Delta DVP specialty communication modules
Delta DVP Specialty Communication Modules
The Delta COA02 and DNA02 are external adapters that connect a serial PLC, drive or other field device to an existing industrial network. The COA02 is a CANopen slave, and the DNA02 is a DeviceNet slave. Identify the machine’s industrial communication network first, then check the protocol and port on the serial equipment.
Model selection
| Model | Field network and role | Address and network speed |
|---|---|---|
| Delta COA02 | CANopen slave, DS301 V4.02 | Node ID 1–127 (01h–7Fh). 10, 20, 50, 125, 250, 500, 800 or 1,000 kbit/s. |
| Delta DNA02 | DeviceNet slave adapter | Decimal MAC ID 00–63. 125, 250 or 500 kbit/s. |
Connecting a serial device to CANopen with COA02
The COA02 lets a CANopen master exchange data with serial equipment. Delta’s manual includes examples for DVP PLCs, VFDs, ASD-A servo drives, DTA/DTB temperature controllers and DOP panels. For example, with the appropriate device profile, the CANopen master can read status data from a serial variable frequency drive. For a servo drive or operator panel, use the serial wiring diagram and data table for the specific model.
PDO mapping determines which status and command data the network exchanges during operation. SDO provides access to device objects and parameters. Import the correct COA02 EDS into the master project. Compare the Node ID, device profile and transmit/receive PDO contents against the working project.
Connecting a serial device to DeviceNet with DNA02
The DNA02 operates as a slave on a DeviceNet scanner’s network. Check the scanner’s MAC ID assignment, baud rate, scan list and I/O data length together. For example, the DNA02 can pass a DVP PLC’s status and fault information to a supervisory controller. Once the data is mapped to tags in that controller, it can be monitored on a SCADA screen.
Record which serial register receives each value from the scanner and which scanner word receives the value back from the device. If the node appears after replacement and values stay stale, start with the scan list, input/output byte lengths and serial device profile.
Serial ports, cabling and engineering software
Both modules provide RS‑485 on RJ‑12 PORT1. DB9 PORT2 can be selected for RS‑232 or RS‑485. Identify the communication port on the serial equipment, then match the pin tables at both ends. Set the Modbus station address, baud rate, parity and ASCII or RTU format for the selected device profile.
Use CANopen Builder on supported projects with Delta’s DVPCOPM-SL master. Use DeviceNet Builder with the DVPDNET-SL scanner. Select the EDS file by protocol, model and revision. When register assignments or Ladder logic change on a DVP CPU, do the PLC programming in the WPLSoft or ISPSoft version supported by that CPU.
Commissioning and troubleshooting
Check the field network first. Verify the supply, unique node address and fieldbus speed. Delta lists 11–25 V DC at the network connection for both units. Check termination and shield connections against the diagram for the relevant network. Route fieldbus and serial wiring away from motor cables to reduce electrical interference.
Then check the serial device. Use RUN/ERROR on the COA02 and MODULE STATUS and NETWORK STATUS on the DNA02 to check the network side. Both models have a SCAN PORT indicator to help diagnose the serial device side. Start by confirming a safe read value. Once addresses, direction and scaling agree, check the command path under the machine’s commissioning conditions.
Editor’s Note
When buying used, write down the full COA02 or DNA02 code. Check for a missing fieldbus plug, a broken RJ‑12 latch or a loose DB9 connector.
Photograph the rotary and DIP switches before removing a working module. Record the COA02 address in hexadecimal and the DNA02 address in decimal.
Keep the master project, EDS file and I/O mapping together. A change in word order can shift the displayed value even when the byte count stays the same.
If the field network works and the serial equipment stays silent, check the device profile, port selection, pinout and serial station address in that order.
After changing switches, follow the manual’s power-cycle procedure. If dropouts coincide with a motor starting, also check the shield connections and cabinet grounding.
Related modules and topics
For network modules that attach to the CPU, see Delta DVP Slim communication modules. To collect sensor and actuator signals at a separate station, see remote I/O and the Delta DVP remote I/O modules.
CAN communication FAQ · RS‑232, RS‑422 and RS‑485 compared
Internal references and PDF files
OtomasyonAVM Delta DVP PLC Files · Delta DVP expansion modules · Delta DVP PLC series · Used Delta equipment
External references
Delta DVP S/H2 Special Modules Application Manual (PDF, 2013, EN) · DNA02 chapter 12, COA02 chapter 13.
Delta DVPCOPM-SL master manual · Delta DVPDNET-SL scanner manual · ODVA DeviceNet cable guide