6ES5 095-8MA02
Siemens SIMATIC S5-95U 6ES5 095-8MA02 Compact PLC
The 6ES5 095-8MA02 is a compact SIMATIC S5 controller that combines the CPU and digital and analog I/O in one housing. It reads sensors, runs machine sequences and drives field outputs. The unit runs from a 24 V DC power supply.
Onboard inputs and outputs
The unit has 16 digital inputs and 16 digital outputs. Each output is rated at 0.5 A under the load conditions specified in the manual. The controller also has two counter inputs and four interrupt inputs. For extra points, see the S5 digital input modules and S5 digital output modules. For pulse signals, see how high-speed counters work.
The onboard analog section has eight 0–10 V inputs and one analog output. Terminal wiring selects 0–10 V or 0–20 mA output. For expansion through external S5 analog modules, revision 8MA02 A02 supports up to 16 analog channels.
STEP 5 connection and memory
The controller has one 20 mA TTY current-loop interface for STEP 5 access. Match the S5 programming cable and any interface converter to the existing programming device. If the cabinet has separate S5 communications hardware, record its order number as well.
Revision 8MA02 A02 has 16 KB of total memory, with up to 8 KB available for instructions. Record the order number of the fitted S5 memory module. The 6ES5 375-0LC31 EEPROM is one of the S5-95U memory options listed in the Siemens manual.
Expansion and model compatibility
For S5-100U expansion, identify the 6ES5 700-8MA11 bus unit and the modules fitted to it. Examples include the 422-8MA11 digital input, 451-8MA11 digital output and 464-8MA11 analog input. Verify signal ranges, addresses and terminal wiring against the existing cabinet before replacing a module.
Check memory, I/O and program compatibility individually for the S5-95U 8MA01, 8MA03, 8MA04 and 8MA05 versions. The 6ES5 090-8MA01 belongs to the S5-90U series. Use the complete order number and hardware revision from the nameplate when sourcing a spare.
Editor’s Note
Before buying a used 8MA02, connect through STEP 5 and confirm that you can read the program and DB1. During a bench test, apply a known signal within the 0–10 V range to an analog input and compare it with the STEP 5 reading. Measure the analog output using the voltage or current wiring used by the machine.
Related topics
About Siemens S5 PLCs · S5 90/110 modules
Shared Siemens S5 PDF archive · S5 CPU models · Siemens SIMATIC S5 · Used Siemens equipment
References
Siemens S5-95U manual, EWA 4NEB 812 6068-01d (German). The base-unit chapters cover the 8MA03. Appendix H-1, PDF page 86, lists revisions 8MA02 A01/A02.
PLC Hardware listing for 6ES5 095-8MA02. Supply, I/O and TTY details for the exact order number.