Yaskawa F7 fault codes 3

Error Codes and Solutions:

OL2 (Inv Overload): The drive's output current exceeded the drive's overload curve.
+ The load was too large or the acceleration/deceleration times were too short. Recheck the operating time and load size, as well as the times set in C1-01 and C1-02. The voltage of the V/F pattern for the application was incorrect. Review the V/F pattern parameters from E1-01 to E1-13. The size of the drive was too small. Switch to a larger drive size.

OL3 (Over Torque Detection 1): The drive's output current exceeded L6-02 for a longer time than set in L6-03 while L6-01 = 3 or 4.
+ The motor was overloaded. Ensure the values in L6-02 and L6-03 are appropriate. Eliminate the error by checking the application/machine condition.

OL4 (Over Torque Detection 2): The drive's output current exceeded L6-05 for a longer time than set in L6-06 while L6-04 = 3 or 4.
+ The motor was overloaded. Ensure the values in L6-05 and L6-06 are appropriate. Eliminate the error by checking the application/machine condition.

OL7 (HSB OL - High Slip Braking Overload): The output frequency remained constant for longer than the time set in n3-04 during high slip braking.
+ The load's inertia was too large. Ensure the load is the unit of inertia. Reduce the load inertia if possible.

OPR (Oper Disconnection): Detected when the Digital Operator is removed and the drive is commanded to operate through the Digital Operator (b1-02 = 0).
+ The Digital Operator was not attached or the Digital Operator connector was broken. Attach the Digital Operator. Check the Digital Operator connector. Verify the setting of O2-06.

OS (Over Speed Detection): Detected when F1-03 = 0 to 2 and A1-02 = 1 or 3. The motor speed feedback (U1-05) exceeded the setting in F1-08 for a longer time than specified in F1-09.
+ Overshooting/undershooting was occurring. Set the ASR settings in the C5 parameter group. The reference was too high. Check the reference circuit and reference gain. The settings in F1-08 and F1-09 were not appropriate. Check the settings in F1-08 and F1-09.

OV (DC Bus Over Voltage): The DC bus voltage exceeded the trigger point. For 208-240Vac, the trigger point is 410Vdc, for 480Vac, the trigger point is 820Vdc.

PF (Input Phase Loss): There is an open phase in the drive's input power supply or a large imbalance in voltage. Detected when L8-05 = 1 (enabled).
+ There is an open phase at the drive's input. Check the input voltage.
+ Terminal screws at R/L1, S/L2, or T/L3 are loose. Tighten the terminal screws.
+ A momentary power loss occurred. Check the input voltage.
+ The input voltage fluctuation is too large. Check the input voltage.

PGO (PG Open): Detected when PG (encoder) pulses are not received for longer than the time set in F1-14. Detected when F1-02 = 0 to 2 and A1-02 = 1 or 3.
+ There is a break in the PG wiring. Correct the broken/disconnected wiring.
+ PG is wired incorrectly. Correct the wiring.
+ PG is not powered. Supply the correct power for the PG encoder.

PUF (DC Bus Fuse Open): Detects when the DC bus fuse is open.
+ Short-circuited output transistor(s) or terminals. Cut power to the Drive. Disconnect the motor. Perform the power-off checks in Table 6.6. Replace the short-circuited component(s). Replace the faulty fuse.

RH (Dynamic Brake Resistor): The heat sink's protection was enabled when L8-01 = 1. This error is valid only when the 3% duty cycle resistor mounted on the drive's heat sink is used. Set L8-01 = 0 for all other resistors.
+ Overloaded load, extended dynamic braking duty cycle, faulty dynamic braking resistor. Verify the dynamic braking duty cycle. Monitor the DC bus voltage. Replace the dynamic braking resistor.

RR (Dynamic Brake Transistor): The internal dynamic braking transistor is not working properly. The dynamic braking transistor was started at high DC bus voltage, faulty dynamic braking resistor.
+ Turn off and on the power to the Drive. Replace the faulty dynamic braking transistor or resistor. Monitor the DC bus voltage.

SER (Search Retry Error): The speed search was repeated more times than set in b3-19 (Search retry count).
+ The settings in b3-17 and b3-18 were not appropriate. Ensure the settings in b3-17 and b3-18 are appropriate.

SVE (Zero Servo Error): The motor position moved more than 10,000 revolutions during the zero servo operation.
+ The torque limit was too small. Increase the torque limit.
+ The load torque was too large. Reduce the load torque.
+ Control circuit error. Check for signal noise.

UL3 (Under Torque Detection 1): The drive's output current was less than L6-02 for longer than the time set in L6-03 while L6-01 = 7 or 8.
+ The motor was underloaded. Ensure the values in L6-02 and L6-03 are appropriate. Eliminate the error by checking the application/machine condition.

UV1 (DC Bus Under Voltage): Detected when the DC bus voltage fell below the point set in L2-05. For 208-240Vac, the default trigger point is ≤ 190Vdc, for 480Vac, the default trigger point is ≤ 380Vdc.
+ Input voltage at R/L1, S/L2, and T/L3 is low. Check the input circuit and increase the input power within specifications.
+ The acceleration time was set too short. Extend the time in C1-01 or other active acceleration settings.

UV2 (Control Power Supply Under Voltage): Under voltage of the control circuit while operating.
+ External load was lowering the drive's power supplies or there was an internal short circuit in the power/gate drive card.
+ Turn off and on the power to the Drive. Remove all control wiring and test the drive or disconnect the control terminal strip.
+ Repair or replace the Power PCB/Gate Drive PCB.

UV3 (MC Response): Detected when the precharge contactor opened while the drive was operating.
+ Contacts of the soft charge contactor were dirty and the soft charge contactor was not mechanically functioning.
+ Turn off and on the power to the Drive. Check the condition of the soft charge contactor.
+ Repair or replace the Power PCB/Gate Drive PCB.