Yaskawa E7 Fault Codes 3

OC - Overcurrent

    Description: Drive output current exceeded the overcurrent detection level (approximately 180% of Drive rated output current). This could be due to a shorted Drive output phase-to-phase, a shorted motor, a locked rotor, a load that is too heavy, accel/decel time that is too short, or a contactor on the Drive output being opened and closed.
    Solution: Remove the motor and run the Drive without the motor. Check the motor and the Drive for a phase-to-phase short. Verify that parameters C1-01 and C1-02 are set correctly. Check the load conditions.

OH1 - Heatsink MAX Temp

    Description: The temperature of the Drive cooling fin exceeded the temperature programmed in parameter L8-02, and L8-03=0-2. This could be due to non-functioning cooling fan(s), high ambient temperature, or a heat source being too close to the Drive.
    Solution: Check for dirt build-up on the fans and cooling fins. Reduce the ambient temperature around the Drive. If the internal cooling fan is the issue, remove the heating unit or replace the cooling fan.

OH3 - Motor Overheat 1

    Description: The Drive stops or continues operation according to the setting of L1-03 due to overheating of the motor as measured by the motor thermistor.
    Solution: Recheck the cycle time and the size of the load. Recheck the accel/decel time (C1-01 and C1-02). Recheck the V/F pattern (E1-01 through E1-13). Recheck the motor rated current value (E2-01).

OH4 - Motor Overheat 2

    Description: The Drive stops operation according to the setting of L1-04 due to overheating of the motor as measured by the motor thermistor.
    Solution: Recheck the cycle time and the size of the load. Recheck the accel/decel time (C1-01 and C1-02). Recheck the V/F pattern (E1-01 through E1-13). Recheck the motor rated current value (E2-01).

OL1 - Motor Overload

    Description: Designed to protect the motor. The load is too large, or the cycle time is too short at the accel/decel time.
    Solution: Recheck the cycle time and the size of the load, as well as the times set in C1-01 and C1-02. Review the V/F pattern parameters (E1-01 through E1-13). Check the motor rated current value in E2-01.

OL2 - Drive Overload

    Description: Designed to protect the Drive. The load is too large, or the cycle time is too short at the accel/decel time.
    Solution: Recheck the cycle time and the size of the load, as well as the times set in C1-01 and C1-02. Review the V/F pattern parameters (E1-01 through E1-13). Consider changing to a larger size Drive if the size of the Drive is too small.

OL3 - Overtorque Detection 1

    Description: Drive output current is greater than L6-02 for more than the time set in L6-03, indicating the motor is overloaded.
    Solution: Ensure the values in L6-02 and L6-03 are appropriate. Check the application/machine status to eliminate the fault.

OPR - Digital Operator Connection Fault

    Description: The Drive will stop if the digital operator is removed when the Drive is commanded to run through the digital operator. The digital operator might not be attached, or the digital operator connector might be broken.
    Solution: Attach the digital operator. Check the digital operator connector. Verify the setting of o2-06.

OV - DC Bus Overvoltage

    Description: DC Bus Overvoltage occurs when the input voltage at R/L1, S/L2, and T/L3 is too high. For 208-240Vac, the trip point is ≥ 400Vdc. For 480Vac, the trip point is ≥ 800Vdc.
    Solution: Check the input circuit and reduce the input power to within specifications. Extend the deceleration time set in C1-02 if it is too short. Remove any power factor correction capacitors being used on the input to the Drive.

PF - Input Phase Loss

    Description: Drive input power supply has an open phase or has a large imbalance of input voltage.
    Solution: Check the input voltage. Tighten loose terminal screws at R/L1, S/L2, or T/L3. If momentary power loss occurred, check the input voltage again. If input voltage fluctuation is too large, check the input voltage. Verify parameter L8-06 is set correctly per the kVA tables on pages C-2 and C-3, and adjust L8-06 according to your application. Note that changing this parameter from the factory default setting may cause Drive failure and void the product warranty.

PUF - DC Bus Fuse Open

    Description: Detects if the DC bus fuse has opened, possibly due to shorted output transistor(s) or terminals.
    Solution: Remove power from the Drive. Disconnect the motor. Perform the checks without power as outlined in Table 6.6. Replace the shorted component(s) and the defective fuse.

RH - Dynamic Braking Resistor

    Description: The protection of the dynamic braking resistor based on the setting of L8-01.
    Solution: Verify the dynamic braking duty cycle. Monitor the DC bus voltage. Replace the dynamic braking resistor if defective.

RR - Dynamic Braking Transistor

    Description: The dynamic braking transistor is not operating properly, possibly due to a shorted dynamic braking transistor, high DC bus voltage, or a defective dynamic braking resistor.
    Solution: Cycle power off and on to the Drive. Replace the defective dynamic braking transistor or resistor. Monitor the DC bus voltage.

UV1 - DC Bus Undervoltage

    Description: The DC bus voltage is less than or equal to L2-05. For 208-240Vac, the trip point is ≤ 190Vdc. For 480Vac, the trip point is ≤ 380Vdc.
    Solution: Check the input circuit and increase the input power to within specifications. If the acceleration time is set too short, extend the time in C1-01. If the voltage fluctuation of the input power is too large, check the input voltage.

UV2 - Control Power Supply Undervoltage

    Description: Undervoltage of the control circuit when running. This could be due to an external load connected, pulling down the Drive power supplies.
    Solution: Cycle power off and on to the Drive. Repair or replace the Power PCB/Gate Drive PCB. Remove all control wiring and test the Drive.

UV3 - Soft Charge Circuit Fault

    Description: The pre-charge contactor opened while the Drive was running. This could be due to dirty contacts on the soft charge contactor, causing it not to function mechanically.
    Solution: Cycle power off and on to the Drive. Check the condition of the soft charge contactor. Repair or replace the Power PCB/Gate Drive PCB.