6ES7 153-2AA03-0XB0

Siemens 6ES7 153-2AA03-0XB0 – ET 200M IM 153-2

The 6ES7 153-2AA03-0XB0 is an IM 153-2 PROFIBUS DP interface module for ET 200M stations within the Siemens ET 200 family. It transfers data between the station's S7-300 modules and the main PLC. The interface connects remote I/O to the controller; it does not run a user control program as a CPU would.

Module capacity and station layout

This model accommodates up to 8 compatible S7-300 modules to its right. A station can combine digital inputs, digital outputs, analog I/O and supported function modules. The eight-module limit refers to hardware modules; the number of I/O channels depends on the cards installed.

ET 200M and ET 200S use different mechanical systems. Sharing the ET 200 family name does not make their modules interchangeable. The ET 200 system overview explains the wider product structure.

Power supply and communication

The interface uses a 24 V DC supply; the IM 153-2 technical table specifies an operating range of 20.4–28.8 V DC. PROFIBUS DP runs over RS 485 through a 9-pin D-sub connector, at rates up to 12 Mbit/s. Housing dimensions are 40 × 125 × 117 mm, in width, height and depth order.

There is no Ethernet/RJ45 connection on this model. Moving the station to PROFINET requires a suitable interface and project configuration; changing the cable or connector alone will not provide that conversion.

Addressing and hardware configuration

The front switches set the PROFIBUS address from 1 to 125. Record the existing setting before replacing the interface. In STEP 7, compare the complete interface order number, module order and parameters with the installed station. Similar-looking I/O modules may have different ranges or channel arrangements.

Redundancy, time stamping and CiR

Redundant operation requires two suitable IM 153-2 interfaces, the appropriate active bus module and a supporting control system. A redundancy-capable interface does not make a single-interface station redundant. Time stamping records transitions on suitable digital inputs; the input hardware, clock synchronization and project settings must support the application.

Siemens explicitly lists 6ES7153-2AA03-0XB0 in the S7-400 CPU manual's hardware requirements for adding ET 200M modules during operation using CiR. The arrangement also needs compatible CPU/master versions, active bus elements and space for expansion. Configuring the station as a DPV0 slave through a GSD file does not meet those requirements. CiR and replacing modules during operation are separate functions with their own prerequisites.

Diagnostics and replacement checks

ON indicates supply voltage, BF a bus fault, SF a group error and ACT the active interface. Use the LEDs as an initial guide, then read station diagnostics. Check power, the station address, PROFIBUS cabling and termination before comparing the configured module sequence with the actual hardware.

Record the order numbers of the connection and bus components as well as the interface. I/O replacement during operation requires a supporting active bus arrangement and configuration. It is not available on every ET 200M station assembled with standard bus connectors.

Editor's Note: Do not select a spare solely by the “IM 153-2” marking on its front. Compare the full order number, version and bus module. This older model has an eight-module limit; the twelve-module capacity of later versions must not be assigned to it. In a redundant station, also check compatibility with the interface that will remain installed.

Manuals and technical references

Documentation page: Siemens ET 200 manuals and PDF documents. References include Siemens' ET 200M Distributed I/O Device manual, the compatibility sections of ET 200M Operating Instructions, and the CiR hardware requirements in S7-400 CPU Specifications. Features described for newer interfaces must be checked before applying them to older order numbers.

Related topics

ET 200 PROFIBUS and PROFINET interfaces · ET 200 additional modules and accessories · S7-300 CPU modules · HMI and operator panels · SCADA systems. These links cover other system components and do not by themselves establish hardware compatibility.

Navigation: Siemens automation · SIMATIC S7 · Siemens ET 200 · OtomasyonAVM home