6ES7 123-1GB10-0AB0

6ES7 123-1GB10-0AB0 – Siemens SIMATIC SC 2 AI Current Input Module

Series: SIMATIC SC / ET 200L-SC
Category: Two-channel, high-accuracy analog current input module

Function and system role

6ES7 123-1GB10-0AB0 is a 2 AI I electronic module used in the Smart Connect architecture of Siemens ET 200. It converts two analog signals from current-output field devices into numerical values for the PLC. Communication over PROFIBUS DP is handled by the associated ET 200L-SC or IM-SC station; the module itself does not receive a separate network address.

Measurement ranges, resolution and accuracy

The selectable input ranges are 4–20 mA and −20…+20 mA. Applications include 4–20 mA sensors, pressure transmitters and level transmitters. Resolution is 12 bits in the 4–20 mA range and 13 bits in the ±20 mA range. Input resistance is 50 Ω for both ranges.

Siemens identifies this version as High Accuracy. Relative to the rated input range, its basic error limit is ±0.1% at 25 °C, and its operating error limit across the operating temperature range is ±0.3%. These figures are not percentages of the instantaneous displayed reading. Sensor accuracy, wiring conditions and software scaling also affect the overall measurement.

Terminal block and transmitter connection

The module occupies one of the eight slots on a TB 16SC terminal block. 6ES7 120-0AH01-0AA0 is a screw-terminal version of this base. The system manual also lists the module for TB 16IM-SC. Check the installed terminal block, slot order and station configuration together. The electronic module measures 10 × 64 × 51 mm; these dimensions exclude the terminal block.

Four-wire current transmitters can be connected. A two-wire transmitter requires an external transmitter supply. Supplying the module with 24 V does not mean that its measurement input powers the transmitter. Follow the terminal assignment for the occupied slot when connecting M0+/M0− and M1+/M1− for channels 0 and 1.

The electronics use a 24 V DC supply and draw up to 30 mA from L+. Include externally powered transmitters in the power supply calculation. When assessing the DIN rail power supply and field wiring, check the reference potentials: the two measurement channels are not galvanically isolated from each other.

Conversion time and filtering

The module uses an integrating measurement principle. The specified times are 60 ms integration and 65 ms conversion with 50 Hz interference suppression, or 50 ms integration and 55 ms conversion with 60 Hz suppression. Conversion times are per channel. The time before a new measurement reaches the PLC program also depends on station data transfer and the program cycle.

Four smoothing settings are available: none, weak, medium and strong. Their filter time constants correspond to 1, 8, 64 and 128 module cycles, respectively. Increasing the filter can steady a fluctuating reading, but it also delays the response to a pressure or level change. Filtering does not correct faulty wiring or an unstable transmitter supply.

Configuration and fault finding

Check both the selected measuring range and the SIMATIC S7 / SIMATIC S5 numerical format. Scaling carried over from an older project must match the selected data representation. The ET 200 communication architecture is defined at station level; this SC module is not configured as a standalone PROFINET device.

The module has no dedicated fault display, readable diagnostic function or interrupt support. An absence of station communication faults therefore does not establish that the analog measurement is correct. Compare the actual loop current first, then the raw PLC value, and finally the value scaled into engineering units.

Distinction from related modules

1GB10 measures current. Voltage-output sensors require a suitable input type; 6ES7 123-1FB00-0AB0 is a voltage input module from the same SC family. The 1GB10 is also not a High Speed version. Do not choose a replacement solely by a “two analog inputs” description: match the full order code, signal range, accuracy and response time.

Editor’s Note

A single test point is insufficient for assessing this module. In 4–20 mA mode, check each channel separately at reference points such as 4, 12 and 20 mA to reveal measurement deviations. Record the filter setting and allow the reading to settle. If the raw value is correct but the displayed pressure or level is wrong, first inspect the scaling and S5/S7 data format.