6ES7 131-4BB00-0AB0

Siemens 6ES7 131-4BB00-0AB0 – ET 200S 2 DI 24 V DC High Feature Input Module

Siemens 6ES7 131-4BB00-0AB0 is a 2-channel, 24 V DC High Feature digital input module for SIMATIC ET 200S stations. It transfers switching states from pushbuttons, limit switches and compatible sensors to the control system. The 15 mm wide electronic module works with the ET 200S terminal and interface arrangement within the Siemens ET 200 family.

For this model, High Feature includes selectable input delay, sensor supply short-circuit diagnostics and hardware interrupt capability in a suitable configuration. When selecting a digital input module, the required response and diagnostic behaviour matter alongside the number of channels.

Input levels and sensor selection

The inputs have an IEC 61131 Type 1 characteristic. The specified voltage range is −30 to +5 V for signal “0” and +11 to +30 V for signal “1”. Typical active-state input current is 8 mA. Voltages between +5 V and +11 V should not be used to establish a defined logic state.

Suitable contacts and PNP-output sensors that apply a positive voltage to the input can be used with this arrangement. When choosing an inductive proximity sensor, check supply voltage, output type and NO/NC behaviour together. Understanding PNP and NPN output compatibility helps explain why two sensors operating at the same voltage may require different input circuits.

Compatible two-wire BERO sensors are supported, with a maximum permitted quiescent current of 1.5 mA. The sensor’s off-state residual current and on-state voltage drop should be checked against the input requirements.

Selectable input delay and event processing

Input delay can be set to 0.1 ms, 0.5 ms, 3 ms or 15 ms. The setting applies at module level and affects both signal transitions; the manual specifies a default of 3 ms. A shorter delay helps evaluate shorter signals, while a longer delay can reduce the effect of brief disturbances or contact bounce. Selection should follow the actual signal duration in the application.

A 0.1 ms input delay does not mean a total PLC response time of 0.1 ms. Interface communication and execution of the PLC program also affect the result. With a compatible interface and configuration, the module can generate a hardware interrupt on a rising edge. Using this function requires both the input parameters and the controller’s interrupt handling to be configured.

The module also supports isochronous operation. The controller, station interface and communication configuration must support the required synchronized operation. Installing an HF input module alone does not automatically make the entire station isochronous.

SF indication and the scope of short-circuit diagnostics

Each channel has a green status LED, and the module has a red SF group fault LED. Diagnostics can be enabled for a short circuit of the sensor supply to M. Siemens states that this diagnostic is reported on channel 0 but applies to the whole module. A report identifying channel 0 therefore does not necessarily locate the fault at the first sensor.

This capability should not be interpreted as individual wire-break or short-circuit detection for every field conductor. When SF is active, inspect the diagnostic record together with the sensor supply and wiring. An unlit channel status LED may simply indicate an inactive sensor; it does not independently prove that the module has failed.

Terminal base and power arrangement

The electronic module is installed on a compatible 15 mm ET 200S TM-E terminal base. The manual shows arrangements including TM-E15S24-01, TM-E15S23-01 and TM-E15S26-A1. Selection of terminal blocks depends on sensor wiring and auxiliary potential requirements. The electronic module and its connection base are separate components.

The station’s power module provides the 24 V DC supply. The sensor supply output has a 500 mA rated current and electronic short-circuit protection at module level. This rating does not mean that each input draws 500 mA. Maximum current drawn from the 3.3 V backplane supply is 10 mA, and typical module power loss is 0.4 W. Consumption from L+ depends on the connected sensors.

The station’s power supply, appropriate ET 200 power module and any potential distribution components should be assessed against the total load in the relevant group.

Dimensions, isolation and address space

Dimensions are 15 × 81 × 52 mm (width × height × depth), with an approximate weight of 35 g. The inputs are galvanically isolated from the backplane bus, but the two input channels are not individually isolated from each other.

Normal address space is 1 byte. With digital input packing in a suitable configuration, the module uses 2 bits. After a replacement, check the input addresses, physical channel order and program signal names together.

Maximum specified cable length is 1,000 metres with shielded cable and 600 metres with unshielded cable. Voltage drop, sensor characteristics and EMC conditions may limit the practical distance. Cable routing and signal quality become particularly important when a short input delay is selected.

Before commissioning, compare input delay, short-circuit diagnostics and any required interrupt functions with the existing project. Consult the Siemens ET 200 manuals and PDF documentation for terminal assignments and parameter descriptions.

Editor’s note: 6ES7 131-4BB00-0AB0 is the High Feature version. It should not be assumed to have the same capabilities as the standard model ending in -0AA0. Siemens specifies five electronic modules per packaging unit for this order code, with two inputs on each module. When requesting individual modules or complete packs, provide the full order number and the existing terminal base details.

Related topics

Communication with the control system is handled by the ET 200S station’s interface module. For station selection, see ET 200 communication modules and the explanation of PROFIBUS and PROFINET. If the application also needs to operate loads, suitable ET 200 digital output modules should be selected separately.

Navigation