Yaskawa A1000 Fault codes 5

- Uv1 (DC Bus Undervoltage)
- - Description: Voltage in the DC bus fell below the undervoltage detection level.
+ Cause: Possible causes include input power phase loss, loose drive input power wiring terminals, or issues with the voltage from the drive input power.
- Check and correct the wiring.
- Ensure there are no loose terminals and apply the specified tightening torque.
- Verify and correct the voltage to be within the specified range.
- If there is no problem with the power supply, check the main circuit magnetic contactor.
- Address any interruptions in the power supply.
- Check and replace the main circuit capacitors if necessary.

- Uv2 (Control Power Supply Voltage Fault)
- - Description: Voltage is too low for the control drive input power.
+ Cause: Possible causes include changes to the L2-02 setting without installing a Momentary Power Loss Ride-Thru unit, damaged control power supply wiring, or damaged internal circuitry.
- Correct the L2-02 setting or install a Momentary Power Loss Ride-Thru unit.
- Cycle power to the drive and check if the fault reoccurs. Replace the control board, entire drive, or control power supply if necessary.

- Uv3 (Undervoltage 3 - Soft-Charge Bypass Circuit Fault)
- - Description: The soft-charge bypass circuit failed.
+ Cause: The relay or contactor on the soft-charge bypass circuit is damaged.
- Cycle power to the drive and check if the fault reoccurs.
- Replace the control board or entire drive if necessary.
- Check the performance life of the soft-charge bypass and replace if it exceeds 90%.

- Uv4 (Gate Drive Board Undervoltage)
- - Description: Voltage drop in the gate drive board circuit.
+ Cause: Not enough power is being supplied to the gate drive board.
- Cycle power to the drive and see if the fault reoccurs.
- Replace the gate drive board or entire drive if the problem continues.

- voF (Output Voltage Detection Fault)
- - Description: Problem detected with the voltage on the output side of the drive.
+ Cause: Hardware is damaged.
- - Solution: Replace the control board or the entire drive.

- AEr (Communication Option Station Number Setting Error)
- - Description: Option card node address is outside of the acceptable setting range.
+ Cause: Station number is set outside the possible setting range.
- Set parameter F6-10 to the proper value for a CC-Link option.
- Set parameter F6-35 to the proper value for a CANopen option.

- bb (Baseblock)
- - Description: Drive output interrupted as indicated by an external baseblock signal.
+ Cause: External baseblock signal was entered via one of the multi-function input terminals (S1 to S8).
- - Solution: Check the external sequence and baseblock signal input timing.

- boL (Braking Transistor Overload Fault)
- - Description: The braking transistor in the drive has been overloaded.
+ Cause: The proper braking resistor has not been installed.
- - Solution: Select the proper braking resistor.

- bUS (Option Communication Error)
- - Description: The connection was lost after initial communication was established.
+ Cause: Possible causes include a broken connection, a master controller that stopped communicating, a damaged option, or improper connection of the option to the drive.
- Check and correct any faulty wiring.
- Replace the option if necessary.
- Reinstall the option ensuring proper alignment of connector pins.
- Take steps to minimize the effects of noise.

- CALL (Serial Communication Transmission Error)
- - Description: Communication has not yet been established.
+ Cause: Possible causes include faulty communications wiring, a programming error on the master side, or damaged communications circuitry.
- Check for wiring errors and correct them.
- Check communications at start-up and correct any programming errors.
- Perform a self-diagnostics check and replace the control board or entire drive if necessary.
- Install a termination resistor at both ends of a communication line and set the internal termination resistor switch correctly on slave drives.

- CE (MEMOBUS/Modbus Communication Error)
- - Description: Control data was not received correctly for two seconds.
+ Cause: Possible causes include noise-induced data errors, incompatible communication protocol, incompatible PLC software settings, or a disconnected or damaged communications cable.
- Take steps to minimize the effects of noise.
- Check the H5 parameter settings and the protocol setting in the controller.
- Check the PLC and change the software settings if necessary.
- Check the connector and replace the communications cable if necessary.

- CrST (Cannot Reset)
- - Description: Fault reset was being executed when a Run command was entered.
+ Cause: A Run command was entered from the external terminals or option during fault reset.
- - Solution: Ensure that a Run command cannot be entered during fault reset and turn off the Run command.

- dEv (Speed Deviation)
- - Description: The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for longer than the time in F1-11.
+ Cause: Possible causes include a heavy load, too short acceleration and deceleration times, a locked-up load, inappropriate parameter settings, or incorrect speed feedback scaling.
- Reduce the load.
- Increase the acceleration and deceleration times.
- Check the machine for any issues.
- Check the settings of parameters F1-10 and F1-11.
- Adjust the speed feedback signal using parameters H6-02 through H6-05.

- dnE (Drive Disabled)
- - Description: "Drive Enable" is set to a multi-function contact input and that signal was switched off.
+ Cause: The "Drive Enable" signal was turned off.
- - Solution: Check the operation sequence to ensure the "Drive Enable" signal is correctly activated.

- EF (Forward/Reverse Run Command Input Error)
- - Description: Both forward run and reverse run closed simultaneously for longer than 0.5 seconds.
+ Cause: Sequence error.
- - Solution: Check the forward and reverse command sequence and correct the problem.

- EF0 (Option Card External Fault)
- - Description: An external fault condition is present.
+ Cause: An external fault was received from the PLC with parameter F6-03 set to 3.
- Remove the cause of the external fault.
- Remove the external fault input from the PLC.
- Check the PLC program and correct problems.

- EF1 to EF8 (External Fault - Input Terminal S1 to S8)
- - Description: External fault at multi-function input terminal S1 to S8.
+ Cause: An external device has tripped an alarm function or the wiring is incorrect.
- Remove the cause of the external fault and reset the multi-function input value.
- Ensure the signal lines are properly connected to the terminals assigned for external fault detection.
- Check if the unused terminals have been set for external fault detection and change the terminal settings if necessary.

- FbH (Excessive PID Feedback)
- - Description: The PID feedback input is higher than the level set for a specified duration.
+ Cause: Parameter settings are incorrect, PID feedback wiring is faulty, the feedback sensor has malfunctioned, or the feedback input circuit is damaged.
- Check parameters b5-36 and b5-37.
- Correct the wiring.
- Check the sensor and replace it if damaged.
- Replace the control board or the entire drive if necessary.

- FbL (PID Feedback Loss)
- - Description: The PID feedback input is lower than the level set for a specified duration.
+ Cause: Similar to FbH.
- - Solution: Similar to FbH.

- Hbb (Safe Disable Signal Input)
- - Description: Both Safe Disable Input channels are open.
+ Cause: Both Safe Disable Inputs H1 and H2 are open.
- Check the signal status at the input terminals H1 and H2.
- Check the Sink/Source Selection for the digital inputs.
- If the Safe Disable function is not utilized, determine if terminals H1-HC, and H2-HC are linked.
- Replace the control board or the entire drive if the channels are broken.

- HbbF (Safe Disable Signal Input)
- - Description: One Safe Disable channel is open while the other channel is closed.
+ Cause: The signals to the Safe Disable inputs are wrong or the wiring is incorrect.
- - Solution: Similar to Hbb.

- HCA (Current Alarm)
- - Description: Drive current exceeded overcurrent warning level.
+ Cause: Load is too heavy, acceleration and deceleration times are too short, or a special-purpose motor is being used.
- Reduce the load for repetitive operations.
- Increase the acceleration and deceleration times.
- Check the motor capacity and ensure it's appropriate for the drive.