Siemens 6ES7 193-1FH20-0XA0 — ET 200L Single-Tier Screw Terminal Accessory
The 6ES7 193-1FH20-0XA0 is a single-tier supplementary terminal with screw connections for the 16-channel Siemens SIMATIC ET 200L arrangement. It adds wiring points to the main terminal block. It is relevant when an existing station needs the appropriate supplementary wiring row or when a damaged terminal accessory requires replacement.
The 16-channel designation describes the arrangement this part serves. It does not create additional inputs or outputs, run a PLC program or electronically process field signals. The electronic block determines the station’s function; the terminal hardware provides the wiring connections.
Function and electrical arrangement
A single-tier supplementary terminal completes the two-wire arrangement for three-wire connections on suitable ET 200L hardware. It provides additional termination points for conductors serving sensors and other field equipment. Its purpose concerns the wiring layout rather than an increase in electronic capacity.
The terminals along the row are internally interconnected. They must not be treated as separate, isolated signal terminals. Connecting different potentials to the same row can create a short circuit. Establish the intended common connection from the circuit drawing and terminal markings before wiring the accessory.
This component is not a power supply. It does not generate voltage or independently protect a circuit. Nor does its channel designation establish the electrical characteristics of a digital input module or the load capacity of a digital output module. Assess the wiring component separately from the signal-processing electronics.
Technical identification
Manufacturer: Siemens. Order number: 6ES7193-1FH20-0XA0. Product family: SIMATIC DP / ET 200L. Component type: supplementary terminal. Arrangement: 16 channels, one tier. Termination method: screw terminals. Primary function: providing additional common connection points on the appropriate terminal block.
The ET 200L system manual’s section 3.3 wiring rules specify a standard conductor range of 0.14–1.5 mm², a stripping length of 7–11 mm and a screw-terminal conductor tightening torque of 0.4–0.7 Nm. Apply these values together with the conductor and ferrule conditions given in that section.
The tightening torque applies to the conductor connection, not automatically to other fastening screws. Conductor size and screw torque do not, by themselves, establish the permissible load current. Check the relevant base, electronic block, supply distribution and field load together.
Main terminal block and related versions
The 6ES7 193-1CH00-0XA0 TB 16L is the main 16-channel screw terminal block that carries the electronics. 1FH20 is not that base. Before ordering, establish whether the required item is the main body or the supplementary wiring row fitted to it. The same distinction matters when reviewing other ET 200 connection components.
6ES7 193-1FH30-0XA0 is the 16-channel two-tier screw version. 6ES7 193-1FH60-0XA0 has two tiers with spring terminals, also for 16 channels. 6ES7 193-1FL20-0XA0 uses one tier and screw connections but belongs to the 32-channel arrangement.
These references identify differences; they are not a list of interchangeable replacements. Check the complete order number, tier count, connection method and mounting arrangement. A broad description such as “compatible with Siemens S7” is insufficient for selecting the correct part.
Installation and wiring
Before starting work, place the machine in a safe condition, isolate the relevant supplies and verify the absence of voltage. Record the existing wire labels and common-row connection so that the replacement can be wired without relying on memory.
The supplementary terminal fits into the guideways underneath the main terminal block, with the locking mechanism fully engaged. The manual specifies fitting supplementary terminals before wiring. Do not force a misaligned assembly into place or rely on a damaged retaining feature.
The conductor must enter the clamping area correctly. Trapped insulation, loose strands or an unsuitable ferrule can compromise the connection. More tightening force does not necessarily produce a better connection: excessive force can damage the screw thread or conductor.
Route cables and connectors so that they do not continuously pull on the terminals. Nearby panel components and cable ducts affect both access and conductor movement during servicing. A sound terminal can still develop problems if the cable route places unnecessary mechanical stress on the connection.
Commissioning and fault checks
6ES7193-1FH20-0XA0 has no independent electronic channel diagnostic test. Verification concerns correct wiring, mechanical retention and electrical continuity. Perform continuity measurements on an isolated circuit, allowing for connected electronics and parallel paths that may influence the result.
No program, firmware download or network address is assigned to this accessory. PROFIBUS communication and station configuration belong to the relevant electronics. The functions of ET 200 communication interfaces should not be attributed to the supplementary terminal.
Editor’s note: If several field devices stop working together, investigate their common connection as well. Voltage at the output of a DIN rail power supply does not prove that the supply reaches every device. Intermittent operation of a connected relay or socket may involve the conductor termination, shared return path, load or electronic output. Establishing whether the symptom affects one connection or a whole group helps narrow the investigation.
Discolouration, melting, cracks, damaged threads or poor conductor retention require more than simply tightening the connection again. Replacing the part without finding the cause may lead to the same damage recurring. For used equipment, inspect the complete part number, terminals, retaining features and supplied components.
PDF documents and related information
+ Siemens ET 200 user manuals — PDF and documentation page.
+ Siemens IK PI 2007 ET 200 catalogue — 6ES7193-1FH20-0XA0 is listed on page 5/214. This document is a general catalogue rather than a dedicated user manual for the accessory.
For an overview of the system, visit About Siemens ET 200. Other hardware is available in the ET 200 product range.
Navigation
++ Siemens Automation Homepage >
++ Siemens product enquiries — OtomasyonAVM.
++ About Siemens ET 200 >
Reminder: Some Siemens and SIMATIC products offered through OtomasyonAVM are used equipment. Review the condition, complete order number and supplied components before purchasing. Used items will not be restocked once sold out. This page provides general information; the relevant manufacturer documentation and the installation’s electrical drawings must guide actual work.
Note: Manuals, commissioning explanations and troubleshooting suggestions are non-binding and may be updated. The OtomasyonAVM Community welcomes practical observations and suggestions. You can share your experience with us.