6EW1890-2AC
Siemens 6EW1890-2AC MPS Main Power Supply Unit
Siemens 6EW1890-2AC is listed in product records as an MPS 393769 main power supply unit for the 6SC36/37, 6SE35/36 and 6SE51/52 converter groups. When selecting this power supply module for an older Siemens automation installation, check both its complete order number and the exact converter identification.
This component belongs within the converter supply arrangement. Siemens describes the 6SE35/36 and 6SC36/37 SIMOVERT P families as PWM converters with a voltage-source DC link. These system characteristics do not establish the input or output ratings of the 6EW1890-2AC module itself.
Distinction from a standard SITOP supply
Its location in our Siemens power supply catalogue does not make this module interchangeable with a standard SITOP power supply. Matching the voltage and current of a DIN rail power supply alone is insufficient for a converter-specific module. Connector assignments, mechanical construction and the requirements of the connected circuits must also match.
Electrical ratings and connections
Determine input voltage, individual output rails, permissible load current and connector assignments from the module markings, the exact converter schematic and verified service documentation. A detailed manufacturer connection table for this complete part number was not obtained, so no estimated voltage, current or pin assignments are stated here.
Photograph connector positions and cable identifiers before removal. After isolating the equipment, safely discharging stored energy and verifying the absence of voltage with a suitable measuring instrument, inspect the connectors. Discoloured contacts, loose connections and incorrectly matched plugs should be considered when investigating a short circuit.
Inspection before repair
With the board de-energised, check any diodes and resistors identified in the actual circuit against its schematic. Parallel paths can affect in-circuit measurements, so a single low resistance reading is not a conclusive fault diagnosis. Investigate the connected load and surrounding components before replacing a burnt part.
Look for leakage, deformation and heat damage on electrolytic capacitors; a normal appearance does not prove that a component is healthy. If a MOSFET switching device is identified, test it according to its actual part number and connections. This is conditional inspection guidance, not a claim that every 6EW1890-2AC revision uses the same semiconductor.
Inspect the transformer, other magnetic components, connector pins and power-carrying solder joints under magnification. Where cracked joints, damaged tracks or previous modifications are found, narrow down the faulty section by measurement rather than replacing electronic components indiscriminately. Preserve insulation clearances and original mechanical supports.
Protection and operating checks
Never bridge an open fuse. Match the specified fuse type, breaking capacity and fast or slow operating characteristic to the original service information. If protection operates again, stop testing and investigate the supply and connected load separately; fitting a larger fuse is not a repair.
Before operation, check protective earthing connections and any mechanical parts removed during service. For intermittent operation, investigate incoming voltage fluctuations, cable contacts and connected loads as well as the supply module. Energised testing requires qualified personnel, suitable equipment and the converter-specific service procedure.
When buying a used power supply, request the complete label, board revision, connector condition, repair history and details of the equipment used for testing. Similar-looking suffix variants must not be assumed interchangeable. An output measured without load and stable operation under the actual converter load are separate test results.
Editor’s Note
Start with the exact identity. Do not choose this unit simply because it is described as a Siemens power supply. Compare the complete label, connectors and board revision with the original. Treat a suffix difference as something to verify against a schematic or manufacturer replacement record.
Look beyond an open fuse. Before installing a replacement, investigate shorted loads and damaged wiring connected to the module. Repairing the supply while leaving an external fault in place can lead to another failure. Assess the module and the circuits it feeds together.
Do not judge capacitors by appearance alone. A swollen component is suspicious, but an apparently normal one may also need measurement. Check capacitance and ESR with suitable equipment, then select replacements for the required voltage, temperature, ripple current and physical dimensions.
A no-load start is only the beginning. Establish the verified supply and connection requirements first. Then use only loads permitted by the service procedure to assess output stability, heating and cold and warm restarts. Applying an arbitrary load before identifying the output ratings is not a valid test.
Choose the oscilloscope reference carefully. For ripple measurements, use a differential probe or suitable isolated measurement system with adequate voltage and common-mode ratings. Do not attach a bench oscilloscope earth clip to an unknown-potential circuit node or disconnect the instrument protective earth.
Ask what “tested” actually means. Request the host converter, loading conditions and test duration rather than accepting a general working claim. Obtain clear label and connector photographs. To offer a unit for sale, send its complete code, quantity and known condition to otomasyonavm@gmail.com.
OtomasyonAVM Resources and PDFs
Browse our Siemens power supply model directory and SITOP information page for related records.
Siemens SITOP files is the common document directory for this project.
Siemens SINAMICS Engineering Manual — SIMOVERT P system context (English, July 2017, V6.5; 556 PDF pages; approximately 14.3 MiB). Section 3.8.2 on PDF page 294 describes the 6SE35/36 and 6SC36/37 families. This is not a pinout or a dedicated service manual for 6EW1890-2AC.
Related Topics
Multimeter measurements, capacitors, short circuits and earthing are useful background topics when preparing maintenance work.
Browse Siemens Power Supplies
+ Siemens second-hand catalogue
Siemens and External References
Siemens SINAMICS Engineering Manual, V6.5, July 2017 — manufacturer documentation for converter-family context.
6EW1890-2AC original label and connector photographs — photographs of a seller’s example unit; its stated condition is not a test result for our stock.
6EW1890-2AC product identification record — MPS 393769 and converter-group identification; not a substitute for a detailed manufacturer datasheet.