Yaskawa F7 fault codes 2

DEV (Speed Deviation): Excessive speed deviation detected. Detected when F1-04 = 0 to 2 and the Flux Vector control method A1-02 = 3. The speed deviation is greater than the setting in F1-10 and continues for longer than the setting in F1-11.
+ The load was locked. Reduce the load.
+ Acceleration or deceleration time was too short. Extend the acceleration and deceleration time.
+ The load was too large. Check the mechanical system.
+ The settings in F1-10 and F1-11 were not suitable for the application. Check the settings in F1-10 and F1-11.
+ The brake mechanism was engaged. Check that the brake (motor) is released when used.
+ Encoder wiring and/or encoder settings (F1 group) were incorrect. Check the correct encoder wiring and verify that the parameter settings are correct.

EF0 (Opt External Error): Option card external error. An external error condition exists.
+ Check an external condition.
+ Verify the parameters.
+ Verify the communication signal.

EF3, EF4, EF5, EF6, EF7, EF8 (External Error S3 - S8): Detected when programmed for an external error function at terminal S3 - S8 (H1-01 to H1-06) and the drive is stopped using the stop ramp, coast to stop, or sudden stop.
+ An external error condition exists. Eliminate the cause of the external error condition.

E5 (SI-T WDT Error): Consistency error in received control data. Synchronization error in control data between the main control device and the drive.
+ Check the communication timing, for example, the communication cycle.
+ Refer to the SI-T manual for details.

E-15 (SI-F/G Communication Error): A communication error is detected when an operation command or frequency reference is set from the SI-F/G Option Card (b1-01=3, b1-02=3) and communication is lost.
+ Check the communication signals.
+ Check the settings of b1-01 and b1-02.
+ Check the setting of F6-01.
+ Check the master communication configuration.

FAN (Cooling FAN Error): A cooling fan error of the drive was detected and the drive was enabled for overload protection based on the internal electrical thermal value. This error is detected when L8-32 is set to 1.
+ Replace the cooling fan.

FBL (Feedback Loss): PID Feedback Loss. This error occurs when PID Feedback Loss Detection is programmed (b5-12 = 2) and PID Feedback < PID Feedback Loss Detection Level (b5-13) for PID Feedback Loss Detection Time (b5-14).
+ Check the PID feedback source (e.g., converter, sensor, building automation signal) was not properly installed or was not functioning.
+ Verify that the drive is programmed to receive the PID feedback source signal.

GF (Ground Fault): Output Ground Fault. The drive output grounding current exceeded 50% of the drive's nominal output current and L8-09 = 1 (enabled).
+ Remove the motor and run the drive without the motor.
+ Check the motor for phase-to-ground short circuit.
+ Check the output current with a clamp meter and verify the DCCT reading.

LF (Output Phase Loss): Output Open-phase. An open-phase occurred at the drive output. This error is detected when the output current imbalance exceeds 5% and L8-07 = 1 (enabled).
+ Check the motor wiring.
+ Check the motor for phase-to-ground short circuit.
+ Check the motor and drive capacity.

OC (Over Current): The drive output current exceeded the overcurrent detection level (approximately 200% of the drive's nominal output current).
+ Remove the motor and run the drive without the motor.
+ Check the motor for phase-to-phase short circuit.
+ Check the drive for phase-to-phase short circuit at the drive output.
+ Verify that C1-01 and C1-02 are set correctly.

OH (Heat Sink Overheating): The temperature of the heat sink exceeded the setting in L8-02 and L8-03 = 0 to 2.
+ Check for dirt accumulation in fans and the heat sink.
+ Reduce the ambient temperature around the drive.

OH1 (Heat Sink Maximum Temperature): The temperature of the drive's heat sink exceeded 105 degrees C.
+ Replace the cooling fan.

OH3 (Motor Overheating 1): The motor was overheating as measured by the motor thermistor. Recheck the operating time and load size. Recheck the acceleration/deceleration time (C1-01 and C1-02). Recheck the V/F pattern (E1-01 to E1-13). Recheck the motor nominal current value (E2-01).

OL1 (Motor Overloaded): Detected when L1-01 = 1 to 3 and the drive's output current exceeds the motor overload curve.
+ Recheck the operating time and load size, as well as the times set in C1-01 and C1-02.
+ Check the motor nominal current value in E2-01.