6ES7 135-7TD00-0AB0

Siemens 6ES7135-7TD00-0AB0 ET 200iSP 4-Channel HART Analog Output Module

6ES7135-7TD00-0AB0 is a 4-channel HART analog current output module with 14-bit resolution for SIMATIC ET 200iSP. Part of the Siemens industrial automation range, it sends command values to compatible valve positioners and process devices with current-reference inputs. HART provides access to parameters and diagnostic information supported by the field device.

This module belongs to the ET 200iSP range within the Siemens ET 200 distributed I/O family and connects field wiring through its terminal base. For process and industrial automation applications, assess the current range, connected device input and hazardous-area suitability alongside the channel count.

Selecting 4–20 mA, 0–20 mA or HART

Each channel can be configured for 0–20 mA, 4–20 mA or HART. Select the HART output setting for channels that require HART communication, and check field-device and device-description compatibility. In PLC-based process control, engineering units, percentage commands and analog output scaling must use the same range. Compare the existing channel parameters when replacing the module.

Five checks before selection or replacement

1. Terminal base and channel mapping: The module plugs into a suitable TM-IM/EM or TM-EM/EM terminal base. Channel 0 uses terminals 1–2, channel 1 5–6, channel 2 9–10 and channel 3 13–14. When reviewing ET 200 system architecture and module compatibility, verify the base type, connection polarity and mechanical coding. Do not modify the coding element.

2. Output load and cable: The specified maximum current-output load is 750 Ω, with a maximum shielded cable length of 500 m. When designing current loops with Siemens PLC and I/O products, include both the device's input resistance and the cable's round-trip resistance. Longer cables also require reassessment of the Ex circuit's capacitance and inductance limits.

3. Response to CPU STOP: Channel options include zero output current, a substitute value or holding the last value. In SIMATIC S7 control applications, select the response according to the process shutdown scenario. Establish the required valve or actuator position; do not assume that 4 mA represents a safe position in every application. Include substitute-value behaviour during restart in the commissioning plan.

4. Diagnostics and actual field response: The module provides configurable wire-break and short-circuit diagnostics and a red SF group fault LED. Compare command values on HMI operator panels with diagnostic records and the field device's actual response. If the current command appears correct but the valve does not move, also investigate the device's local operating mode and mechanical condition.

5. Isolation and Ex circuit suitability: The channels are galvanically isolated from the backplane bus, but there is no galvanic isolation between individual channels. For Zone 1 installations, meet the manufacturer's Ex e enclosure requirement. Check the field device's Ex certificate, the module's permissible safety values and the cable's electrical characteristics together. Matching 4–20 mA signals alone does not establish Ex circuit suitability.

PDF manual and parameter information

Visit the Siemens ET 200 PDF manuals page for system documentation. In the ET 200iSP manual, 11/2022, A5E00247483-AK, Section 14.6 covers connections and specifications, while Section 14.11.3 describes channel parameters. Also consult the model-specific A5E00308259-07 product information. Share the label, terminal wiring and channel settings through Siemens product technical enquiries.

Editor's note: On a linear 4–20 mA scale, 12 mA represents a 50% command. It does not by itself establish that a valve is physically 50% open. Assess output current, positioner configuration and any independent position feedback together.

Related topics and Siemens navigation

Product families
Siemens main menu  |  Siemens PLC products  |  SIMATIC S7

ET 200 resources
ET 200 products  |  ET 200 system overview  |  ET 200 PDF manuals

Control and assistance
HMI operator panels  |  SCADA systems  |  Siemens product enquiries