Delta DVP01LC-SL

Delta DVP01LC-SL Single-Channel Load Cell Module

The Delta DVP01LC-SL is a single-channel weighing module that mounts on the left side of a compatible Delta DVP PLC CPU. It processes the millivolt signal from a four- or six-wire load cell and makes the weight available to the PLC. Typical uses include single-platform filling machines, small hoppers and product weight checks.

The mV/V rating on a strain gauge load cell describes its signal at rated load. A 2 mV/V cell supplied with 5 V produces about 10 mV at rated load. For an analog signal this small, cable routing, electromagnetic interference and panel grounding affect reading stability. Route the load cell cable separately from drive-to-motor wiring.

Technical specifications

Measurement channel • One input, CH1, for a four- or six-wire load cell. The input range is ±40 mV DC and the sensor excitation is 5 V DC ±10%.

Supply and resolution • External 24 V DC power supply, with a 20.4–28.8 V DC operating range and 3 W power consumption. Delta specifies 20-bit ADC resolution and 16-bit weight data output.

Sensitivity and filtering • Select 1, 2, 4 or 6 mV/V to match the load cell. The factory default is 2 mV/V. The available response times are 2, 10, 20, 40, 80, 200 and 380 ms. The default is 80 ms, and the averaging filter can use 1–100 samples. For filling applications, check settling time during an actual machine cycle.

Load cell wiring and PLC compatibility

For a four-wire sensor, connect the excitation leads to EXC+ / EXC− and the signal leads to SIG+ / SIG−. Fit jumpers between EXC+ and SEN+ and between EXC− and SEN− at the module. For a six-wire sensor, connect the separate sense leads to SEN+ / SEN− and terminate the cable shield at SHD as shown in Delta’s wiring diagram. Use the sensor label or wiring diagram to identify each conductor.

Check the full CPU part number for left-side expansion support. Compatible DVP-SX2 and DVP-SA2 CPUs are among the series listed by Delta. Left-side modules are numbered 100–107 starting closest to the CPU. Delta’s examples use K100 for the first module. The PLC uses FROM to read weighing registers and TO to write settings.

LCSoft, programming cable and calibration

Use Delta LCSoft for module setup and calibration. A PC can connect directly to the module’s COM1 RS-232 port through its 8-pin mini-DIN connector. In Delta’s wiring diagram, PC DB9 pins connect to module pins as 2 → 5, 3 → 4 and 5 → 8. The module’s COM2 port supports RS-485 Modbus.

Write the PLC program in WPLSoft or, for supported CPUs, ISPSoft. For an ISPSoft connection, select the channel for the CPU in COMMGR. For example, DVP20SX2 CPUs use UC-PRG015-01A for mini USB or UC-PRG020-12A for CPU COM1 RS-232. Select the Delta PLC cable for the device and port you intend to use.

To calibrate, capture zero with the platform empty, then establish the second point with a known reference weight. When calibrating from the PLC, send the calibration command through CR#26. Write H5678 to CR#41 to save the settings to flash. The register returns HFFFF when the save completes. During operation, CR#6 captures the tare for a container or package, and CR#7 selects gross or net weight.

Editor’s Note

When checking a used module, confirm the DVP01LC-SL label and the CH1 terminals. Look for bent pins on the left-side expansion connector, loose terminals and corrosion.

If there is no reading, first use a multimeter to check the module supply and the excitation voltage across the EXC terminals. The sense jumpers are easy to overlook on a four-wire sensor.

If the reading falls as load increases, check SIG+ and SIG− against the sensor wiring diagram. Confirm that the platform can also move freely.

If the ERROR LED flashes, read CR#51. Bit 0 indicates a supply fault, bit 2 a CH1 conversion error and bit 3 a CH1 sense voltage fault.

After calibration, check an intermediate point with a different known weight. Verify that the reading returns to zero after unloading and that calibration is retained after a power cycle.

Related Delta load cell modules

DVP02LC-SL • Two weighing channels in the same family. DVP201LC-SL • Single channel with a 24-bit ADC. DVP202LC-SL • Two channels with a 24-bit ADC. DVP211LC-SL • Single weighing channel with additional digital I/O and a current output. Compare CPU compatibility, terminals and register addresses before replacing a module.

Related topics and Delta files

How does a load cell work? · Types of load cells · What is a PLC?

Delta DVP PLC PDF files · DVP Slim load cell modules · Used Delta PLC models · Delta main page