Delta AH08TC-5A
Delta AH08TC-5A 8-Channel Thermocouple Input Module
Delta AH08TC-5A is a temperature measurement module for Delta AH500 rack-based PLC systems. Its CH0–CH7 inputs accept type J, K, R, S, T, E and N thermocouples. Each channel can also be set to the ±150 mV voltage range. The module sends measurements from multi-zone equipment such as ovens and extruders to the PLC.
User manuals
AH500 Module Manual (PDF, English) · Chapter 6 covers channel setup, diagnostics and ISPSoft examples.
AH500 Hardware & Operation Manual (PDF, English) · See printed page 4-76 for wiring and page 5-19 for the addressing example.
Measurement and wiring
Temperature resolution is 0.1 °C / 0.1 °F. The specification table lists a conversion time of 200 ms per channel. The module input range is −100 to +1150 °C for type J and −100 to +1350 °C for type K. Check the probe’s own operating range as well.
On the removable terminal block, CH0 uses I0+ and I0−. Use shielded extension or compensating cable matched to the thermocouple type and route it away from drive output cables. The module provides cold-junction compensation and open-sensor detection.
ISPSoft and channel addressing
Scan the rack in HWCONFIG in ISPSoft and choose the input type for each channel. Connect the PC through a port supported by the CPU. For the connection profile, see COMMGR and the Delta PLC software section.
Each channel occupies two 16-bit D registers. If the start address is D0, CH0 uses D0–D1 and CH7 uses D14–D15. The start address is configurable in the project.
Editor’s note
When checking a second-hand unit, read the AH08TC-5A label and make sure the removable terminal block is included.
Inspect the terminal screws and rear rack connector. Loose terminals, corrosion or bent pins can cause intermittent readings.
On the bench, check all eight channels in turn with a known-good thermocouple or a suitable simulator.
Delta specifies a 30-minute warm-up before measurement. Once the module has warmed up, check that the reading is stable at a steady temperature.
If a reading is off, check the input type, polarity, extension cable and D register assignment before replacing the module.
Related topics
For four thermocouple channels, see the AH04TC-5A. When comparing Pt100 and thermocouple inputs, see the AH04PT-5A and AH08PTG-5A RTD options. For standard voltage or current signals, see the AH08AD-5A and AH04AD-5A in the AH analog module range.
For rack components, see AH expansion modules and AH power supplies. Compare the AHPS05-5A and AHPS15-5A against your rack’s power budget.