Delta DVPCOPM-SL

Delta DVPCOPM-SL – CANopen Communication Module

Delta DVPCOPM-SL is a DVP Slim communication module that mounts on the left side of a compatible Delta DVP PLC. It can operate as a CANopen master or slave. In master mode, the PLC exchanges commands and status data with CANopen-compatible servo drives and remote I/O stations. The CPU supplies the module through its internal bus. Power consumption is 1.7 W.

Specifications and CAN bus wiring

The module offers eight bit rates from 10 kbit/s to 1 Mbit/s. Delta’s product page lists support for up to 110 slave devices in master mode. When sizing the network for a target cycle time, account for the node count, PDO traffic and bus length. Delta’s wiring table specifies 25 m at 1 Mbit/s and 100 m at 500 kbit/s.

The removable 5-pin connector is marked 1 GND, 2 CAN_L, 3 SHLD, 4 CAN_H, 5 reserved. Use shielded twisted-pair CANopen cable. Fit 120 Ω between CAN_H and CAN_L at each physical end of the trunk. Give each device a unique Node ID (1–127). The module has two rotary switches for node addressing and DR0–DR2 DIP switches for bit rate. Use the same bit rate across the network and switch off power before changing the switches.

Compatible PLCs, CANopen Builder and cable

Delta’s product page lists the DVP-EH3-L, DVP-MC, DVP-SA2, DVP-SE, DVP-SV2 and DVP-SX2 families. The current module manual also covers DVP-28SV, DVP-EH2-L, DVP-SV3, DVP-SX3 and DVP-SE2. Before installing, check left-side expansion support and the module limit for the exact CPU model.

Use Delta CANopen Builder to scan the network, import the device’s EDS file, build the node list and configure PDO mapping. In Delta’s DVP-28SV example, the PC connects to the CPU’s RS-232 programming port. For compatible CPUs with an 8-pin mini-DIN RS-232 port, Delta’s cable guide lists the UC-PRG020-12A USB-to-RS-232 cable or the UC-MS020-01A serial cable, depending on the CPU. Edit the PLC logic in WPLSoft or ISPSoft as supported by that CPU.

PDOs, SDOs and PLC data registers

PDOs carry process data such as control words and status values. SDOs read or write parameters in a device’s object dictionary. NMT manages node operating states, and heartbeat monitors node availability. Use the resulting CANopen Builder mapping to reference the correct D registers in the ladder program. Select the register table for the CPU model and the module’s position in the left-side stack. In Delta’s DVP-28SV example, the first module’s PDO input area starts at D6032 and its output area starts at D6282.

Editor’s Note

When buying second-hand, inspect the side connector, the retaining clips and the five-pin CAN terminal block. Check the exact CPU model before selecting a module.

Before replacing a unit in an existing machine, save the CANopen Builder project. Keep a copy of the rotary and DIP switch settings and the node list.

Start the bench test with one slave device. Watch RUN, ERR and the numeric display. Check that a status value reaches the PLC’s D register through the PDO.

For F4, check bus wiring, bit rate and termination. If the master reports E1, compare the slave’s PDO length with the project mapping. If communication drops when a drive starts, inspect grounding and electromagnetic interference.

For SAE J1939, check the label and version. Delta specifies support for v2.xx units made in calendar week 29 of 2025 or later.

Related topics and modules

See the CAN communication FAQ and industrial communication guide when planning the bus. For other networks, DVPDNET-SL supports DeviceNet, DVPPF02-SL supports PROFIBUS DP, and DVPEN01-SL supports Ethernet. For CANopen on the Delta AH platform, see AH10COPM-5A.

Delta DVP expansion modules · Delta DVP PLC series · Second-hand Delta models · Delta DVP PLC PDF files

External references

Delta DVP Module Manual, Section 13.3 (2026, EN) · DVPCOPM-SL Instruction Sheet (2018, EN/ZH) · Delta SAE J1939 version note · Delta DVPCOPM-SL product specifications · CiA CANopen bit rate and bus length table