Delta DVP24XP11R

Delta DVP24XP11R - 16 Input / 8 Relay Output ES/EX Extension Unit

Delta DVP24XP11R is an extension unit for the DVP-ES and DVP-EX family, providing 16 digital inputs and 8 relay outputs. The number 24 represents the total I/O count. It is a 24 V DC H-type unit; its I/O is controlled by the program in the host PLC.

Select it within the ES/EX digital extension range after checking the CPU generation, hardware revision, extension order and power budget. DVP24XP00R has the same 16/8 count but a different supply and terminal arrangement. Use the complete ordering code.

Power supply and digital inputs

Supply: nominal 24 V DC. The manufacturer’s terminal drawing identifies 24VDC and 0V as the operating-supply terminals. Distinguish these from the +24V/24G field terminals and S/S input common. Size the 24 V power supply against the unit label, hardware revision and field load.

Inputs: 16 channels, locally labelled X0-X7 and X10-X17. The digital extension sheet specifies 24 V DC, nominal 5 mA and approximately 20 ms response. For PNP/NPN wiring, connect S/S to 0 V for PNP sensors or to +24 V for NPN sensors.

Typical signals come from inductive sensors, photoelectric sensors, limit switches and pushbuttons. Optocoupler inputs and status LEDs support normal state monitoring. Fast encoder pulses require suitable high-speed CPU inputs or a dedicated counter module.

Relay outputs and separate contact pairs

Outputs: Y0-Y7, eight relay outputs. The ES/EX digital extension sheet gives 2 A per channel, voltage limits of 250 V AC / 30 V DC and approximately 10 ms response. Apply the manufacturer’s load-type limits when assessing inductive loads and inrush. Relay contacts are unsuitable for high-speed pulse generation.

Terminal pairs: C0-Y0, C1-Y1, C2-Y2, C3-Y3, C4-Y4, C5-Y5, C6-Y6 and C7-Y7. The eight output commons are brought out separately. Wire each load through its corresponding C-Y pair; assess the circuit before bridging commons. A relay contact does not generate a load supply.

Use suitable suppression and circuit protection when switching contactor or valve coils. For DC coils, use a suitable diode or manufacturer-approved suppressor; use an appropriate AC suppressor for AC coils. A channel rating does not establish an unlimited total unit rating.

Addressing and extension cable

X/Y numbering is octal: X10 follows X7. Local terminal labels can differ from program addresses. For example, a first extension in a suitable 14ES/32ES installation may occupy X20-X37 and Y20-Y27. Preceding modules change the starting addresses; track input and output allocation separately.

The unit connects through the CPU’s extension interface. Legacy ES/EX peripherals include the DVPACAB403, 30 cm extension cable. This carries extension I/O connections and serves a different purpose from a computer programming cable.

Programming software and computer cable

The host CPU stores the program and executes I/O commands. Legacy ES/EX documentation specifies WPLSoft. Before using ISPSoft, confirm support for the exact CPU in that software version and configure COMMGR. DVP24XP11R has no separate user-program download or independent Modbus station setting.

Connect the computer to the host CPU’s COM1 RS-232 port. Examples for suitable ES/EX CPUs include the UC-PRG020-12A USB programming cable, UC-MS020-01A serial cable and legacy DVPACAB2A30. Choose the Delta PLC cable for the host port and pinout; check the USB-serial driver and COM number.

Related models and selection differences

DVP24XP11T has 16 inputs/8 transistor outputs. DVP24XP00R is an AC-powered relay unit with the same point count. DVP32XP11R provides 16 inputs/16 relay outputs; DVP24XN11R provides 24 relay outputs; DVP08XP11R provides 4 inputs/4 relay outputs. Review supply, contacts, terminals and addressing together before changing models.

Editor’s Note

Verify DVP24XP11R on the actual label. 11R, 00R, 11T and newer 200R codes identify different units; a short sales title is insufficient.

Photograph all eight C-Y pairs before removal. Existing bridges may distribute a field supply; establish their purpose before transferring wiring to another unit.

A relay click and an LED do not prove contact health. Test every contact with a controlled load in both states; a welded contact may keep a load powered after its command disappears.

Apply a controlled 24 V input signal with the correct S/S connection. Compare the terminal LED with the actual CPU address to distinguish wiring from module faults.

Do not treat filter settings from a general CPU sheet as extension-module parameters. Use the digital extension sheet for this unit’s input response.

For overheated terminals or darkened boards, investigate inrush, fuses and grounding. Disconnect power, preserve the CPU program and prevent machine movement during the first test.

PDF files and related topics

Use our Delta DVP PLC files page for manuals. The ES/EX general instruction sheet already hosted on our site is in English and includes this exact 16-input/8-relay-output model.

Navigation: DVP24XP11R main page · ES/EX extension modules · DVP extension modules · Delta PLC · Used Delta equipment.

External references

ES/EX digital expansion instruction sheet · Legacy ES/EX technical and programming manual · PLC/HMI Cable Selection Guide – ES/EX CPU connections