6ES7 133-0BN01-0XB0
6ES7 133-0BN01-0XB0 – Siemens ET 200B 24 DI / 8 DO
Series: SIMATIC ET 200B
Category: 24 V DC digital input/output electronics block
Function and system role
6ES7 133-0BN01-0XB0 is an ET 200B electronics block in the Siemens ET 200 family, providing 24 digital inputs and 8 digital outputs. It exchanges machine signals with the host controller over PROFIBUS DP. The PLC executes the control program, while this block provides distributed connections for field inputs and outputs.
24 digital inputs and 3 ms delay
The inputs are rated for 24 V DC. The specified signal ranges are 13–30 V for “1” and −30 to +5 V for “0”. The maximum input delay for a “0” to “1” transition is 3 ms. When choosing sensors or inductive proximity sensors, check both the output type and signal duration. A fast PROFIBUS connection alone does not guarantee that a short pulse will be detected.
The distinction between 0BN01 and 0BN11 matters: 6ES7 133-0BN11-0XB0 is the version with a 0.2 ms input delay. Their matching 24 DI / 8 DO channel counts do not imply identical behaviour in applications with fast input signals.
8 digital outputs and total current
The outputs are rated for 24 V DC, up to 0.5 A per channel, with electronic short-circuit protection. The total load current for the group of eight outputs must not exceed 2 A. Consequently, the eight channels must not all be loaded at 0.5 A simultaneously to obtain a 4 A total.
When selecting a valve coil, relay or contactor, consider its pickup current as well as its continuous current. Establish which loads operate together during the machine sequence before calculating the group load. An illuminated output LED alone does not establish that the connected device receives the required voltage and current.
Terminal block and power supply
This part is the electronics block; field wiring is connected through a suitable ET 200 terminal block. The Siemens product data sheet lists TB2/DC, TB2-4/DC, TB4/DC and TB4-4/DC. Before ordering, check whether the terminal block is included, and compare the full designation and wiring arrangement of the existing base.
The rated supply is 24 V DC, with a permissible continuous operating range of 18.5–30.2 V DC. L5+ serves the electronics/sensor side, while L1+ supplies the output loads. Include both circuits when assessing power supply capacity. Before choosing a DIN rail power supply, compare the installed cables, protective devices and terminals with the module wiring diagram.
PROFIBUS configuration and diagnostics
The maximum communication rate is 12 Mbit/s; the actual network rate also depends on the master and network installation. SYNC and FREEZE are supported. This is a PROFIBUS DP device and cannot be added directly as a PROFINET device. When planning a network conversion, review the differences between ET 200 PROFIBUS and PROFINET systems.
Select the GSD or hardware entry for the exact model. The Siemens manual assigns Ident_Number 000FH to 0BN01; 0BN11 has a different identity. Compare the station address and the PLC program’s I/O mapping with the existing project.
BF indicates a bus fault, while DIA assists with group diagnostics such as a short circuit or missing load voltage. Also inspect the RUN and L1+ indicators. If communication is established but loads do not operate, measure the load supply, output voltage and return circuit. Changing network settings alone may not address the fault.
Cabinet installation
The electronics block and terminal block together measure 235 × 130 × 60 mm. The protection rating is IP20. The specified operating temperature is 0–60 °C for horizontal installation, with a maximum of 40 °C for other mounting positions. Allow for cable routing and maintenance access when using these dimensions in the cabinet layout.
Editor’s Note
Do not select a replacement solely by its “24 inputs, 8 outputs” description. Check the 0BN01 suffix, 3 ms input delay, terminal block and 2 A total output limit together. During fault finding, inspect the base connections and measure the L1+ load supply before concluding that the electronics block has failed. Testing under conditions representative of the machine’s actual loads gives more useful evidence than an LED check alone.