6ES7 132-0BL01-0XB0
Siemens main menu › SIMATIC S7 family › ET 200 › Digital output modules
6ES7 132-0BL01-0XB0 — Siemens ET 200B-32DO, 24 V DC / 0.5 A Digital Output Block
6ES7 132-0BL01-0XB0 is the ET 200B-32DO electronics block in the Siemens SIMATIC product family. It provides 32 digital outputs at 24 V DC, rated up to 0.5 A per channel. When selecting this product within the ET 200 distributed I/O family, check the ET 200B series, terminal base and eight-channel output groups together.
Five checks before selection
1. Series and communication: Do not match ET 200 digital output modules by channel count alone. This device uses PROFIBUS DP at up to 12 Mbit/s. When comparing PROFIBUS and PROFINET options, use the device’s actual interface as your starting point. In the Siemens S7 control system project, compare the station address, device configuration and output addresses with the existing installation.
2. Channel current and group limit: The outputs form four electrically isolated groups of eight. Each channel supports up to 0.5 A, but the combined current per group must not exceed 2 A. Plan load and power distribution around actuators operating simultaneously; loading all eight channels in a group at 0.5 A is not permitted.
3. Electronics block and terminal base: TB2/DC, TB2-4/DC and TB4/DC are among the compatible bases listed in the manufacturer’s documentation. Record the complete base designation when reviewing ET 200 terminal blocks. The electronics block and terminal base are separate components; check the scope of supply individually. Match field connection components and terminal arrangements to the wiring diagram for the selected base.
4. Supply arrangement: The nominal supply is 24 V DC, with a permissible range of 18.5–30.2 V DC. L1+–L4+ supply the load groups; L5+ supplies the internal logic. The L+ and M connections of different groups are not internally interconnected. Keep this separation in mind when reviewing ET 200 power supply options. If the station communicates but some outputs do not operate, also measure the supply to the affected group.
5. Maintenance and cabinet layout: RUN monitors supply/operation, BF indicates a bus fault, and DIA provides group diagnostics for short circuits or missing load voltage. An output LED alone does not confirm actuator movement; monitor digital input feedback signals where required. The 235 × 130 × 60 mm dimensions apply to the electronics block and terminal base combined. For the IP20 assembly, observe 0–60 °C with horizontal installation and a maximum of 40 °C for other mounting orientations.
Editor’s note
Example: Eight loads drawing 0.3 A each in the same group require 2.4 A when operated together. Each load is below the channel rating, yet the group limit is exceeded. Prepare the load schedule by group and simultaneous operating condition, as well as by channel, and account for pickup currents.
PDF and technical documentation
Visit the Siemens ET 200 PDF and user manual library for the documentation guide. For this model, use the 6ES7132-0BL01-0XB0 datasheet and section 7.3.5, printed pages 7-38–7-43, of ET 200B Distributed I/O Station, EWA 4NEB 812 6089-02c. Check terminal assignments against both the installed base label and the cabinet drawings.
Related topics
Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules