Abb Acs355 fault codes 1

Alarm and fault indications
Fault is indicated with a red LED. See section LEDs on page 356.
An alarm or fault message on the panel display indicates abnormal drive status.
Using the information given in this chapter, most alarm and fault causes can be identified and corrected. If not, contact an ABB representative.
The four digit code number in parenthesis after the fault is for the fieldbus communication. See chapters Fieldbus control with embedded fieldbus on page 301 and Fieldbus control with fieldbus adapter on page 325.

How to reset
The drive can be reset either by pressing the keypad key (basic control panel) or (assistant control panel), through digital input or fieldbus, or by switching the supply voltage off for a while. The source for the fault reset signal is selected by EXIT/RESET
336 Fault tracing parameter 1604 FAULT RESET SEL. When the fault has been removed, the motor can be restarted.

Fault history
When a fault is detected, it is stored in the fault history. The latest faults are stored together with the time stamp.
Parameters 0401 LAST FAULT, 0412 PREVIOUS FAULT 1 and 0413 PREVIOUS FAULT 2 store the most recent faults. Parameters 0404...0409 show drive operation data at the time the latest fault occurred. The assistant control panel provides
additional information about the fault history. See section Fault logger mode on page 101 for more information.


2001 OVERCURRENT 0308 bit 0
(programmable fault function 1610)
Output current limit controller is active.
Check motor load.
Check acceleration time (2202 and 2205).
Check motor and motor cable (including phasing).
Check ambient conditions. Load capacity decreases if installation site ambient temperature exceeds 40 °C.
See section Derating on page 319.
--------------
2002 OVERVOLTAGE 0308 bit 1
(programmable fault function 1610)
DC overvoltage controller is active.
Check deceleration time (2203 and 2206).
Check input power line for static or transient overvoltage.
--------------
2003 UNDERVOLTAGE 0308 bit 2
(programmable fault function 1610)
DC undervoltage controller is active.
Check input power supply.
--------------
2004 DIR LOCK 0308 bit 3
Change of direction is not allowed.
Check parameter 1003 DIRECTION settings.
--------------
2005 IO COMM 0308 bit 4
(programmable fault function 3018, 3019)
Fieldbus communication break
Check status of fieldbus communication. See chapter Fieldbus control with embedded fieldbus on page 271.
Check fault function parameter settings.
Check connections.
Check if master can communicate.
--------------
2006 AI1 LOSS 0308 bit 5
(programmable fault function 3001, 3021)
Analog input AI1 signal has fallen below limit defined by parameter
--------------
3021 AI1 FAULT LIMIT.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
--------------
2007 AI2 LOSS 0308 bit 6
(programmable fault function 3001, 3022)
Analog input AI2 signal has fallen below limit defined by parameter
3022 AI2 FAULT LIMIT.
Check fault function parameter settings.
Check for proper analog control signal levels.
Check connections.
--------------
2008 PANEL LOSS 0308 bit 7
(programmable fault function 3002)
Control panel selected as active control location for drive has ceased communicating.
Check panel connection.
Check fault function parameters.
Check control panel connector.
Refit control panel in mounting platform. If drive is in external control mode (REM) and is set to accept start/stop, direction commands or references through control panel:
Check group 10 START/STOP/DIR and 11 REFERENCE SELECT settings.
--------------
2009 DEVICE OVERTEMP 0308 bit 8
Drive IGBT temperature is excessive. Alarm limit is 120 °C.
Check ambient conditions. See also section Derating on page 319.
Check air flow and fan operation.
Check motor power against unit power.
--------------
2010 MOTOR TEMP 0305 bit 9
(programmable fault function 3005…3009 / 3503)
Motor temperature is too high (or appears to be too high) due to excessive load, insufficient motor power, inadequate cooling or incorrect start-up data.
Check motor ratings, load and cooling.
Check start-up data.
Check fault function parameters.
Measured motor temperature has exceeded alarm limit set by parameter 3503 ALARM LIMIT.
Check value of alarm limit.
