6ES7 151-3AA20-0AB0

Siemens 6ES7 151-3AA20-0AB0 – ET 200S IM151-3 PN ST

The Siemens 6ES7 151-3AA20-0AB0 is the IM151-3 PN ST interface module for an ET 200S station. Part of the ET 200 range, it exchanges data between the station’s I/O modules and a PROFINET IO controller. The machine program runs in the connected PLC; this module handles the station’s network interface.

Connections and station capacity

The module has two RJ45 ports and supports 100 Mbit/s full-duplex PROFINET IO communication. It requires a 24 V DC supply. When identifying an installed unit, note that this is the Ethernet-based PN version; PROFIBUS DP interfaces use different hardware.

A station can contain up to 63 modules, with a maximum backplane bus length of 2 metres. The available address space is 256 bytes for inputs and 256 bytes for outputs. Module count and address space are separate limits, so both need checking before adding I/O.

Field signals connect through the station’s digital input, digital output and analog input modules. The chosen I/O modules determine the channel count and signal types.

Device name and memory card

The assigned PROFINET device name must match the STEP 7 project. Checking the IP address alone can miss a naming mismatch. On this generation, a SIMATIC Micro Memory Card (MMC) stores the device name and allows it to be transferred to a replacement interface. An MMC can also be used for firmware updates.

If communication fails after a replacement, compare the device name and module arrangement with the project, then read the diagnostics. The front-panel ON, SF, BF, LINK and RX/TX LEDs help with the initial assessment. A lit LINK indicator confirms a network connection, but does not by itself confirm cyclic I/O exchange with the controller.

Check firmware before adding modules

Module support can depend on the firmware installed in the interface. For example, Siemens specifies V4.0.1 or later on this IM151-3 PN for the 6ES7131-4BF00-0AA0 eight-channel digital input module and 6ES7132-4BF00-0AA0 eight-channel digital output module. A module fitting the station physically is only part of the compatibility check.

Replacement with a later version

Siemens identifies 6ES7151-3AA23-0AB0 as compatible with this version and states that it can replace it in an existing system without reconfiguration. The replacement instructions also require a previously used AA23 to be reset to its default settings before use as a spare. Include that requirement, the device name and the existing project in the replacement plan.

Editor’s note: Record the full order number from the label. Several versions share the IM151-3 PN name, and features documented for later units, such as MRP or Shared Device, should not automatically be attributed to the 3AA20. The order number and firmware version together provide a useful starting point when identifying a spare.

Manuals and PDF downloads

Visit the Siemens ET 200 user manuals page for wiring and commissioning documents. Check that the selected manual covers 6ES7151-3AA20-0AB0. Section 10.8 of the December 2005 ET 200S Operating Instructions describes this interface.

Related topics

Station hardware: Terminal blocks · Connection modules · Power supply modules · Power distribution modules.

More from the ET 200 range: PROFIBUS and PROFINET interfaces · Other network interfaces · Functional modules · Safety modules · PROFIsafe. These links cover other parts of the range; they do not establish compatibility with this interface.

Navigation: Siemens automation · SIMATIC S7 · About ET 200.

Sources: Siemens, ET 200S Operating Instructions, 12/2005 (A5E00515771-03), section 10.8; 08/2008 (A5E00515771-06), PROFINET commissioning; ET 200S Product Information, 09/2006 (A5E00847859-01); IM151-3 PN – 6ES7151-3AA23-0AB0, 08/2010 (A5E01638907-04), predecessor compatibility.