Yaskawa E7 Fault Codes 4
WARNING
Some features within the PI function group cause the Drive to shut down momentarily (e.g., Sleep Function, Snooze Function, Feedback Loss feature, etc.). Upon recovery from the conditions that activate these features, the Drive may start unexpectedly. Therefore, when enabling these features, take appropriate measures to notify personnel working with this equipment that unexpected starting may occur.
Alarm Detection
BUS - Option Communication Error: Check all connections and verify all user-side software configurations.
CALL - SI-F/G Communication Error: Check all connections and verify all user-side software configurations.
EF - External Fault: Check external sequence logic.
EF0 - Opt External Fault (Flashing): Check for an external condition, verify the parameters, and verify the communication signal.
EF3 - External Fault S3 (Flashing): Eliminate the cause of an external fault condition.
EF4 - External Fault S4 (Flashing)
EF5 - External Fault S5 (Flashing)
EF6 - External Fault S6 (Flashing)
EF7 - External Fault S7 (Flashing): Remove the fault from a multi-function digital input.
DNE - Drive Not Enabled (Flashing): Apply the enable command before applying the run command.
FAN - Cooling Fan Error: Replace the cooling fan if the Drive internal cooling fan has stopped and L8-32=0.
FBL - PI Feedback Loss
Description: This fault occurs when PI Feedback Loss Detection is programmed to fault (b5-12 = 2) and the PI Feedback is below the PI Feedback Loss Detection Level (b5-13) for the PI Feedback Loss Detection Time (b5-14).
Solution: Verify the Drive is programmed to receive the PI Feedback source signal. Check to ensure the PI Feedback source (e.g., transducer, sensor, building automation signal) is installed and working properly.
LL3 - Loss of Load Detection 1 (Flashing)
Description: Drive output current is less than L6-02 for more than the time set in L6-03, indicating the motor is underloaded.
Solution: Ensure the values in L6-02 and L6-03 are appropriate. Check the application/machine status to eliminate the fault.
OH - Cooling Fin/Cooling Fan Overheat (Flashing)
Description: The temperature of the Drive cooling fin exceeded the temperature programmed in parameter L8-02.
Solution: Check for dirt build-up on the fans and cooling fins. Reduce the ambient temperature around the Drive. Remove the heating unit if present.
OH2 - Drive Overheat Pre-alarm (Flashing)
Description: Drive overheat pre-alarm signal is input from a multi-function digital input terminal. An external overheat condition exists connected to one of the multi-function input terminals S3, S4, S5, S6, or S7.
Solution: Check for an external condition. Verify the program parameters H1-01 through H1-05.
OH3 - Motor Overheat 1 (Flashing)
Description: Motor Overheating Alarm. The Drive stops or continues operation according to the setting of L1-03.
Solution: Recheck the cycle time and the size of the load. Recheck the accel/decel time (C1-01 and C1-02). Recheck the V/F pattern (E1-01 through E1-13). Recheck the motor rated current value (E2-01).
OV - DC Bus Overvoltage (Flashing)
Description: DC Bus Overvoltage occurs when the input voltage at R/L1, S/L2, and T/L3 is too high. For 208-240Vac, the trip point is ≥ 400Vdc. For 480Vac, the trip point is ≥ 800Vdc.
Solution: Check the input circuit and reduce the input power to within specifications. Extend the deceleration time set in C1-02 if it is too short. Remove any power factor correction capacitors being used on the input to the Drive.
OVRD - Emergency Override
Description: Emergency Override is active when the Forward or Reverse Emergency Override input is closed.
Solution: When the Forward (H1-0X = 81) or Reverse (H1-0X = 82) Emergency Override multi-function input is closed, the drive will run at either the B1-14 reference (B1-15 = 0) or the AUTO reference (B1-15 = 1), and "OVRD Emergency Override" will be displayed on the digital operator.
PRHT - Motor Preheating
Description: The motor is preheating when the Motor Preheat 2 input is closed.
UV - DC Bus Undervoltage (Flashing)
Description: The DC bus voltage is less than or equal to L2-05. For 208-240Vac, the trip point is ≤ 190Vdc. For 480Vac, the trip point is ≤ 380Vdc.
Solution: Check the input circuit and increase the input power to within specifications. If the acceleration time is set too short, extend the time in C1-01. If the voltage fluctuation of the input power is too large, check the input voltage.
UV2 - Control Power Supply Undervoltage
Description: Undervoltage of the control circuit when running. This could be due to an external load connected, pulling down the Drive power supplies.
Solution: Cycle power off and on to the Drive. Repair or replace the Power PCB/Gate Drive PCB.
UV3 - Soft Charge Circuit Fault
Description: The pre-charge contactor opened while the Drive was running. This could be due to dirty contacts on the soft charge contactor, causing it not to function mechanically.
Solution: Cycle power off and on to the Drive. Check the condition of the soft charge contactor.
OPE01 - kVA Selection
Description: Drive kVA setting error. The control board was replaced, and the kVA parameter is set incorrectly.
Solution: Enter the correct kVA setting (o2-04) by referring to the Drive model number in Appendix B.
OPE02 - Limit Constant
Description: Data out of range. Parameter set above the allowable range.
Solution: Verify the program settings.
OPE03 - Terminal Multi-function
Description: Input selection fault. Duplicate functions are selected, up/down commands or trim control increase/decrease are not set simultaneously. Emergency override FWD (H1-0X = 81) and Emergency Override REV (H1-0X = 82) are set simultaneously.
Solution: Verify program settings (H1-01~H1-05).
OPE05 - Sequence Select
Description: Run command is selected through serial communication at 2CN, but the option board is not installed.
Solution: Verify that the board is installed. Remove power to the Drive and connect the option board once more.
OPE09 - PID Selection
Description: PID Control Setup Error. The following settings have been made at the same time: b5-01 (PID Control Method Selection) has been set to a value other than 0, b5-15 (PID Sleep Function Start Level) has been set to a value other than 0, and b1-03 (Stopping Method Selection) was set to 2 or 3.
Solution: Check parameters b5-01, b5-15, and b1-03 and correct the error.
OPE10 - V/f Pattern Setting
Description: V/f data setting fault. V/f parameter settings are not set correctly.
Solution: Check parameters (E1-04 ~ E1-11). A minimum frequency/voltage value may be set higher than the maximum frequency/voltage.
OPE11 - Carrier Frequency/On-Delay
Description: Carrier frequency data setting fault. Carrier frequency proportional gain C6-05 > 6 and C6-04 > C6-03. Upper/lower limit error of C6-03 to 5.0kHz.
Solution: Check the program settings and correct the errors.
ERR - EEPROM R/W Error
Description: It does not match at EEPROM write. This can occur if the power supply is turned OFF or the parameter is reset repeatedly.
Solution: Cycle power off and on to the Drive. Perform a factory initialization (A1-03).