6ES7 142-1BF30-0XA0
Siemens 6ES7142-1BF30-0XA0 ET 200X EM 142 Digital Output Module
6ES7142-1BF30-0XA0 is an EM 142 expansion module that adds eight digital outputs to a SIMATIC ET 200X station. The outputs are rated 24 V DC / 1.2 A. Part of the Siemens industrial automation range, it controls solenoid valves, DC contactors and suitable indicator lamps.
Within the Siemens ET 200 distributed I/O family, this product belongs to ET 200X. Each of its eight 5-pin M12 sockets carries one output channel. When selecting replacements for industrial automation applications, compare the complete order number, basic module and field connections rather than relying on the description “eight digital outputs”.
What is the combined current limit?
The 1.2 A channel rating is separate from the module's combined load limit. The Siemens manual specifies a maximum total output current of 7 A up to 20 °C and 5 A up to 50 °C, in all mounting positions. For PLC-based control applications, add the currents of loads energized together. Loading all eight channels at 1.2 A exceeds the total limit.
Five checks before selection or replacement
1. Basic module and station layout: EM 142 is an expansion connected to an ET 200X basic module; the basic module provides the PROFIBUS DP connection. When reviewing ET 200 system architecture and module selection, record the basic module order number, expansion sequence and configured output addresses. A correct mechanical fit does not establish that the project configuration is also correct.
2. M12 socket assignment: Sockets X1–X8 correspond to output channels 0–7, respectively. Pin 4 carries the output signal, and pin 3 is the load supply return. When replacing a cable, verify connector pin numbers instead of relying on wire colors. Label both ends with the same channel identification to avoid checking the wrong actuator during later maintenance.
3. Load supply: The module receives its 2L+ load supply through the station's backplane connection. In SIMATIC S7 control systems, communication can remain active while load power is absent. If all outputs are affected in a station using Siemens PLC and I/O products, inspect the common supply path, connections between modules and voltage drop under load.
4. Load type and switching frequency: The manufacturer's limits are 100 Hz for resistive loads, 0.5 Hz for inductive loads and 1 Hz for lamp loads; lamp load must not exceed 10 W per channel. Assess a valve coil's operating cycle and connected suppression components as well as its continuous current.
5. Status indication and field protection: Each channel has a green status LED. Compare commands displayed on HMI operator panels with this indication and the actual actuator response. To maintain IP66/IP67 protection, fit suitable connectors correctly and close unused M12 sockets with sealing caps. Moisture or poor socket contacts can cause intermittent behavior that resembles a module fault.
PDF manuals and connection diagram
Use the Siemens ET 200 PDF manuals page for documentation resources. The ET 200X Distributed I/O Device manual, 02/2003 covers this model in Section 7.15, with socket assignments in Table 7-30. Share the label photograph, basic module order number and channel loads through Siemens product technical enquiries.
Editor's note: Eight 0.8 A loads draw 6.4 A in total. Although every channel remains below 1.2 A, this arrangement exceeds the 5 A combined limit at 50 °C. Base the load calculation on the machine's highest operating temperature and the simultaneous output combinations that the program can activate.
Related topics and Siemens navigation