Yaskawa G7 fault codes 2
UL3 (Under Torque Detection 1): A current lower than the settings in L6-02 occurred for a longer time than the settings in L6-03.
+ Verify that the settings in L6-02 and L6-03 are appropriate.
+ Check the mechanical system and correct the cause of the under torque.
UL4 (Under Torque Detection 2): A current lower than the settings in L6-05 occurred for a longer time than the settings in L6-06.
+ Verify that the current setting in L6-05 and the time setting in L6-06 are appropriate.
+ Check the mechanical system and correct the cause of the under torque.
OS (Over Speed Detection): Speed exceeded the settings in F1-08 for a longer time than the settings in F1-09.
+ Overrun/underrun is occurring. Readjust the gain.
+ The reference speed is too high. Check the reference circuit and reference gain.
+ The settings in F1-08 and F1-09 are not appropriate. Check the settings in F1-08 and F1-09.
PGO (PG Open): PG pulses were input while the drive was outputting a frequency.
+ There is a break in the PG wiring. Fix the broken/disconnected wiring.
+ The PG is wired incorrectly. Correct the wiring.
+ Power is not being supplied to the PG. Supply power to the PG correctly.
+ Check the open circuit when using a brake (motor).
DEV (Speed Deviation): Speed deviation exceeded the settings in F1-10 for a longer time than the settings in F1-11.
+ The load is too heavy. Reduce the load.
+ The acceleration time and deceleration time are too short. Extend the acceleration and deceleration time.
+ The load is locked. Check the mechanical system.
+ The settings in F1-10 and F1-11 are not appropriate. Check the settings in F1-10 and F1-11.
+ Check the open circuit when using a brake (motor).
CF (Control Error): During open-loop vector control 1, the torque limit was continuously reached for 3 seconds or longer during deceleration stop.
+ Motor parameter settings are incorrect. Check the motor parameters. Perform autotuning.
+ An error occurred in the speed estimation calculation for open-loop vector control 2. Motor parameter settings are incorrect. Perform autotuning.
+ A start command was received while the motor was in free rotation. Perform autotuning. Enter the start command after the motor has stopped. Set B3-01 (Speed search selection) to 1 or 3 (start with speed search enabled). See notes for using open-loop vector control 2 (page 10-4).
FBL (Feedback Loss): PID feedback reference loss was detected (b5-12 = 2) and the PID feedback input continued for a time set in b5-14 (PID feedback loss detection time) that was less than b5-13 (PID feedback loss detection level).
+ Check the Communication Option Card and communication signals.
EF0 (Opt External Error): External error input from the Communication Option Card.
+ Check the Communication Option Card and communication signals.
EF3, EF4, EF5, EF6, EF7, EF8, EF9, EF10, EF11, EF12 (External Error S3 - S12): "External error" input was made from a multi-function input terminal.
+ Reset the external error inputs to the multi-function inputs.
+ Eliminate the cause of the external error.
SVE (Zero Servo Error): Rotation position moved during zero servo operation.
+ The torque limit was too small. Increase the limit.
+ The load torque was too large. Reduce the load torque.
+ Check for signal noise.
OPR (Operator Connection Disconnected): Connection with the Digital Operator was disconnected during operation for a RUN command from the Digital Operator.
+ Check the connection with the Digital Operator.
CE (Modbus Communication Error): Control data was not received normally once in 2 seconds or longer.
+ Check the communication devices and communication signals.
BUS (Option Communication Error): A communication error was detected from a Communication Option Card when a Run command or frequency reference was set.
+ Check the communication devices and communication signals.
E-15 (SI-F/G Communication Error): A communication error was detected when a Run command or frequency reference was set from an Option Card and E-15 operation selection for continuous operation was set.
+ Check the communication signals.
E-10 (SI-F/G CPU Failure): SI-F/G Option Card operation failed.
+ The connection with the Digital Operator is incorrect. Disconnect and then reconnect the Digital Operator.
+ The drive's control circuits are faulty. Replace the drive.
CPF00 (CPF Digital Operator Communication Error 1): Communication with the Digital Operator was not established within 5 seconds after power was applied.
+ The connector of the Digital Operator was not connected properly. Disconnect and then reconnect the Digital Operator.
+ The drive's control circuits are faulty. Replace the drive.
CPF01 (CPF01 Digital Operator Communication Error 2): After communication was established, a communication error occurred with the Digital Operator for 2 seconds or longer.
+ The Digital Operator was not connected properly. Disconnect and then reconnect the Digital Operator.
+ The drive's control circuits are faulty. Replace the drive.
CPF02 (BB Circuit Error): Baseblock circuit error.
+ Try turning the power supply off and on.
+ The control circuit is damaged. Replace the drive.
CPF03 (EEPROM Error): EEPROM error.
+ Try turning the power supply off and on.
+ The control circuit is damaged. Replace the drive.