Check that actual number of sensors corresponds to value set by parameter (3501 SENSOR TYPE).
Let motor cool down.
Ensure proper motor cooling:
Check cooling fan, clean cooling surfaces, etc.
--------------
2012 MOTOR STALL 0308 bit 11
(programmable fault function 3010…3012)
Motor is operating in stall region due to eg excessive load or insufficient motor power.
Check motor load and drive ratings.
Check fault function parameters.
--------------
2013   AUTORESET 0308 bit 12
Automatic reset alarm Check parameter group 31 AUTOMATIC RESET settings.
--------------
2014  AUTOCHANGE 0308 bit 13
PFC Autochange function is active.
See parameter group 81 PFC CONTROL, section PFC control macro on page 110 and section SPFC control macro on page 111.
--------------
2015 PFC I LOCK 0308 bit 14
PFC Interlocks are active.
Drive cannot start
• any motor (when Autochange is used)
• the speed regulated motor (when Autochange is not used).
See parameter group 81 PFC CONTROL.
--------------
2018 PID SLEEP 0309 bit 1
Sleep function has entered sleeping mode.
See parameter groups 40 PROCESS PID SET 1… 41 PROCESS PID SET 2.
--------------
2021 START ENABLE MISSING 0309 bit 4
No Start enable 1 signal received
Check parameter 1608 START ENABLE 1 settings.
Check digital input connections.
Check fieldbus communication settings.
--------------
2022 START ENABLE 2 MISSING 0309 bit 5
No Start enable 2 signal received
Check parameter 1609 START ENABLE 2 settings.
Check digital input connections.
Check fieldbus communication settings.
--------------
2023 EMERGENCY STOP 0309 bit 6
Drive has received emergency stop command and ramps to stop according to ramp time defined by parameter 2208 EMERG DEC TIME.
Check that it is safe to continue operation.
Return emergency stop push button to normal position.
--------------
2025 FIRST START 0309 bit 8
Motor identification magnetization is on.
This alarm belongs to normal start-up procedure.
Wait until drive indicates that motor identification is completed.
--------------
2026 INPUT PHASE LOSS 0306 bit 5
(programmable fault function 3016)
Intermediate circuit DC voltage is oscillating due to missing input ower line phase or blown fuse.
Alarm is generated when DC voltage ripple exceeds 14% of nominal DC voltage.
Check input power line fuses.
Check for input power supply imbalance.
Check fault function parameters.
--------------
2027 USER LOAD CURVE 0309 bit 10
Condition defined by 3701 USER LOAD C MODE has been valid longer than half of the time set by 3703 USER LOAD C TIME.
See parameter group 37 USER LOAD CURVE.
--------------
2028 START DELAY 0309 bit 11
Start delay in progress See parameter 2113 START DELAY.
--------------
2030 INLET LOW 0309 bit 13
Pressure at pump/fan inlet too low
Check for a closed valve on the inlet side of the pump/fan.
Check piping for leaks.
See parameter group 44 PUMP PROTECTION.
--------------
2031 OUTLET HIGH 0309 bit 14
Pressure at pump/fan outlet too high
Check piping for blocks.
See parameter group 44 PUMP PROTECTION.
--------------
2032 PIPE FILL 0309 bit 15
Pipe fill in progress See parameters 4421…4426.
--------------
2033 INLET VERY LOW 0310 bit 0
Pressure at pump/fan inlet too low
Check for a closed valve on the inlet side of the pump/fan.
Check piping for leaks.
See parameter group 44 PUMP PROTECTION.
--------------
2034 OUTLET VERY HIGH 0310 bit 1
Pressure at pump/fan outlet too high
Check piping for blocks.
See parameter group 44 PUMP PROTECTION.
--------------
Alarms generated by the Basic Control Panel
 
5001 Drive is not responding. Check panel connecion.

5002 Incompatible communication profile. Contact our Abb product representative (contact information available on the Abb homepage).

5010 Corrupted panel parameter backup file Retry parameter upload. Retry parameter download.

5011 Drive is controlled from another source. Change drive control to local control mode.

5012 Direction of rotation is locked. Enable change of direction. See parameter 1003 DIRECTION.

5013 Panel control is disabled because start inhibit is active. Start from the panel is not possible. Reset the emergency stop command or remove the 3-wire stop command before starting from the panel.
See section 3-wire macro on page 105 and parameters 1001 EXT1 COMMANDS, 1002 EXT2 COMMANDS and 2109 EMERG STOP SEL.

