Delta VFD-E Fault codes 2
Hi everyone,
This page continues our guide to Delta VFD-E fault codes, alarm messages and basic troubleshooting. Fault messages are displayed on the drive's digital keypad. The five most recent faults can be read from the keypad or through communication. After the cause of a fault has been cleared, it is recommended to wait approximately 5 seconds before resetting the drive from the keypad or an input terminal.
fbE: PID Feedback Signal Error
The PID feedback signal is missing, incorrect or outside the expected operating condition.
- Check the Pr.10.01 parameter setting.
- Check the AVI / ACI wiring and make sure that the feedback signal is correctly connected.
- Verify that the feedback sensor is operating and producing a valid signal.
- Check for a possible mismatch between the system response time and the
PID feedback signal detection time – Pr.10.08.
An unstable or missing PID feedback signal may prevent the control loop from regulating the process correctly.
PHL: Phase Loss
One or more phases of the input power supply may be missing or improperly connected.
- Check the input phase wiring for loose connections.
- Make sure all power terminals are properly tightened.
- Inspect the input wiring for damaged conductors or poor contacts.
- On three-phase models, verify that all phases are present at the drive input.
If the wiring is correct, the incoming power supply and upstream protection equipment should also be checked.
AUE: Auto Tuning Error
The automatic motor tuning process could not be completed successfully.
- Check the cabling between the drive and motor.
- Make sure that the motor terminals are correctly connected and secure.
- Verify that the required motor parameters have been entered correctly.
- Correct any wiring or parameter problems and retry the auto-tuning procedure.
If the error remains, check the motor and the conditions required for the selected auto-tuning procedure.
CP10: Communication Time-out
A communication time-out has occurred between the drive's control board and power board.
- Check the recommended reset procedure in the Delta VFD-E documentation.
- If required, perform the appropriate parameter reset / factory-default procedure according to the user manual.
- If the fault returns, avoid repeatedly resetting and operating the drive.
- Persistent CP10 errors may require technical inspection of the internal control or power electronics.
If the fault cannot be cleared by the procedures specified in the manual, contact qualified technical service or the manufacturer.
PTC1 / PTC2: Motor Overheat Protection
The motor temperature protection circuit has detected an over-temperature condition.
- Check whether the motor is overheating.
- Allow the motor to cool before restarting if excessive temperature is present.
- Check the motor cooling conditions, ventilation and mechanical load.
- Inspect the PTC sensor and its wiring.
- Check the settings from Pr.07.12 to Pr.07.17.
Do not repeatedly reset an over-temperature fault without identifying the reason for the motor temperature increase.
PGEr: PG Signal Error
A problem has been detected in the PG / pulse-generator feedback signal.
- Check the PG card wiring and connectors.
- Verify that the PG feedback signal reaches the drive correctly.
- Inspect the cable for broken conductors, loose terminals or damaged insulation.
- If the wiring is correct and the fault remains, test with another compatible PG card if available.
The PG feedback device, wiring and PG interface card should be evaluated as one signal path.
CGUd: CANopen Guarding Time-out
This message applies to the relevant CANopen-equipped VFD-E models.
- Check the physical CAN bus connection.
- Verify that the connected CANopen devices are powered and communicating.
- Check the CANopen communication settings and network connections.
- Reconnect to the CAN bus if communication has been lost.
- Reset the CAN bus when required by the system configuration.
CGUd indicates that the expected CANopen guarding communication was not received within the permitted time.
deb: Deceleration / Momentary Power-loss Condition
This message may be displayed during deceleration when
Pr.08-24 is set to a value other than 0 and an unexpected or momentary
loss of input power is detected.
- Check the Pr.08-24 setting.
- Set Pr.08-24 to 0 when this setting is appropriate for the application.
- Check whether the input power supply is stable.
- Inspect the supply system for momentary voltage loss or abnormal voltage fluctuations.
The parameter should not be changed simply to hide the message;
the cause of an unexpected power interruption should also be investigated.
ACL: Abnormal Communication Loop
An abnormal condition has been detected in the drive's communication circuit or communication path.
- Check whether the communication wiring is correct.
- Make sure all communication connections are secure.
- Inspect the cable for damage, broken conductors or incorrect connections.
- If the wiring is correct but the fault remains, the communication circuit may require technical inspection.
- For a persistent ACL fault, contact qualified technical service or the manufacturer.
Repeatedly resetting the drive without correcting the communication problem may not resolve the underlying fault.
Delta VFD-E Fault codes (pdf)+ VFD-E Fault Codes – First Page >
+ VFD-E Fault Codes – Second Page >
-----------------
++ Delta Second-Hand Main Page
* The user manuals, commissioning suggestions, fault codes and troubleshooting recommendations provided on this page are not binding. The information and documents above are open to improvement and, in some areas, may still require improvement. As the Otomasyon Mall Community, we welcome your suggestions and contributions. If you have field experience or practical information that could make these products easier to use, please do not hesitate to share it with us. 22.07.2013