Delta DVP32EH00R

Delta DVP32EH00R | 32-Point Relay Output PLC

The Delta DVP32EH00R is a 100–240 V AC PLC main unit from the first-generation Delta DVP-EH series. It has 16 digital inputs rated at 24 V DC and 16 relay outputs. It reads sensors and sequences valves, contactors and indicators on conveyors, packaging machines and assembly stations.

Digital inputs and field wiring

The onboard inputs use octal addresses X0–X17. The S/S common connection sets the input circuit for sinking or sourcing. Check PNP or NPN wiring against the panel diagram. When replacing an inductive sensor, photoelectric sensor or limit switch, check both the signal voltage and the common connection.

When using an incremental encoder, check the signal type, input filter and limits of the selected high-speed counter mode. The first-generation EH sheet assigns its 5 V differential, 200 kHz input diagram to the DVP32EH00M. The DVP32EH00R terminal diagram shows 24 V DC inputs with an S/S common.

Relay outputs and load selection

The onboard outputs are addressed Y0–Y17. Delta’s EH sheet specifies 2 A per point and 5 A per common group. Contact operating voltage must be below 250 V AC or at most 30 V DC. Allow for inrush current and switching frequency when driving coils. Use a suitably rated interposing relay and load suppression where needed. A suitable flyback diode limits the voltage spike when a DC coil switches off.

Programming software and cable

Use WPLSoft for first-generation EH projects. When using ISPSoft, verify that the installed release offers the first-generation DVP-EH target. Configure and start the serial channel in COMMGR and select the same channel in ISPSoft. On an existing machine, retain the original project file, the program read from the CPU and the required retained settings. See the guides to ladder diagrams and PLC programming for help reading the program.

The computer connects through the PLC’s 8-pin mini-DIN COM1 / RS-232 port. The DVPACAB2A30 serial programming cable has a mini-DIN connector at the PLC end and a 9-pin D-sub at the computer end. On a USB-equipped PC, use a suitable USB-to-RS-232 adapter and its driver. Select the COM port assigned by Windows. See Delta PLC cables and the guide to RS-232, RS-422 and RS-485 when choosing the connection.

Field communication, memory and expansion

COM2 / RS-485 can communicate with an HMI or drive. For Modbus over RS-485, match the station address, baud rate, parity and frame format. Verify the existing project’s Modbus ASCII or Modbus RTU setting on the device at the other end.

The EH technical table lists 15,872 program steps and battery-backed SRAM. With compatible expansion modules, the system can reach 512 total I/O points. For analog voltage or current measurement, consider a compatible first-generation EH module such as DVP04AD-H. Check the channel settings and see the guide to analog and digital inputs when selecting an interface.

Editor’s Note

Read the full code on the label. When buying used, confirm that it ends in 00R. Ask for photos of the terminals and any fitted communication cards.

Test the relays under load. A relay can click while a worn contact drops voltage under load. Isolate the machine loads and test the required Y channels with a suitable test load.

Check the common when a group fails. If several outputs stop together, inspect the feed and connection at that group’s C terminal first.

Back up first if BAT.LOW is lit. Save the program, retained data and serial settings before switching off. Follow the battery procedure in the first-generation EH sheet.

Test COM1 and COM2 separately. A successful program read verifies COM1. Test the COM2 field link with the machine’s HMI or drive and its actual serial settings.

Internal References | Related Delta Models

The DVP32EH00T has the same 16/16 I/O count with transistor outputs and supports 200 kHz pulse output on Y0 and Y2. For relay control with fewer onboard points, the DVP20EH00R has 12 inputs and 8 relay outputs.

The DVP32EH00R2 and DVP32EH00R3 are the 16-input, 16-relay-output models in the EH2 and EH3 generations. Compare terminal layouts, program instructions, fitted modules and serial settings before replacing a CPU.

Related Topics

See grounding and fuses for the panel supply, and NO and NC contacts for field signals. See safety relays for emergency-stop and guard-door circuits.