6ES5 247-4UA41

Siemens 6ES5 247-4UA41 – IP 247 Three-Axis Stepper Positioning Module

The Siemens SIMATIC S5 6ES5 247-4UA41 (IP 247) positions three independent stepper axes in open loop. It sends pulse and direction commands to external drives and calculates position from the steps it commands. The double-width 4UA41 measures 40 × 233 × 160 mm and has an additional heat sink for natural cooling. The single-width 6ES5 247-4UA31 requires forced ventilation.

Drive and field connections

The 9-pin X4, X5 and X6 connectors serve axes 1, 2 and 3 respectively. Each carries pulse, direction and reset signals. The BB input reports drive readiness. When matching a stepper motor and stepper drive, use Siemens figures 3/7 and 3/8 to check X30/X31 jumper settings for the drive's 5 V differential RS-422 or optocoupler inputs. All three drive interfaces use the same signal supply voltage.

The shared 25-pin X7 connector provides two limit inputs, a BERO reference input, an external start/stop input and a position-reached output for each axis. This field I/O is rated for 24 V DC. When checking S5 cables and connectors, label the axis plugs separately from the shared X7 cable. The programming device connects to front connector X8 (20 mA) for COM 247.

S5 rack and PLC program

Siemens documents the IP 247 for the S5-115U with CPU 941, CPU 942, CPU 943 or CPU 944, the S5-135U with CPU 922 or CPU 928, and for the S5-150U and S5-155U. FB164 operates and monitors the axes. FB165 transfers data.

Check the S5 rack label and compare the installed layout with the drawings for racks such as the CR 700-2, CR 700-3 or ER 701-3. The S5-115U manual lists the 6ES5 491-0LB12 adapter casing for the double-width IP 247. Confirm the CP slot, adapter part number and mounting clearance for your rack.

Choosing a replacement module

The IP 267 also controls stepper drives. The IP 266, incremental IP 246 and absolute IP 246 use different drive or feedback interfaces. The IP 241 position decoder and IP 288 fast/slow positioning module serve separate functions. Match the full order number, module width and axis connectors when choosing a spare. To sell a module, send photos of its label and connectors to otomasyonavm@gmail.com.

Editor's note

Back up machine data and traversing programs with COM 247 before removing the module. Record the IP 247 addresses in the PLC project as well.

With power isolated, label X4, X5 and X6 by axis number. All three connectors have the same pin assignment.

Compare the replacement module's X30/X31 jumper positions with the original module and the drive input type. Check the supply and signal commons against the Siemens diagram.

If an axis fails to start, check the BB drive-ready signal first, then the limit, reference and external start/stop states at X7.

Verify the limits and emergency stop before testing one axis at low speed. If the displayed position advances while the mechanism falls behind, check for missed steps.

PDFs and Siemens documentation

+ Siemens IP 247 manual (EN) – Wiring in chapter 3, COM 247 in chapter 5, FB164/165 in chapter 6

+ Siemens IP 247 manual (DE)

+ Siemens S5-115U manual (EN) – Adapter casings in section 15.3

+ Siemens S5 PDF archive