Yaskawa 616 G5 fault codes 2

RR Dynamic Brake Transistor
Brake transistor failure
The brake transistor has failed

    Replace the inverter

RH Dynamic Brake Resistor
Brake resistor unit overheated
The temperature of the brake resistor unit exceeded the allowable value

    Reduce regenerative load

OS Over Speed Detection
Motor speed exceeded the over speed level

PGO PG Open Circuit
PG line is broken

    Check the PG line
    Check the motor lock or load condition

DEV Speed Deviation
The deviation between the speed reference and speed feedback exceeded the adjustment level

    Check the load

OPR Operator Connection Disconnected
Digital operator connection error
The connection with the digital operator was disconnected during operation with the operation command

    Check the operator connection

ERR EEPROM R/W Error
EEPROM write error (ERR)
The internal data of the EEPROM did not match the fixed values during initialization

    Replace the control board

CALL SerCom Error
SI-B communication error
Control data was not received normally when power was turned on

    Check the communication devices

CE Memobus Com Error
Communication error
Control data was not received normally when power was turned on

    Check the communication devices

Control Out
Control error
In open-loop vector control, it took 0.8 seconds or more to reach the torque limit during deceleration

    Check related to the motor

SVE Zero Servo Error
During the zero-servo operation, the return position deviated by 10000 rpm or more

    Make sure the torque limit value is not too low
    Make sure the load torque is not excessive
    Check the noise of PG signals

EF External Error
Operation reference error (External)
Both FORWARD and REVERSE operation commands remained off for 500 ms or more

    Check the sequencing circuit

EF3 External Error 3
External error at terminal 3
EF4 External Error 4
External error at terminal 4
EF5 External Error 5
External error at terminal 5
EF6 External Error 6
External error at terminal 6

    An error occurred in the external control circuit
    Check the status of the input terminal
    If an error is displayed when the terminal is not connected, replace the inverter

OPE01 kVA Selection
kVA selection error (OPE01)
kVA selection error

    Check and adjust the fixed data

OPE02 Limit
Fixed setting range error (OPE02)
Fixed data outside the range
    Check the fixed data settings

OPE03 Terminal
Multi-function contact input selection error (OPE03)
In settings from HI-01 to HI-06
The same values were set except for F, FF, and from 20 to 2F
Both UP/DOWN and HOLD commands were set
UP and DOWN commands were not set at the same time
Two or more HOLD, UP/DOWN, sample/hold commands were set
Two or more speed search 1, 2, 3 commands were set
In setting B5-01, both PID control and UP/DOWN commands were set
In setting H3-09, terminal 13/14 selection and a value other than "Not used" were set at the same time

    Check the constants

OPE05 Sequence Selection
Option reference selection error (OPE05)

    In setting B1-01, the frequency reference was selected from the C-option when the C-option was not connected
    In setting B1-02, the operation command was selected from the C-option when the C-option was not connected

    Check the constants

OPE06 PG Option Missing
Control method selection error (OPE06)

    PG was not connected while PG feedback with V/f control was selected
    PG-B was not connected while vector control was selected

    Check the constants

OPE07 Analog Selection
Multi-function analog input selection error (OPE07)
In settings H3-05 and H3-09, the same values were set other than 0 and 1F
When AI-I4B is connected, "0" was set in F2-01 and the option/inverter selection was set in the multi-function contact input

    Check the constants

OPE10 V/f Curve Setting
V/f data setting error (From E1-04 to E1-10)
If the settings from E1-04 to E1-10 do not meet the following conditions
    F Max > F A > F_B > F Min
    (E1-04)(E1-06)(E1-07)(E1-09)

    Check the constants

OPE11 Carrier Frequency/Pre-Delay
Fixed setting error

    Carrier frequency upper limit (C6-01) > 15kHz and Carrier frequency lower limit (C6-02) < 5kHz
    Carrier frequency proportional gain (C6-M3) > 6 and (C6-01) < 10kHz
    Upper/lower limit setting error from C6-01 to C6-03 and C8-1

    Check the constants

COM-ERR(OP&INV)
Control circuit error I (CPF00)
(Digital operator communication error)

    Communication between the inverter and digital operator could not be established within 5 seconds after power was supplied
    MPU peripheral element control error (initialization)
    Reconnect the digital operator connector
    Check the control circuit wiring
    Replace the control board

CPF01 COM-ERR(OP&INV)
Control circuit error 2 (CPF01)
(Digital operator communication error)

    Communication between the inverter and digital operator was established once after power was supplied, but then communication error continued for more than 2 seconds
    MPU peripheral element control error (online)
    Reconnect the digital operator connector
    Check the control circuit wiring
    Replace the control board

CPF02 BB Circuit Error
Basic block circuit error (CPF02)

    Inverter control unit error

    Replace the control board

CPF03 EEPROM Error
EEPROM error (CPF03)

CPF04 Internal A/D Error
CPU internal A/D
converter error (CPF04)

CPF05 External A/D Error
CPU external A/D converter error (CPF05)

CPF06
Option Error
Option connection error (CPF06)
Option card not properly installed

    Reinstall the option card

CPF20 Option A/D Error
A/D converter error in the analog speed reference card (CPF20)
Option card (AI-I4B) A/D converter error

    Replace the option card

This completes the detailed explanation of inverter fault codes and possible solutions. Each fault code specifies a specific problem that can occur in the inverter and how it can be resolved. This information can be helpful in diagnosing and solving inverter problems.