ATV 11 Fault codes


Preventive Maintenance for Altivar 11:

* Regularly check the condition and tightness of connections to ensure they are secure.
* Monitor the temperature around the unit and make sure that ventilation is effective. The average service life of fans is 3 to 5 years, depending on operating conditions.
* Remove any dust from the drive to maintain its performance.

Troubleshooting:

- If a problem arises during setup or operation, check that the recommendations relating to the environment, mounting, and connections have been followed.
- The first fault detected is stored and displayed on the screen. The drive locks, and the fault relay (RA - RC) contact opens.
- In the event of a non-resettable fault, cut the power supply to the drive, wait for the display to go off completely, and then find and correct the cause of the fault. Restore the power supply to clear the fault if it has disappeared.
- In some cases, there may be an automatic restart after the fault has disappeared if this function has been programmed.

Common Faults and Remedies:

    Overcurrent (OCF):
- Causes: Ramp too short, inertia or load too high, mechanical locking.
+ Remedies: Check the settings, motor/drive/load size, and the state of the mechanism.

    Motor Short-Circuit (SCF):
+ Cause: Insulation fault or short-circuit at the drive output.
+ Remedy: Check the cables connecting the drive to the motor and the motor insulation.

    Internal Fault (InF):
+ Cause: Internal fault within the drive.
+ Remedy: Check the environment for electromagnetic compatibility and consider sending the drive for repair.

    Configuration Fault (CFF):
+ Cause: The current configuration is inconsistent.
+ Remedy: Return to factory settings or call up the backup configuration if valid.

    Overspeed (SOF):
- Causes: Instability or driving load too high.
+ Remedies: Check motor, gain, and stability parameters. Consider adding a braking resistor and module.

    Drive Overload (OHF):
+ Cause: Drive temperature too high.
+ Remedy: Check the motor load, drive ventilation, and environment. Wait for the drive to cool down before restarting.

    Motor Overload (OLF):

+ Cause: Triggered by motor current too high.
+ Remedy: Check the setting of the motor thermal protection and the motor load. Wait for the drive to cool down before restarting.

    Overvoltage (OSf):
- Causes: Line voltage too high or disturbed line supply.
+ Remedy: Check the line voltage. The overvoltage threshold is typically around 415 V on the DC bus.

    Overvoltage during Deceleration (ObF):
- Causes: Braking too sudden or driving load.
+ Remedies: Increase the deceleration time, install a braking module and resistor if necessary, and activate the braking function if compatible with the application.

    Line Phase Failure (PHF):
- Causes: Drive incorrectly supplied, a fuse blown, or failure of one phase.
+ Remedy: Check the power connection and fuses. Reset the drive, and ensure it's used with a 3-phase line supply.

    Undervoltage (USF):
- Causes: Line supply too low or transient voltage dip.
+ Remedy: Check the voltage and the voltage parameter. The undervoltage threshold is typically around 230 V on the DC bus.

These faults can often be reset by switching the drive off and on again. For persistent issues, it's important to identify and address the underlying cause to prevent future occurrences.