Unidrive SP Fault codes 3

EnC15 Drive encoder fault: The number of periods per revolution calculated from encoder data during auto-configuration is either less than 2 or greater than 50,000

- The linear motor pole pitch/encoder ppr setup is incorrect or out of parameter range (e.g., Pr 5.36 = 0 or Pr 21.31 = 0).
- The encoder may be faulty.

EnC16 Drive encoder fault: EnDat encoder - The number of communication bits per period for a linear encoder exceeds 255

- Select a different type of encoder.
- The encoder may be faulty.

EnC17 Drive encoder fault: The periods per revolution obtained during auto-configuration for a rotary SINCOS encoder is not a power of two

- Select a different type of encoder.
- The encoder may be faulty.

ENP.Er Data error from the electronic nameplate stored in the selected feedback device

- Replace the feedback device.

Et External trip

- Check terminal 31 signal.
- Check the value of Pr 10.32.
- Enter 12001 in Pr xx.00 and check the parameter controlling Pr 10.32.
- Ensure that Pr 10.32 or Pr 10.38 (=6) are not being controlled by serial communications.

HF01 Data processing error: CPU address error

- Hardware fault - return the drive to the supplier.

HF02 Data processing error: DMAC address error

- Hardware fault - return the drive to the supplier.

HF03 Data processing error: Illegal instruction

- Hardware fault - return the drive to the supplier.

HF04 Data processing error: Illegal slot instruction

- Hardware fault - return the drive to the supplier.

HF05 Data processing error: Undefined exception

- Hardware fault - return the drive to the supplier.

HF06 Data processing error: Reserved exception

- Hardware fault - return the drive to the supplier.

HF07 Data processing error: Watchdog failure

- Hardware fault - return the drive to the supplier.

HF08 Data processing error: Level 4 crash

- Hardware fault - return the drive to the supplier.

HF09 Data processing error: Heap overflow

- Hardware fault - return the drive to the supplier.

HF10 Data processing error: Router error

- Hardware fault - return the drive to the supplier.

HF11 Data processing error: EEPROM access failure

- Hardware fault - return the drive to the supplier.

HF12 Data processing error: Main program stack overflow

- Hardware fault - return the drive to the supplier.

HF13 Data processing error: Software incompatible with hardware

- Hardware or software fault - return the drive to the supplier.

HF17 Multi-module system thermistor short circuit or open circuit

- Hardware fault - return the drive to the supplier.

HF18 Multi-module system interconnect cable error

- Hardware fault - return the drive to the supplier.

HF19 Temperature feedback multiplexing failure

- Hardware fault - return the drive to the supplier.

HF20 Power stage recognition: Serial code error

- Hardware fault - return the drive to the supplier.

HF21 Power stage recognition: Unrecognized frame size

- Hardware fault - return the drive to the supplier.

HF22 Power stage recognition: Multi-module frame size mismatch

- Hardware fault - return the drive to the supplier.

HF23 Power stage recognition: Multi-module voltage or current rating mismatch

- Hardware fault - return the drive to the supplier.

HF24 Power stage recognition: Unrecognized drive size

- Hardware fault - return the drive to the supplier.

HF25 Current feedback offset error

- Hardware fault - return the drive to the supplier.

HF26 Soft start relay failed to close, soft start monitor failure, or braking IGBT short circuit at power-up

- Hardware fault - return the drive to the supplier.

HF27 Power stage thermistor 1 fault

- Hardware fault - return the drive to the supplier.

HF28 Power stage thermistor 2 fault, or internal fan fault (size 3)

- Hardware fault - return the drive to the supplier.

HF29 Control board thermistor fault

- Hardware fault - return the drive to the supplier.

HF30 DCCT wire break trip from power module

- Hardware fault - return the drive to the supplier.

HF31 Internal capacitor bank fan failure (size 4 and larger) or a module has not powered up in a multi-module parallel drive

- Check the AC or DC power supply to all modules in the multi-module parallel drive.
- If the AC or DC power supply is present, or if this is a single drive, then there is a hardware fault - return the drive to the supplier.

HF32 Power stage: Identification and trip information serial code error

- Hardware fault - return the drive to the supplier.