The Delta AS-F2AD is a two-channel analog input card that plugs into a function-card slot on a Delta AS300 PLC CPU. It reads signals from pressure transmitters, level transmitters and analog position sensors. If the CPU has a free slot, this AS function card adds two measuring points while saving panel space.

Signal ranges and wiring

Each analog input supports 0–10 V DC, 12-bit, 0–4000 raw counts in voltage mode or 4–20 mA, 11-bit, 0–2000 raw counts in current mode. Conversion takes 3 ms per channel. Include the PLC scan time and any averaging setting when estimating the response time in the program.

The terminal order is V1+, I1+, V2+, I2+, COM. The channels share COM. For a 4–20 mA signal, bridge V+ and I+ for the relevant channel as shown in Delta’s wiring diagram. Route the analog signal cable away from power cables. Check the transmitter’s power and signal terminals against the wiring diagram before connection.

CPU compatibility and SR addresses

Delta lists the card for function-card slot 1 or 2 on AS300 CPUs such as the AS332T-A, AS332P-A, AS324MT-A and AS300N-A. The card occupies one slot. Two AS-F2AD cards provide four analog inputs if both slots are available. The AS-FEN02 occupies both CPU slots. Delta’s table lists separate communication-card options for the AS00SCM-A.

In slot 1, read CH1 from SR168 and CH2 from SR169. In slot 2, read CH1 from SR170 and CH2 from SR171. Check the program’s register addresses if you move the card.

ISPSoft setup and card selection

Connect the PC to the CPU over Mini USB or Ethernet and set up the connection in COMMGR. In ISPSoft, open HWCONFIG and select the relevant Function Card 1 or 2 section. Confirm the AS-F2AD and select the channel mode. For analog output, see the AS-F2DA. For more input channels, see AS analog modules such as the AS04AD-A.

Editor’s Note

On a used card, check the F2AD marking, connector pins and PUSH latch.

Install the card with the CPU powered off. Check the slot and signal mode in HWCONFIG before testing.

In current mode, apply 4, 12 and 20 mA. The relevant SR should read approximately 0, 1000 and 2000.

Monitor the second channel while testing the first, and check the shared COM connection.

Before replacement, save the CPU project and record the card’s slot and scaling settings.