Yaskawa Vs Mini fault codes

EF (Simultaneous Forward/Reverse commands)
When Forward and Reverse commands are simultaneously input to the terminals for more than 500ms, the inverter stops according to constant n03.
BB (External baseblock)
When the base block command at the multi-function terminal is active, the inverter output is temporarily stopped, and the condition is cleared when the input command is removed. Check the multi-function input terminals S1, S2, or S3.
STP (Operator function stop)
When the RESET button is pressed during operation by the control circuit terminals, check the SF and SR terminals. The inverter stops according to constant n03.
OL 3 (Over torque detection)
Motor current exceeds the preset value in constant n51. The inverter continues operation. Check the driven machine and correct the cause of the fault, or increase the value of constant n51 up to the highest value allowed for the machine.
SEr (Sequence error)
The inverter receives a LOCAL/REMOTE select command from the multi-function terminal while the inverter is outputting. Refer to page 39 for the LOCAL/REMOTE select signal. Check the multi-function input terminals S1, S2, and S3.
UV (Main circuit low voltage)
Main circuit DC voltage drops below the low voltage detection level while the inverter output is OFF. Check the power supply voltage, that the main circuit power supply wiring is connected, and that the terminal screws are securely tightened.
OV (Main circuit overvoltage)
Main circuit DC voltage exceeds the overvoltage detection level while the inverter output is OFF. Check the power supply voltage.
OH (Cooling fin overheat)
Intake air temperature rises while the inverter output is OFF. Check the intake air temperature.
OC (Overcurrent)
Inverter output current momentarily exceeds approximately 250% of the rated current. Check for a short circuit or grounding at the inverter output side, excessive load, extremely rapid acceleration/deceleration time, use of a special motor, starting a motor of a capacity greater than the inverter rating, and opening/closing of a magnetic contactor at the inverter output side.