6ES7 151-7AB00-0AB0
Siemens 6ES7 151-7AB00-0AB0 – ET 200S IM151-7 CPU FO
The 6ES7 151-7AB00-0AB0 is an IM151-7 CPU FO interface module for the Siemens ET 200S distributed I/O system. It combines a PLC CPU capable of running a user program with a fiber-optic PROFIBUS DP slave interface.
The CPU can use suitable local digital, analog and other ET 200S modules. It can exchange data with a higher-level controller over PROFIBUS, and the manual also describes standalone operation. The installed program and station configuration determine how the device is used.
Technical specifications
The nominal supply is 24 V DC, with a permissible range of 20.4–28.8 V DC. The data sheet specifies a maximum supply current of 250 mA and typical power loss of 3.3 W. Dimensions are approximately 60 × 119.5 × 75 mm and weight is approximately 200 g.
Up to 63 ET 200S modules can be connected. Selection also depends on station width, backplane current, address space and the rules for the modules used.
24 KB and 48 KB work memory
The original Siemens manual specifies 24 KB of work memory. A later data sheet specifies 48 KB from firmware V1.13 onward, and 24 KB for earlier firmware. Check the actual firmware before assuming that every device with this order number has 48 KB.
Work memory belongs to the CPU and is not listed as expandable. It is different from the capacity of the MMC card. The executable parts of the program must fit within the CPU's actual work-memory limit.
MMC memory card
A suitable SIMATIC Micro Memory Card is used for power-fail-proof storage of the user program and configuration. Check the card order number, capacity, CPU version and Siemens compatibility information. Related products are listed under used memory cards.
Siemens sources differ on maximum MMC capacity: the product data sheet specifies 2 MB, while a later Siemens compatibility table lists up to 4 MB for 7AB00. If using a 4 MB card, verify compatibility against the actual hardware and firmware version. Do not assume that a larger card will work automatically.
Back up the program and project data before replacing the card. A blank card does not automatically acquire the machine program. Do not format a SIMATIC MMC with Windows; its internal structure and machine data can be damaged.
Fiber-optic PROFIBUS connection
FO identifies the fiber-optic interface. The device operates as a PROFIBUS DP slave, with a data-sheet transmission rate of up to 12 Mbit/s. Speed alone does not establish compatibility between the fiber cable, connectors and other network devices.
The data sheet also identifies an integrated RS-485 connection for programming and states that MPI is not supported. Distinguish the optical PROFIBUS connection from the programming connection and MPI. See PROFIBUS and PROFINET for general network information.
This model has no direct PROFINET interface. Its optical PROFIBUS connection is not directly interchangeable with a standard copper PROFIBUS plug. Select the cable, optical connection and topology according to the device manual.
Programming and troubleshooting
The Siemens data sheet specifies STEP 7 V5.1 or later. Check software and hardware support for the actual device version. General information is available under PLC programming software.
If the station does not operate, first check supply voltage, CPU operating state, MMC and PLC diagnostics. For communication faults, inspect the fiber connections, PROFIBUS address, higher-level controller configuration and module order. Verify the existing backup before deleting a program or replacing the card.
Editor's Note: Check both the FO designation and firmware version. This is a CPU-equipped ET 200S interface with fiber-optic PROFIBUS. Before choosing a replacement, verify the 24 / 48 KB distinction, the conflicting MMC capacity information and the backup of the existing machine program.
Manuals and related topics
For wiring, memory, configuration and diagnostics, visit Siemens ET 200 manuals and PDF files. See About Siemens ET 200 for the general system arrangement.
Related topics: What is a PLC? · Used PLC CPUs · ET 200 communication modules · PLC troubleshooting
Navigation: Siemens automation · SIMATIC S7 · Siemens ET 200 · OtomasyonAVM homepage