Hi everyone,
This passage describes how warnings and alarms are indicated and what actions can be taken to reset them. A warning is indicated by an LED and a code on the display, and remains active until the cause is resolved. An alarm results in the frequency converter tripping and requires resetting once the cause has been rectified. Alarms can be reset in four ways, including via a manual reset, digital input, or serial communication.
If
an alarm cannot be reset, it may be trip-locked, in which case the
mains supply must be switched off before it can be reset. Table 6.1
provides codes for warnings and alarms, and in some cases, it can
specify whether a warning or alarm is to be displayed. After an alarm or
trip, the motor coasts and both the warning and alarm flash. Once the
problem is resolved, only the alarm continues flashing.
AL 2: Live zero error It appears that you have provided a technical error message related to some system or device. The error message states that there is a "Live zero error" and the signal on terminal 53 or 60 is less than 50% of the value set. The specific parameters that are affected by this error are 6-10 (Terminal 53 Low Voltage), 6-12 (Terminal 53 Low Current), and 6-22 (Terminal 54 Low Current). It is recommended to consult the user manual or technical support for the system or device in question to troubleshoot and resolve this error.
AL 4: Mains phase loss The error message you provided indicates a "Mains phase loss" issue, which could be caused by a missing phase on the supply side or an excessively high voltage imbalance. To resolve this issue, you should first check the supply voltage and ensure that all phases are present and within the acceptable voltage range.
AL 7: DC over voltage The error message you provided indicates a "DC over voltage" issue, which occurs when the DC-link voltage exceeds the specified limit. This can be caused by a number of factors, such as a faulty power supply, a malfunctioning rectifier, or a failure in the voltage regulation system. To resolve this issue, you should first check the voltage levels and ensure that they are within the acceptable range.
AL 8: DC under voltage The error message you provided indicates a "DC under voltage" issue, which occurs when the DC-link voltage drops below the specified warning limit. This can be caused by a number of factors, such as a faulty power supply, a malfunctioning rectifier, or a failure in the voltage regulation system. To resolve this issue, you should first check the voltage levels and ensure that they are within the acceptable range.
AL 9: Inverter overloaded The error message you provided indicates an "Inverter overloaded" issue, which occurs when the load on the inverter exceeds its rated capacity for an extended period of time. This can be caused by a number of factors, such as a sudden increase in demand, a malfunctioning component, or improper load balancing. To resolve this issue, you should first reduce the load on the inverter to a level that is within its rated capacity. It is also recommended to investigate and address any underlying issues that may have contributed to the overload condition.
AL 10: Motor ETR overtemperature The error message you provided indicates a "Motor ETR overtemperature" issue, which occurs when the motor temperature exceeds the safe operating range due to prolonged operation at a load exceeding 100%. This can be caused by a number of factors, such as a blocked cooling system, a malfunctioning motor component, or an excessively high ambient temperature. To resolve this issue, you should first allow the motor to cool down and reduce the load to a level that is within its rated capacity. It is also recommended to investigate and address any underlying issues that may have contributed to the overtemperature condition, such as by checking the cooling system and ensuring proper ventilation of the motor.
AL 11: Motor thermistor overtemperature The error message you provided indicates a "Motor thermistor overtemperature" issue, which occurs when the temperature sensor (thermistor) or its connection becomes disconnected or fails. The thermistor is an important component that measures the motor temperature and sends a signal to the control system to regulate the motor operation. If the thermistor becomes disconnected or fails, it can cause the motor to overheat and trigger an overtemperature error. To resolve this issue, you should first check the thermistor and its connection to ensure that they are properly installed and functioning correctly.
AL 12: Torque limit The error message you provided indicates a "Torque limit" issue, which occurs when the torque output of the motor exceeds the specified limit set in either the "Torque Limit Motor Mode" or "Torque Limit Generator Mode" parameter (4-16 or 4-17). This can be caused by a number of factors, such as an excessive load, a malfunctioning component, or improper parameter settings. To resolve this issue, you should first check the load and ensure that it is within the rated capacity of the motor. It is also recommended to review the parameter settings and adjust them as necessary to ensure that the torque limit is set correctly.
