Yaskawa Vs Mini fault codes 2

UV1 (Main circuit low voltage) Main circuit DC voltage drops below the low voltage detection level while the inverter output is ON. Check for a reduction in input power supply voltage, occurrence of momentary power loss, and insufficient acceleration time. Check the power supply voltage, that the main circuit power supply wiring is connected, and that the terminal screws are secure. Increase the acceleration time.

UV2 (Control power supply fault) A voltage fault of the control power supply is detected. Cycle the power. If the fault remains, replace the inverter.

OH (Cooling fin overheat) Temperature rise due to inverter overload operation or intake air temperature rise. Check for excessive load, improper V/f pattern setting, and insufficient acceleration time if the fault occurs during acceleration. Check the intake air temperature if it exceeds 50°C (122°F). Check the load size, V/f pattern setting, and intake air temperature.

OU (Motor overload) Motor overload protection operates by the built-in electronic thermal overload relay. Check the load size or V/f pattern setting. Set the motor rated current shown on the nameplate by constant n31.

OL2 (Inverter overload) Inverter overload protection operates by the built-in electronic thermal overload relay. Check the load size or V/f pattern setting. Check the inverter capacity.

OL3 (Over torque detection) Motor current exceeds the preset value in constant n51 due to machinery fault or overload. Check the driven machine and correct the cause of the fault, or increase the value of constant n51 up to the highest value allowed for the machine.

EF1, EF2, EF3 (External fault) The inverter receives an external fault input from the control circuit terminal. Check the multi-function input terminals S1, S2, and S3.

CPF-00 (Initial memory fault) An initial memory fault is detected. Cycle the power. If the fault remains, replace the inverter.

CPF-01 (ROM fault) A ROM fault is detected.

CPF-04 (Constant fault) A constant fault is detected. Record all constant data and initialize the constants. Refer to page 22 for constant initialization. Cycle the power. If the fault remains, replace the inverter.

CPF-05 (AD converter fault) An AD converter fault is detected. Cycle the power. If the fault remains, replace the inverter.

CPF-06 (Option connection fault) Remove power to the inverter. Check the connection of the option. Check for insufficient power supply voltage. Check the power supply voltage, that the main circuit power supply wiring is connected, and that the terminal screws are securely tightened. Check the control sequence and replace the inverter.