Yaskawa A1000 Fault codes 6

 LT-1 to LT-4 (Maintenance Time Alarms)
- - Description: Various components (cooling fan, capacitors, soft charge bypass relay, IGBTs) have reached a certain percentage of their expected performance life.
- - Cause: The respective component has reached a certain percentage of its expected performance life.
- Replace the cooling fan and set o4-03 to 0 to reset the Maintenance Monitor (for LT-1).
- Replace either the control board or the entire drive for LT-2, LT-3, and LT-4.
- Check the load, carrier frequency, and output frequency for LT-4.

 oH (Heatsink Overheat)
- - Description: The temperature of the heatsink exceeded the overheat pre-alarm level.
- - Cause: Surrounding temperature is too high, internal cooling fan has stopped, or airflow around the drive is restricted.
- Improve the air circulation within the enclosure panel.
- Install a fan or air conditioner to cool the surrounding area.
- Replace the cooling fan and ensure proper installation space around the drive.
- Check for dust or other foreign materials clogging the cooling fan.

 oH2 (Drive Overheat Warning)
- - Description: "Drive Overheat Warning" was input to a multi-function input terminal.
- - Cause: An external device triggered an overheat warning in the drive.
- - Solution: Search for the device that tripped the overheat warning and remove the cause of the problem.

 oH3 (Motor Overheat)
- - Description: The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level.
- - Cause: Faulty motor thermostat wiring, a fault on the machine side, or the motor has overheated.
- Repair the PTC input wiring.
- Check the status of the machine and remove the cause of the fault.
- Check the load size, accel/decel times, and cycle times. Adjust settings as needed and ensure the motor cooling system is operating normally.

 oH5 (Motor Overheat - NTC Input)
- - Description: The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2).
- - Cause: Motor has overheated.
- - Solution: Reduce the load and check the ambient temperature.

 oL3 (Overtorque 1)
- - Description: Drive output current (or torque in certain control modes) was greater than L6-02 for longer than the time set to L6-03.
- - Cause: Inappropriate parameter settings or a fault on the machine side.
- - Solution: Check parameters L6-02 and L6-03, check the status of the machine, and remove the cause of the fault.

 oL4 (Overtorque 2)
- - Description: Similar to oL3, but relates to parameters L6-05 and L6-06.
- - Cause: Similar to oL3.
- - Solution: Similar to oL3.

 oL5 (Mechanical Weakening Detection 1)
- - Description: Overtorque occurred, matching the conditions specified in L6-08.
- - Cause: Overtorque occurred, triggering the mechanical weakening level set to L6-08.
- - Solution: Check for the cause of mechanical weakening.

 oS (Overspeed - for Control Mode with PG)
- - Description: The motor speed feedback exceeded the F1-08 setting.
- - Cause: Overshoot is occurring, incorrect speed feedback scaling, incorrect PG pulse number set, or inappropriate parameter settings.
- Adjust the settings for C5-01 and C5-02.
- Enable Feed Forward Control and perform Inertia Auto-Tuning if using Closed Loop Vector mode.
- Set H6-02 to the value of the speed feedback signal frequency when the motor runs at the maximum speed.
- Check and correct parameter F1-01.
- Check the setting for the overspeed detection level and time (F1-08 and F1-09).

  ov (DC Bus Overvoltage)
- - Description: The DC bus voltage exceeded the trip point.
- - Cause: Surge voltage present in the drive input power, motor short-circuited, ground current overcharging the main circuit capacitors, or noise interference.
- Install a DC link choke or an AC reactor.
- Check the motor power cable, relay terminals, and motor terminal box for short circuits.
- Review and implement solutions for handling noise interference.
- Set the number of fault restarts (L5-01) to a value other than 0.
- Check and correct the PG cable and wiring.

  PASS (MEMOBUS/Modbus Comm. Test Mode Complete)
- - Description: MEMOBUS/Modbus test has finished normally.
- - Cause: This indicates a successful test.
- - Solution: No action required as this is a confirmation of successful communication test.

  PGo (PG Disconnect - for Control Mode with PG)
- - Description: Detected when no PG pulses are received for a time longer than the setting in F1-14.
- - Cause: PG cable is disconnected, wiring is wrong, PG encoder lacks power, or brake is holding the PG.
- Reconnect the cable.
- Correct the wiring.
- Ensure the correct power supply is connected to the PG encoder.
- Ensure the brake releases properly.

