC with 24 Inputs and 16 Relay Outputs

The Delta DVP40EC00R3 is a 100–240 V AC PLC main unit in the Delta DVP-EC3 series. It has 24 digital inputs rated at 24 V DC and 16 relay outputs. It reads sensors and sequences valves, contactors and indicators on conveyors, filling machines and packaging equipment.

Digital inputs and high-speed counting

The onboard inputs use octal addresses X0–X27. The S/S common connection sets the input circuit for sinking or sourcing. Check the PNP or NPN signal type against the panel diagram. When replacing an inductive sensor, photoelectric sensor or limit switch, check the signal voltage and common connection together.

The 20 kHz input group differs between instruction sheet editions. The 2010 sheet specifies 20 kHz for X0 and X1. The 2014 sheet specifies it for X0–X3. Both list 60 Hz for X20–X27. When connecting an incremental encoder, check the sheet applicable to the unit, the assigned inputs and the frequency limit for the selected high-speed counter mode.

Relay outputs and common terminals

The Y0–Y17 outputs are divided into four common groups. C0 serves Y0–Y3, C1 serves Y4–Y7, C2 serves Y10–Y13, and C3 serves Y14–Y17. Delta’s sheet lists 2 A per point and 5 A per COM for resistive loads. Contact operating voltage is specified as below 240 V AC or at most 30 V DC. The relay outputs are intended for on/off switching. Allow for inrush current and contact life when switching coils. Use an appropriately rated interposing relay and a suitable flyback diode or suppressor for DC coils where needed.

4K and 8K versions | Programming software

Use WPLSoft for EC3 projects. Earlier EC3 catalogues specify 4K steps. Delta’s programming manual identifies V8.60 and later as the 8K-step EC3-8K version. For this version, select EC3-8K in ISPSoft. Start the serial channel in COMMGR and select the same channel in ISPSoft. See the guides to ladder diagrams and PLC programming for help reading the program.

Programming cable and field communication

The PC connects through the PLC’s 8-pin mini-DIN COM1 / RS-232 port. Use UC-PRG020-12A for a USB-equipped PC or UC-MS020-01A for a PC with a physical RS-232 port. Install the USB cable driver and select the COM port assigned by Windows. See Delta PLC cables and the guide to RS-232, RS-422 and RS-485 when selecting a cable.

COM2 / RS-485 uses the D+, D− and SG terminals. For Modbus communication with an HMI or drive, match the station address, baud rate and parity. Verify the existing project’s Modbus ASCII or Modbus RTU setting at the other end.

The EC3 has fixed onboard I/O. Count the points needed when planning the panel. Where a device such as a pressure transmitter provides a 0–10 V or 4–20 mA signal, select a suitable measurement interface. See the guide to analog and digital inputs to compare signal types.

Editor’s Note

Check the label and firmware when buying used. Ask for a photo of the full model code and output terminals. Read the CPU version in software to establish program capacity.

Check the common first if a group fails. If Y14–Y17 stop together, check the feed to C3. Isolate the machine loads and test suspect relays with a suitable test load.

Keep fast signals off the slow input group. The sheet lists 60 Hz for X20–X27. If counts are lost as speed rises, check the input address and counter mode together.

Budget the auxiliary 24 V supply. The sheet specifies 300 mA for this model. Include the current drawn by the inputs and plan a separate HMI supply.

Save the working project before replacement. Back up the program, required retained values and serial settings. Test COM1 programming and COM2 field communication independently on the replacement CPU.

Internal References | Related Delta Models

The DVP40EC00T3 has the same 24 inputs and 16 outputs with NPN transistor switching. The DVP32EC00R3 has 16 inputs and 16 relay outputs. For more onboard points, the DVP48EC00R3 has a 28/20 I/O split and the DVP60EC00R3 has a 36/24 split.

For a project that needs modular expansion, consider the DVP40ES200R. Compare terminal layouts, software targets, special M/D addresses and serial settings before replacing a CPU.

Related Topics

See grounding and fuses for the panel supply, and NO and NC contacts for field signals. See safety relays for emergency-stop and guard-door circuits.

OtomasyonAVM PDF and Series Links

Delta DVP PLC files · Delta DVP-EC3 hardware and terminal sheet, 2010 (PDF)

All Delta DVP PLC series · Used Delta models

External References

Delta EC3 hardware sheet, 2014 (manufacturer download page) · Delta DVP-PLC programming manual and EC3-8K version note (EN, PDF) · Delta PLC/HMI cable selection guide, section 1.3 (EN, PDF)