6ES7 131-1BH00-0XB0

Siemens 6ES7 131-1BH00-0XB0 – ET 200L 16 DI 24 V DC Electronic Input Block

Siemens 6ES7 131-1BH00-0XB0 is a 16-channel, 24 V DC digital input electronic block for SIMATIC ET 200L. It transfers field switch and sensor states to the control system through its integrated PROFIBUS-DP interface. This compact ET 200L product within the Siemens ET 200 family forms a distributed input station when combined with the appropriate terminal base.

The arrangement can collect signals from a particular section of a machine. Position switches or auxiliary contacts on a conveyor, for example, connect to the station, and the PLC reads their states over the network. Selecting a digital input module requires consideration of the terminal base, network speed and sensor characteristics alongside channel count.

Input arrangement and signal levels

The inputs are arranged in two groups of eight. Their sixteen states provide two bytes of input data to the control system. Typical signal sources include pushbuttons, limit switches and sensors with compatible switching outputs.

Rated input voltage is 24 V DC. Siemens catalog data for this order number specifies −30 to +5 V for signal “0” and +13 to +30 V for signal “1”. Typical active-state input current is 5 mA, with an input delay of 2–4.5 ms. The intermediate voltage region should not be used to establish a reliable logic state.

Use compatible sensors and contact circuits that apply a positive voltage to the input. An inductive proximity sensor fitting the same mounting position does not establish electrical compatibility. Supply voltage, NO/NC behaviour and PNP/NPN output compatibility should be checked together.

Integrated PROFIBUS-DP interface

The PROFIBUS-DP interface is built into the electronic block. Connection is through a 9-pin Sub-D connector, and the maximum supported transmission rate is 1.5 Mbit/s. Two rotary switches set the station address within the range 1–99. This address must match the PLC project and must not duplicate another device on the network.

Commissioning checks should include the correct device definition or GSD file, input data length and the network’s common transmission rate. A station at the end of a segment requires appropriate bus termination. Since PROFIBUS and PROFINET use different connection arrangements, this product must be configured for its PROFIBUS-DP interface. Other options within the family can be explored through ET 200 communication arrangements.

TB 16L terminal base and field wiring

The electronic block is used with a TB 16L terminal base. The screw-terminal version is 6ES7 193-1CH00-0XA0, while the spring-terminal version is 6ES7 193-1CH10-0XA0. The terminal block carries the field wiring, and the electronic section clips onto it.

The standard terminal arrangement provides two-wire connections. Suitable supplementary terminals allow three-wire or four-wire field connections to be arranged. These terminals provide wiring and potential distribution; they do not increase the input count. Select connection components to suit the existing TB 16L arrangement and the common connections required by the sensors.

Keeping field wiring on the terminal base simplifies replacement of the electronic block. Before replacement, isolate the station supply, record the PROFIBUS address and check the complete order number of the replacement block.

Supply groups and the 1BH00 current limit

The electronics and sensor groups operate from 24 V DC, with separate supply connections arranged on the terminal base. The power supply calculation should account for both the electronics and total field sensor consumption. Adding the typical input currents alone does not establish the sensor supply load.

For the older 6ES7 131-1BH00-0XB0 version, the sensor supply load is limited to 0.5 A per input byte. One byte represents a group of eight inputs. This is not a per-channel current rating. Siemens’ note distinguishing the old and new versions also requires the sensor supply connections to be protected appropriately for the installed version.

PROFIBUS-DP is galvanically isolated from the internal electronics. The input channels do not have independent galvanic isolation from one another. Where separate field supplies are used, their reference potentials must be arranged according to the device wiring diagram.

ON, BF and channel indicators

The green ON LED indicates the electronics supply, while the red BF LED indicates a bus fault condition. Separate green channel LEDs show the input states. These indicators assist with station-level communication and supply checks; they do not establish individual wire-break or short-circuit diagnostics for every sensor circuit.

If ON is lit but BF remains active, inspect the station address, PROFIBUS cable, termination and PLC hardware configuration. If an input LED changes but the program signal does not, first confirm that the correct input address is being monitored. Comparing the sensor’s own indicator with the input block’s LED helps distinguish field wiring problems from data transfer problems.

Installation and cable arrangement

The ET 200L arrangement has an IP20 protection rating and should be installed inside an appropriate cabinet or enclosure. Siemens catalog conditions specify an operating temperature of 0 to +60 °C with horizontal installation and 0 to +40 °C with vertical installation. Allow space for the terminal base, PROFIBUS connector and cable bends when planning the layout.

The Siemens ST40 catalog entry containing this order number specifies a maximum field input cable length of 100 metres. This is not the PROFIBUS segment length. Cable routing, voltage drop and EMC conditions must also be assessed. Connection and configuration details can be checked through the Siemens ET 200 manuals and PDF documentation.

Editor’s note: Do not treat 1BH00 and 1BH01 as equivalent solely because both are described as 16-input ET 200L products. Check the sensor supply limit, product version and existing wiring together. When requesting a replacement, include the electronic block’s complete order number, the TB 16L base details and the configured PROFIBUS address.