Yaskawa J7 fault codes 2

BB (External base block): Base block command on the multifunction terminal is active. The inverter output is turned OFF (motor coasts to a stop). Temporary condition, cleared when input command is removed. Check the external circuit (sequence).

EF (Simultaneous Forward/Reverse operation commands): When Forward and Reverse operation commands are entered simultaneously for more than 500 ms, the inverter stops according to parameter n04. Check the external circuit (sequence).

STP (Operator function stop): STOP/RESET is pressed while operating with the Forward/Reverse command from the control circuit terminals or the operation command from communication. The inverter stops according to parameter n04.

STP (Emergency stop): The inverter receives an emergency stop alarm signal. The inverter stops according to parameter n04. Open the Forward/Reverse command of the control circuit terminals. Check the external circuit (sequence).

FAN (Cooling fan failure): Cooling fan is locked. Check the following:
Cooling fan
Cooling fan cable is not connected.

OC (Overcurrent): Inverter output current momentarily exceeds approximately 200% of the nominal current. (Control power supply error) Voltage error of the control power supply is detected.
Short circuit or grounding on the inverter output side.
Overload GD2
Extremely fast acceleration/deceleration time (parameters n19 - n22)
Use of special motor
Starting the motor during free rotation
A motor with a capacity larger than the inverter rating is started.
Magnetic contactor on the inverter output side is open/closed.

GF (Ground fault): Ground fault current at the inverter output exceeded the inverter's nominal current.
Check motor insulation.
Ensure the connection between the inverter and the motor is not damaged.

OV (Main circuit overvoltage): Main circuit DC voltage exceeds the over-fatigue detection level due to excessive regenerative energy from the motor. Detection level:
200V: Main circuit DC voltage stops below approximately 410V.
400V: Main circuit DC voltage stops at approximately 820V or more.
Insufficient deceleration time (parameters n20 and n22)
Reduction of overload (e.g., elevator)
Increase the deceleration time.

UV1 (Main circuit low voltage): Main circuit DC voltage drops below the low voltage detection level while the inverter output is OPEN.
200V: Main circuit DC voltage stops below approximately 200V (160V for single phase).
400V: Main circuit DC voltage stops at approximately 400V or more.
Decrease in input power supply voltage
Open phase of the input source
Instantaneous power loss occurred
Check the following:
Power supply voltage
Main circuit power supply wiring is connected.
Terminal screws are tightly fastened.

OH (Cooling fin overheating): Temperature increase due to the inverter's overload operation or increase in input air temperature.
Overload
Improper V/f pattern setting
Insufficient accel time if the error occurs during acceleration.
Input air temperature exceeds 122°F (50°C)
Call fan stops
Check the following:
Load size
V/f pattern setting (parameters n11 - n17)
Input air temperature

OL1 (Motor overload): Motor overload protection is activated by the internal electronic thermal overload relay.
Check the load size or V/f pattern setting (parameters n09 - n15)
Set the motor's nominal current according to the plate with parameter n36.

OL2 (Inverter overload): Inverter overload protection is activated by the internal electronic thermal overload relay.
Check the load size or V/f pattern setting (parameters n09 - n15)
Check the inverter capacity.

OL3 (Over torque detection): Inverter output current exceeded the value preset in parameter n60. When over torque is detected, the inverter performs the operation according to the preset setting of parameter n59.
Check the driven machine and correct the cause of the error or increase the value of parameter n60 to the highest allowable value for the machine.

EF! (External error): The inverter receives an external error input from the control circuit terminal.
EF0: External error reference via MEMOBUS communications
EF2: External error input command from control circuit terminal S2
EF3: External error input command from control circuit terminal S3
EF4: External error input command from control circuit terminal S4
EF5: External error input command from control circuit terminal S5
Check the external circuit (sequence).

CPF-00: Initial memory error detected. Cycle the power. If the error continues, replace the digital operator or inverter.

CPF-01: ROM error detected. Cycle the power. If the error continues, replace the digital operator or inverter.

CPF-04: EEPROM error of the inverter control circuit detected.
Save all parameter data and initialize the parameters. (See page 25 for parameter initialization)
Cycle the power. If the error continues, replace the inverter.

CPF-05: AD converter error detected. Cycle the power. If the error continues, replace the inverter.

CPF-06:
Option card connection error
An incompatible option card is connected.
Turn off the power to the inverter.
Check the connection of the digital operator.
Verify the inverter software number (n179).

CPF-07: Operator control circuit (EEPROM or AD converter) error. Cycle the power. If the error continues, replace the digital operator or inverter.

CE (MEMOBUS communication error): Normal reception of communication data is not possible. Check communication devices and communication signals.

STP (Emergency stop): The inverter stops according to parameter n04 after receiving an emergency stop error signal. Check the external circuit (sequence).

(OFF):
Insufficient power supply voltage
Control power supply error
Hardware error
Check the following:
Power supply voltage.
Main circuit power supply wiring is connected.
Terminal screws are tightly fastened.
Control sequence.
Replace the inverter.