Yaskawa A1000 Fault codes 1

Yaskawa A1000 VFD: Types of Alarms, Faults, and Errors

When operating the Yaskawa A1000 VFD, you may encounter various alarms, faults, and errors. It's essential to understand the differences and how to respond to them.

Faults:

    Drive Response: The drive detects a fault, displays the specific fault on the digital operator, and the ALM (Alarm) indicator LED remains lit until the fault is reset. The fault interrupts drive output, and the motor coasts to a stop. Some faults allow you to select the stopping method.
    Output Terminals: Fault output terminals MA-MC will close, and MB-MC will open.
    Resolution: The drive remains inoperable until the fault is cleared. Refer to the manual for fault reset methods.

Minor Faults and Alarms:

    Drive Response: The drive detects an alarm or a minor fault, displays the specific alarm or minor fault on the digital operator, and the ALM indicator LED flashes. The drive continues running the motor, although some alarms allow you to select a stopping method.
    Output Terminals: A multi-function contact output set to be tripped by a minor fault (H2-oo = 10) closes. If the output is set to be tripped by an alarm, the contact will not close.
    Resolution: Remove the cause of the problem to reset a minor fault or alarm.

Operation Errors:

    Drive Response: An operation error occurs when parameter settings conflict or do not match hardware settings (such as with an option card). The digital operator displays the specific error, and multi-function contact outputs do not operate.
    Resolution: The drive will not operate the motor until the error has been reset. Correct the settings that caused the operation error to clear the error.

Tuning Errors:

    Drive Response: Tuning errors occur while performing Auto-Tuning. The digital operator displays the specific error, multi-function contact outputs do not operate, and the motor coasts to a stop.
    Resolution: Remove the cause of the error and repeat the Auto-Tuning process.

Copy Function Errors:

    Drive Response: Copy Function Errors occur when using the digital operator or the USB Copy Unit to copy, read, or verify parameter settings. The digital operator displays the specific error, and multi-function contact outputs do not operate.
    Resolution: Pressing any key on the digital operator will clear the fault. Investigate the cause of the problem (such as model incompatibility) and try again.

Here are explanations for some Yaskawa A1000 VFD fault displays, their causes, and possible solutions:

boL (Braking Transistor Overload Fault):

    Cause: The braking transistor reached its overload level.
    Possible Solution: Select the correct braking resistor if the wrong one is installed.

bUS (Option Communication Error):

    Cause: The connection was lost after establishing initial communication, or no signal was received from the PLC.
    Possible Solution: Check for faulty wiring, correct the wiring, repair disconnected cables and short circuits, minimize the effects of noise, use recommended cables or shielded line, separate communication wiring from drive power lines, install an EMC noise filter, and replace the option card if damaged or not properly connected.

CE (MEMOBUS/Modbus Communication Error):

    Cause: Control data was not received for the CE detection time set to H5-09.
    Possible Solution: Similar to the solutions for bUS fault, including checking for faulty wiring, minimizing the effects of noise, and using recommended cables or shielded lines.

CF (Control Fault):

    Cause: The torque limit was reached continuously for three seconds or longer while ramping to stop in OLV Control.
    Possible Solution: Check the motor parameter settings and repeat Auto-Tuning, set the torque limit to the most appropriate setting (L7-01 through L7-04), adjust the deceleration time (C1-02, C1-04, C1-06, C1-08), and set the frequency to the minimum value and interrupt the Run command when the drive finishes decelerating.

CPF11 to CPF14, CPF16 to CPF19 (Control Circuit Error):

    Cause: Self-diagnostic error in the control circuit.
    Possible Solution: Cycle power to the drive. If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a representative for instructions on replacing the control board. If the connector on the operator is damaged, replace the operator.

CPF02 (A/D Conversion Error):

    Cause: A/D conversion error or control circuit error occurred.
    Possible Solution: Cycle power to the drive. If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a representative for instructions.

CPF03 (Control Board Connection Error):

    Cause: Connection error between the control board and the drive, or drive fails to operate properly due to noise interference.
    Possible Solution: Turn off the power and check the connection between the control board and the drive. If the problem continues, replace the control board or the entire drive. Minimize the effects of noise and use recommended cables or shielded lines.

CPF06 (EEPROM Memory Data Error):

    Cause: Error in the data saved to EEPROM, or power supply was switched off while parameters were being saved.
    Possible Solution: Turn off the power and check the connection between the control board and the drive. If the problem continues, replace the control board or the entire drive. Reinitialize the drive using parameter A1-03 if the error is due to interrupted parameter saving.

CPF07, CPF08 (Terminal Board Connection Error):

    Cause: Faulty connection between the terminal board and the control board.
    Possible Solution: Turn off the power and check the connection between the control board and the drive. If the problem continues, replace the control board or the entire drive.

CPF20, CPF21 (Control Circuit Error):

    Cause: Hardware is damaged.
    Possible Solution: Cycle power to the drive. If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a representative for instructions.


CPF22 (Hybrid IC Failure):

    Cause: Hybrid IC failure on the power board.
    Possible Solution: Cycle power to the drive. If the problem continues, replace the power board or the entire drive. Contact Yaskawa or a representative for instructions on replacing the power board.

CPF23 (Control Board Connection Error):

    Cause: Hardware is damaged.
    Possible Solution: Turn off the power and check the connection between the control board and the drive. If the problem continues, replace the control board or the entire drive.

CPF24 (Drive Unit Signal Fault):

    Cause:
The drive capacity cannot be detected correctly.
    Possible Solution: If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a representative for instructions.

CPF26 to CPF34, CPF40 to CPF45 (Control Circuit Error, CPU Error):

    Cause: Hardware is damaged.
    Possible Solution: If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a representative for instructions on replacing the control board.