Delta DVP01PU-S

Delta DVP01PU-S – Single-Axis 200 kHz Positioning Module

The Delta DVP01PU-S generates pulse commands up to 200 kHz for one axis in a compatible Delta DVP Slim PLC system. It connects to the CPU’s right-side expansion bus. It is used for feeding, indexing and linear positioning with a pulse-input servo drive or a compatible stepper drive. Functions include absolute and relative moves, jogging and homing.

Power supply and FP/RP pulse outputs

Connect an external 24 V DC supply to the module. The operating range is 20.4–28.8 V DC, with a nominal current draw of 70 ±10 mA. The FP+/FP− and RP+/RP− terminals provide 5 V differential line-driver signals. In Delta’s ASDA-A2 wiring example, the FP pair connects to the pulse input and the RP pair to the direction input in Pulse/Dir mode.

Use CR#5 to select Pulse/Dir, CW/CCW or A/B phase. In Pulse/Dir, FP carries the motion pulses and RP carries the direction signal. In CW/CCW, FP and RP carry pulses for opposite directions. In A/B mode, the outputs provide phase-shifted signals. Set the same format on the module and drive. Match the + and − terminals of each differential pair and route the signal cable away from motor wiring to reduce electromagnetic interference. Follow the equipment grounding diagrams for shield connections.

Travel limits, homing sensor and handwheel

START, STOP, LSP, LSN and DOG are 24 V DC control inputs and share the S/S common. LSP/LSN monitor the travel limits in each direction. During homing, DOG receives the near-point signal and PG0 receives the zero signal. A+/A− and B+/B− accept an A/B-phase manual pulse generator (MPG). CLR+/CLR− is a 5–24 V DC NPN open-collector output rated below 20 mA that can clear the position deviation counter on a compatible drive.

During homing, first check that the DOG sensor switches as expected. If the selected homing mode uses PG0, confirm that the zero signal arrives and that motion finishes in the intended direction. When scaling position, use both the command pulses accepted by the drive per motor revolution and the mechanical travel per revolution. For example, if the drive accepts 2,000 pulses per revolution and a directly coupled screw advances 5 mm per revolution, a 10 mm move requires 4,000 command pulses.

PLC registers and diagnostics

Use FROM to read the module’s control registers and TO to write them in the PLC program. CR#0 reports the model ID (H0110) and CR#5 sets the output format and basic parameters. CR#23–24 holds the first target position and CR#25–26 holds the first move speed. In each pair, the first register is the low word and the second is the high word. CR#31 holds operating commands, CR#32 selects the operating mode, CR#38 reports status, CR#39 reports the error code and CR#47 shows terminal status. Set the module number in the program according to its position among the CPU’s right-side special modules.

Programming software and cable

Download the program to the host CPU using a compatible version of WPLSoft or ISPSoft. Configure the ISPSoft connection through COMMGR. The UC-PRG020-12A is an option for a compatible COM1 RS-232 port such as the DVP-SS2. The UC-PRG015-01A can be used with the DVP-SX2 mini-USB port. Delta also documents Modbus ASCII/RTU access to the control registers through the module’s own RS-485 port.

Editor’s Note

When buying a used unit, verify the full DVP01PU-S code and inspect the power plug, signal terminal block and side expansion connector.

Start with a short move at low speed. Check the actual direction of travel and confirm that the LSP/LSN inputs respond in the expected direction.

If the motor stays still, check that the drive is set to accept pulse commands. Then compare the CR#5 format and the wiring of the FP/RP pairs.

If the home position varies between cycles, check the DOG sensor, PG0 when used by the selected mode, and the homing approach speed. Monitor input states through CR#47.

If ERROR flashes, read CR#39. For example, H0030 indicates low supply voltage. Measure it at the module’s own power terminals.

Related models and topics

The DVP01PU-H and DVP01PU-H2 are positioning modules for their respective DVP families. The DVP01HC-H2 and DVP02HC-H are high-speed counters for reading external pulses. For the drive side, see servo motors and Delta motion control cards.

Manual and wiring diagram

Chapter 10 of the DVP Series Module Manual covers the terminal layout, control registers, ASDA-A2 wiring and error codes. See Delta DVP PLC files for the series documentation.