5014 Panel control is disabled because of drive fault. Reset drive fault and retry.

5015 Panel control is disabled because local control mode lock is active. Deactivate local control mode lock and retry. See parameter 1606 LOCAL LOCK.

5018 Parameter default value is not found.  Contact our Abb product representative (contact information available on the Abb homepage)..

5019 Writing non-zero parameter value is prohibited. Only parameter reset is allowed.

5020 Parameter or parameter group does not exist or parameter value is inconsistent.  Contact our Abb product representative (contact information available on the Abb homepage)..

5021 Parameter or parameter group is hidden.  Contact our Abb product representative (contact information available on the Abb homepage)..

5022 Parameter is write protected. Parameter value is read-only and cannot be changed.

5023 Parameter change is not allowed, when drive is running. Stop drive and change parameter value.

5024 Drive is executing task. Wait until task is completed.

5025 Software is being uploaded or downloaded. Wait until upload/download is complete.

5026 Value is at or below minimum limit.  Contact our Abb product representative (contact information available on the Abb homepage)..

5027 Value is at or above maximum limit.  Contact our Abb product representative (contact information available on the Abb homepage)..

5028 Invalid value  Contact our Abb product representative (contact information available on the Abb homepage)..

5029 Memory is not ready. Retry.

5030 Invalid request  Contact our Abb product representative (contact information available on the Abb homepage)..

5031 Drive is not ready for operation, eg due to low DC voltage. Check input power supply.

5032 Parameter error  Contact our Abb product representative (contact information available on the Abb homepage)..

5040 Parameter download error. Selected parameter set is not in current parameter backup file. Perform upload function before download.

5041 Parameter backup file does not fit into memory.  Contact our Abb product representative (contact information available on the Abb homepage)..

5042 Parameter download error. Selected parameter set is not in current parameter backup file. Perform upload function before download.

5043 No start inhibit

5044 Parameter backup file restoring error . Check that file is compatible with drive.

5050 Parameter upload aborted Retry parameter upload.

5051 File error  Contact our Abb product representative (contact information available on the Abb homepage)..

5052 Parameter upload has failed. Retry parameter upload.

5060 Parameter download aborted. Retry parameter download.

5062 Parameter download has failed. Retry parameter download.

5070 Panel backup memory write error.  Contact our Abb product representative (contact information available on the Abb homepage)..

5071 Panel backup memory read error .  Contact our Abb product representative (contact information available on the Abb homepage)..

5080 Operation is not allowed because drive is not in local control mode. Switch to local control mode.

5081 Operation is not allowed because of active fault. Check cause of fault and reset fault.

5083 Operation is not allowed because parameter lock is on. Check parameter 1602 PARAMETER LOCK setting.

5084 Operation is not allowed because drive is performing task. Wait until task is completed and retry.

5085 Parameter download from source to destination drive has failed. Check that source and destination drive types are same, ie ACS310. See the type designation label of the drive.

5086 Parameter download from source to destination drive has failed. Check that source and destination drive type designations are the same. See type designation labels of the drives.

5087 Parameter download from source to destination drive has failed because parameter sets are incompatible. Check that source and destination drive information are same. See parameters in group 33 INFORMATION.

5088 Operation has failed because of drive memory error.  Contact our Abb product representative (contact information available on the Abb homepage)..

5089 Download has failed because of CRC error.  Contact our Abb product representative (contact information available on the Abb homepage)..

5090 Download has failed because of data processing error.  Contact our Abb product representative (contact information available on the Abb homepage)..

5091 Operation has failed because of parameter error.  Contact our Abb product representative (contact information available on the Abb homepage)..

5092 Parameter download from source to destination drive has failed because parameter sets are incompatible. Check that source and destination drive information are same. See parameters in group 33 INFORMATION.

++ ABB ACS 350 User manual / files

++ Dear visitor, you can discuss possible warnings and basic commissioning questions(s) you may encounter while using ABB products with our product representatives on the ABB homepage.

- However, the technical support we have declared here is only valid for the products sold in the automation avm. Please, we ask you to be sensitive in this matter.

++ Abb Acs355 fault code 2 >>