AL 13: Overcurrent The error message you provided indicates an "Overcurrent" issue, which occurs when the peak current limit of the inverter is exceeded. This can be caused by a number of factors, such as a short circuit, a malfunctioning component, or an excessive load. To resolve this issue, you should first identify and address the underlying cause of the overcurrent condition, such as by checking the wiring and ensuring that the load is within the rated capacity of the inverter. It may also be necessary to reset the inverter or adjust the parameter settings to prevent future overcurrent conditions.
AL 14: Ground fault The error message you provided indicates a "Ground fault" issue, which occurs when there is an unintended discharge of current from the output phases of the system to ground. This can be caused by a number of factors, such as a faulty insulation system, a damaged component, or improper wiring. To resolve this issue, you should first ensure that the wiring is properly grounded and that there are no loose connections or damaged components. It may also be necessary to inspect the insulation system and identify any areas that may be compromised.
AL 16: Short circuit The error message you provided indicates a "Short circuit" issue, which occurs when there is a low-resistance connection between two points in the electrical circuit, such as in the motor or on the motor terminals. This can be caused by a number of factors, such as damaged insulation, loose connections, or a faulty component. To resolve this issue, you should first isolate the affected circuit and identify the location of the short circuit, such as by using a multimeter to measure the resistance. It may be necessary to repair or replace the damaged component or rework any loose connections. It is also recommended to inspect the insulation system and ensure that it is in good condition to prevent future short circuit conditions.
AL 17: Control word timeout The error message you provided indicates a "Control word timeout" issue, which occurs when there is a failure of communication between the control system and the frequency converter. This can be caused by a number of factors, such as a faulty communication cable, a malfunctioning component, or incorrect parameter settings. To resolve this issue, you should first check the communication cable and ensure that it is properly connected and functioning correctly. It is also recommended to review the parameter settings and adjust them as necessary to ensure that the communication settings are correct.
AL 25: Brake resistor short-circuited The error message you provided indicates a "Brake resistor short-circuited" issue, which occurs when the brake resistor in the system becomes short-circuited, causing the brake function to become disconnected. This can be caused by a number of factors, such as a damaged resistor, improper installation, or a faulty component. To resolve this issue, you should first isolate the affected circuit and identify the location of the short circuit in the brake resistor, such as by using a multimeter to measure the resistance. It may be necessary to repair or replace the damaged resistor or rework any loose connections. It is also recommended to inspect the brake system and ensure that it is in good condition to prevent future short circuit conditions.
AL 27: Brake chopper short-circuited The error message you provided indicates a "Brake chopper short-circuited" issue, which occurs when the brake transistor in the system becomes short-circuited, causing the brake function to become disconnected. This can be caused by a number of factors, such as a damaged transistor, improper installation, or a faulty component. To resolve this issue, you should first isolate the affected circuit and identify the location of the short circuit in the brake chopper transistor, such as by using a multimeter to measure the resistance. It may be necessary to repair or replace the damaged transistor or rework any loose connections. It is also recommended to inspect the brake system and ensure that it is in good condition to prevent future short circuit conditions.
AL 28: Brake check The error message you provided indicates a "Brake check" issue, which occurs when the brake resistor in the system is not connected or not working correctly. The brake resistor is an important component that helps to dissipate the energy generated by the motor during deceleration, and if it is not functioning correctly, it can cause issues with the motor operation. To resolve this issue, you should first check the brake resistor and its connections to ensure that they are properly installed and functioning correctly. It may also be necessary to check the parameter settings to ensure that the brake system is configured correctly.
AL 29: Power board over temp The error message you provided indicates a "Power board over temp" issue, which occurs when the heat sink of the power board reaches its maximum temperature and triggers a cutout. This can be caused by a number of factors, such as a blocked ventilation system, a malfunctioning cooling fan, or an excessively high ambient temperature. To resolve this issue, you should first allow the power board to cool down and ensure that the ventilation system is free from obstructions. It may also be necessary to inspect the cooling fan and ensure that it is functioning correctly.
+