6ES7 138-4FA04-0AB0

Siemens main menu › Siemens S7 family › ET 200 › Safety modules

6ES7 138-4FA04-0AB0 — Siemens ET 200S 4/8 F-DI PROFIsafe Digital Input Module

6ES7 138-4FA04-0AB0 is a 24 V DC, 4/8 F-DI PROFIsafe fail-safe digital input module for the Siemens ET 200S distributed I/O system. Part of the ET 200 safety module range, the electronics module is 30 mm wide.

What does 4/8 F-DI mean?

The module has 8 physical digital inputs. Single-channel evaluation uses eight inputs; dual-channel evaluation uses four input pairs. “4/8” therefore does not mean twelve inputs. When selecting digital input modules, distinguish the number of sensors from the number of physical channels required.

Rated supply: 24 V DC; permitted range: 20.4–28.8 V DC. Electronics module dimensions: 30 × 81 × 52 mm. Safety data uses ET 200 PROFIsafe communication. Operation in a PROFINET configuration with IM 151-3 HF is also supported.

Check the power module when assessing SIL 3 / PL e

The product supports applications up to SIL 3 / PL e under the appropriate system conditions. The selected ET 200S power supply module affects this assessment. Siemens supplement A5E36397089-AA, 07/2015 specifies SIL 2 / Category 3 / PL d for 4FA04 supplied by PM-E DC24V models up to and including 6ES7138-4CA01-0AA0.

The highest catalogue rating therefore does not apply automatically to every potential group and power distribution arrangement. Assess the sensor architecture, supply components and safety project together.

Terminal base and application matching

Siemens light curtain application 58793869 uses this module with the 6ES7193-4CF40-0AA0 screw-terminal base. When choosing ET 200S terminal blocks, match the terminal arrangement and complete order number; a 30 mm width alone does not establish compatibility.

Review the field connection components, sensor supply and F-CPU project together when studying the light curtain example. The PROFIBUS and PROFINET interfaces provide station communication; this input module is not a standalone network interface.

Checks before replacement

Record the existing ET 200 station configuration: complete module code, hardware release, terminal base, power module and interface model. Compare the F-address, channel evaluation and safety program parameters. Complete the relevant safety function validation after replacement.

Editor’s note

A small revision change can matter in a safety project. Keep 4FA04 and 4FA05 specifications separate. Use the updated supplement when checking the safety level achievable with the power module; the “PROFIsafe” marking alone does not establish interchangeability.

PDF documentation and technical references

Use the Siemens ET 200 PDF and user manual page as a technical reference hub. Review the 6ES7138-4FA04-0AB0 data sheet, power module correction A5E36397089-AA and application example 58793869 together. The 4/8 F-DI product section in the 2013 edition of A5E00103686-08 describes 4FA05; do not transfer all its specifications to 4FA04.

Related topics

Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules

Otomasyon AVM • Siemens guide

Siemens main menu  |  SIMATIC S7 family  |  ET 200 module categories  |  ET 200 PDF archive