Delta DVP26SE11T
Delta DVP26SE11T | Ethernet DVP-SE PLC with 14 inputs and 12 NPN outputs
The Delta DVP26SE11T is a compact PLC CPU in the Delta DVP-SE family with 14 digital inputs and 12 NPN transistor outputs. It has built-in Ethernet, mini-USB and one RS-485 port. The nominal supply is 24 VDC, with an operating range of 20.4–28.8 VDC. Delta’s catalogue specifies a 16k-step program capacity and 12k words of data registers.
NPN outputs, high-speed inputs and expansion
The 24 VDC inputs use addresses X0–X7 and X10–X15. When wiring an inductive sensor, match the S/S common to its PNP or NPN output. For high-speed counter applications, check the input frequency limits in the instruction sheet. It specifies 100 kHz for X0–X3, 10 kHz for X4–X7 and 50 Hz for X10–X15. Check the counter mode and input filter for the application.
The 12 NPN outputs are divided into two groups. Y0–Y7 use UP0/ZP0 and Y10–Y13 use UP1/ZP1. The instruction sheet gives resistive load limits of 0.5 A per point and 4 A per common. Check the 24 VDC auxiliary supply for each group. Select suppression or a suitable interposing relay for the coil type and current.
Y0 and Y2 support pulse rates up to 100 kHz. Y1 and Y3 support up to 10 kHz. Check the pulse frequency and NPN input wiring required by the drive. The DVP26SE11T supports right-side expansion with compatible DVP Slim digital modules or analog modules. For analog measurements, match the input range and sensor type to the expansion module.
WPLSoft, ISPSoft and programming connections
Use WPLSoft or ISPSoft to develop the PLC program and select DVP-SE as the CPU family. For USB, use the CPU’s mini-USB programming port with a data cable such as UC-PRG015-01A. Check the COM number assigned by Windows. For ISPSoft, select the appropriate USB driver and port in COMMGR.
You can also connect the PC to the PLC with a CAT5e Ethernet cable. Use DCISoft to find the PLC and check its IP address and subnet mask. Delta’s factory settings are 192.168.1.5 / 255.255.255.0. On an installed machine, use the configured IP address. Put the PC on the same subnet and select the Ethernet driver and PLC IP address in COMMGR for an ISPSoft connection.
Ethernet, Modbus and RS-485
The built-in Ethernet port supports Modbus TCP, EtherNet/IP adapter mode and explicit messaging. For a Modbus TCP HMI, check the CPU’s IP address along with the HMI driver and register settings. The DVP26SE11T has one RS-485 port, COM2. When connecting serial devices with Modbus ASCII/RTU, check the station address, baud rate, parity and bus termination.
Editor’s Note
When buying a used unit, check the full model code, removable terminals, RJ45 and mini-USB sockets, right-side expansion connector and DIN rail clip.
Before replacement, back up the project, required retained values and IP settings. Disconnect the old CPU before bringing the replacement online with the same IP address.
Test both output groups with a suitable load. If a whole group fails, measure its UP/ZP supply first.
During troubleshooting, verify program readback over USB, Ethernet access and COM2 communication individually.
Check the high-speed pulse with an oscilloscope where possible. Inspect the field cable shielding and grounding connections.
Related models
The DVP26SE11R has 14 inputs and 12 relay outputs. The DVP12SE11T has 8 inputs and 4 NPN outputs. The DVP12SE11R has 8 inputs and 4 relay outputs. The DVP28SS211T is an SS2 CPU with 16 inputs and 12 NPN outputs. For a CPU replacement, check the I/O addresses, output type and communication ports used by the installation.
Navigation and PDF files
Delta Automation · Delta PLC · Delta DVP PLC series · DVP expansion modules · Delta DVP PLC files
External references · DVP-SE instruction sheet (EN / Chinese) · Delta DVP programming manual (EN) · Delta PLC/HMI cable selection guide (EN)