6ES7 133-0BN00-0XB0

Siemens 6ES7 133-0BN00-0XB0 – ET 200B 24 DI / 8 DO

The 6ES7 133-0BN00-0XB0 is an electronics block with 24 digital inputs and 8 digital outputs for the ET 200B distributed I/O system, part of the Siemens ET 200 family. Inputs and output loads operate at 24 V DC. The station exchanges data with the main PLC over PROFIBUS DP, providing local field connections where more sensor inputs than control outputs are required.

24 inputs with a 3 ms delay

The digital inputs read switches and suitable proximity sensors. This model has a specified 3 ms input delay. The 6ES7 133-0BN10-0XB0 has a 0.2 ms delay despite having the same channel count. This order-number distinction matters when monitoring short pulses.

Input delay, PLC scan time and communication time are separate quantities. Raising the PROFIBUS baud rate alone may not resolve missed sensor pulses. For encoders or high-speed pulse acquisition, assess suitable counter modules. This device occupies 3 input bytes and 1 output byte in the configured I/O address space.

Individual and aggregate output current

Each of the eight digital outputs supports up to 0.5 A at 24 V DC. However, the aggregate load current of all eight outputs must not exceed 2 A. Eight simultaneous 0.5 A loads would draw 4 A and exceed this limit. Multiplying the individual channel rating by the output count does not establish the permissible aggregate current.

The outputs provide short-circuit protection, but load calculations and suitable circuit protection remain necessary. These are not volt-free relay contacts. Check coil voltage, inrush current and switching frequency when selecting solenoids or contactors.

Power supplies and isolation

The nominal supply is 24 V DC, with a specified permitted range of 18.5–30.2 V DC. L5+/M5 supplies the electronics and sensors, while L1+/M1 supplies the output group. The positive and return terminals of these two supplies are not internally interconnected. Plan the power supply and power distribution accordingly.

The inputs are not galvanically isolated from the internal electronics. The outputs are isolated as one group of eight, and isolation is also provided on the PROFIBUS side. This does not mean that each individual channel is isolated from every other channel.

Terminal blocks and installation

The electronics block plugs into a terminal block carrying the field wiring. The model-specific manual lists TB2/DC – 6ES7 193-0CB10-0XA0, TB2-4/DC – 6ES7 193-0CB20-0XA0 and TB4/DC – 6ES7 193-0CB30-0XA0. The first two use screw terminals; TB4/DC uses spring terminals.

As permanent wiring remains on the terminal block, establish whether a spare is needed for the electronics, the base or both. Include the relevant connection parts and accessories in that check. The manual specifies 235 × 130 × 60 mm for the electronics block and terminal block together; these dimensions do not describe the detached electronics block alone.

PROFIBUS and configuration

PROFIBUS DP supports rates of up to 12 Mbit/s with a suitable master. With an IM 308-B, the maximum is 1.5 Mbit/s. Station numbers selected on the terminal block range from 3 to 99 with IM 308-B, or 1 to 99 with IM 308-C and S7/M7 DP masters. An address change is accepted during the station's STOP-to-RUN transition.

The configured device, I/O addresses and physical station number must match the installed hardware. Different ET 200 communication interfaces support different protocols; this device has no PROFINET port.

Indicators and fault checks

RUN indicates electronics power and operating status, BF indicates a bus fault, and DIA reports group diagnostics such as a short circuit or missing load voltage. L1+ monitors output-group power. If RUN is lit but loads remain off, check the L1+ supply, connected loads and station diagnostics alongside communication status.

Editor's Note: The full order number, terminal block and aggregate output current are the three key checks when selecting a spare. The 0BN00 and 0BN10 do not have the same input response. Also, “8 outputs × 0.5 A” does not permit a 4 A load: the aggregate limit is 2 A. Record the station address, wire labels and existing project settings before replacement.

Manuals and technical references

For wiring diagrams and diagnostics, visit Siemens ET 200 manuals and PDF documents. Main reference: Siemens ET 200B Distributed I/O Station, Edition 3, EWA 4NEB 812 6089-02b, section 8.1.11, pages 8-49–8-53. System and master information was also checked against Edition 04, EWA 4NEB 812 6089-02c.

Related topics

ET 200 families · HMI and operator panels · SCADA systems. When investigating an operator-panel alarm, compare the main PLC's diagnostic records with the remote station's LED indications.

Navigation: Siemens automation · SIMATIC S7 · Siemens ET 200 · OtomasyonAVM home