Delta RTU-DNET
Delta RTU-DNET | DeviceNet remote I/O communication module
The Delta RTU-DNET is a remote I/O adapter for connecting compatible DVP Slim expansion modules to a DeviceNet network. It operates as a DeviceNet slave. The scanner reads field inputs from the station and sends output commands to it. RTU-DNET supports polled I/O and explicit messages for parameter access. Delta discontinued the model in June 2024.
Supply, network connector and I/O capacity
The unit draws power from the DeviceNet bus. It is rated at 24 VDC nominal, with a documented operating range of 11–25 VDC. The removable five-terminal connector carries V+, V−, CAN_H, CAN_L and shield. The module mounts on a 35 mm DIN rail and accepts compatible DVP Slim digital, analog and temperature modules on its right side.
The manual specifies up to 128 digital inputs, 128 digital outputs and 8 special modules. Its compatibility table includes the DVP16SP11R digital I/O module and DVP04PT-S temperature module. Check the full part numbers and installation order when selecting modules for the station.
DeviceNet Builder, PLC connection and I/O mapping
Use the front rotary switches to select a unique DeviceNet node address from 00 to 63. The DR1 and DR0 switches set the standard network rate. OFF/OFF selects 125, OFF/ON selects 250 and ON/OFF selects 500 kbit/s. Match the rate to the scanner and set the switches with power off.
Configure RTU-DNET with DeviceNet Builder. In Delta’s example, the PC connects to the DVP28SV11T CPU over RS-232 and reaches the network through a DVPDNET-SL scanner. Select the PC cable for the host CPU port. For DVP-SV2 COM1, Delta’s cable guide lists UC-PRG020-12A USB-to-RS-232 and UC-MS020-01A RS-232 options. Choose WPLSoft or ISPSoft according to the host PLC model and project support.
After scanning for online nodes in Builder, select RTU-DNET and use I/O Configure → Scan IO to detect the station modules. Download the configuration to RTU-DNET and add the station to the scanner’s Scan List. Compare the input and output lengths in bytes on both sides. Enabling the control and status words adds two bytes in each direction. If the scanner requires a device description, use an EDS file that matches the hardware revision.
RS-485 Modbus gateway
The separate RS-485 Modbus port supports up to 8 slave devices. In Builder’s Modbus Gateway Setup, match the drive or temperature controller’s station address, ASCII/RTU mode, baud rate and parity. Define read and write data using the field device’s register map. When routing a temperature reading to the scanner, check the Modbus station address and the DeviceNet node address on their respective networks.
When diagnosing industrial communications, verify that the DeviceNet scanner exchanges I/O with the station first. Next, check the response from the Modbus device and the PLC’s scaling of its analog data. An RS-485 device can go offline while the DeviceNet connection is still active.
Editor’s Note
When buying a used unit, inspect the full model label, the removable DeviceNet connector, the right-side expansion port and the clips.
Before replacing a working station, record the node address, DIP switch settings, module order and scanner project.
On the bench, check POWER for supply, NS for network status and MS for module status. If ALARM lights, check the diagnostics in Builder.
Start troubleshooting with the node address and rate. Then check the cable termination, shield and grounding connections.
IN0 affects buffer retention when the network link drops. IN1 affects it when the master stops. After replacement, verify the actual output behaviour in both cases under safe test conditions.