  PGoH (PG Hardware Fault - detected when using a PG-X3 option card)
- - Description: PG cable has become disconnected.
- - Cause: PG cable is disconnected.
- - Solution: Reconnect the cable and check the setting of F1-20.

  rUn (Motor Switch during Run)
- - Description: A command to switch motors was entered during run.
- - Cause: A motor switch command was entered during run.
- - Solution: Change the operation pattern so that the motor switch command is entered while the drive is stopped.

  SE (MEMOBUS/Modbus Communication Test Mode Error)
- - Description: Error during MEMOBUS/Modbus communication test mode.
- - Cause: A digital input set to 67H (MEMOBUS/Modbus test) was closed while the drive was running.
- - Solution: Stop the drive and run the test again.

  THo (Thermistor Disconnect)
- - Description: The thermistor used to detect motor temperature has become disconnected.
- - Cause: The motor thermistor is not connected properly.
- - Solution: Check the thermistor wiring.

  TrPC (IGBT Maintenance Time - 90%)
- - Description: IGBTs have reached 90% of their expected performance life.
- - Cause: IGBTs have reached 90% of their expected performance life.
- - Solution: Replace the drive.

  UL3 (Undertorque Detection 1)
- - Description: Drive output current (or torque in certain control modes) less than L6-02 for longer than L6-03 time.
- - Cause: Inappropriate parameter settings or load has dropped or decreased significantly.
- Check parameters L6-02 and L6-03.
- Check for broken parts in the transmission system.

  UL4 (Undertorque Detection 2)
- - Description: Similar to UL3, but relates to parameters L6-05 and L6-06.
- - Cause: Similar to UL3.
- - Solution: Similar to UL3.

  Uv (Undervoltage)
- - Description: One of the following conditions was true when the drive was stopped and a Run command was entered: DC bus voltage dropped below the level specified in L2-05, contactor to suppress inrush current in the drive was opened, or low voltage in the control drive input power.
- - Cause: Phase loss in the drive input power.
- - Solution: Check for wiring errors in the main circuit drive input power and correct the wiring.
- - Description: One of the following conditions was true when the drive was stopped and a Run command was entered: DC bus voltage dropped below the level specified in L2-05, contactor to suppress inrush current in the drive was opened, or low voltage in the control drive input power.
- - Cause: Loose wiring in the drive input power terminals, a problem with the drive input power voltage, drive internal circuitry is worn, the drive input power transformer is too small, air inside the drive is too hot, or the CHARGE light is broken or disconnected.
- Ensure the terminals have been properly tightened.
- Check the voltage and lower it if necessary.
- Check the maintenance time for the capacitors and replace parts if needed.
- Check the capacity of the drive input power transformer.
- Check the temperature inside the drive.
- Replace the control board or the entire drive if the CHARGE light is broken or disconnected.

  voF (Output Voltage Detection Fault)
- - Description: There is a problem with the output voltage.
- - Cause: Hardware is damaged.
- - Solution: Replace either the control board or the entire drive.

  oPE (Operator Programming Error)
- - Description: An Operator Programming Error occurs when a contradictory parameter is set or an individual parameter is set to an inappropriate value.
- - Cause: Various causes depending on the specific oPE error code (oPE01, oPE02, oPE03, oPE04, oPE05, oPE06).
- For oPE01: Correct the value set to o2-04.
- For oPE02: Set parameters to the proper values.
- For oPE03: Ensure all multi-function inputs are assigned to different functions, properly set functions that required for use in combination with other functions, correct setting errors, set b5-01 to 0 to disable PID control or disable the Up/Down command, correct the settings for the multi-function input terminal parameters.
- For oPE04: Set A1-03 to 555o to load the parameter settings stored in the terminal board to the drive. Initialize parameters after drive replacement by setting A1-03 to 1110 or 2220.
- For oPE05: Reconnect the input option card to the drive, set H6-01 to 0, properly set parameters.
- For oPE06: Connect a PG option card or correct the value set to A1-02.


oPE07 (Multi-Function Analog Input Selection Error)
- Description: A contradictory setting is assigned to multi-function analog inputs H3-02, H3-06, or H3-10, and PID functions conflict.
- Cause: At least two analog input terminals are set to the same function, or there are simultaneous contradictory settings related to PID feedback and target value.
- - Change the settings to H3-02, H3-06, and H3-10 so that functions no longer conflict.
- - Disable one of the PID selections.

oPE08 (Parameter Selection Error)
- Description: A function has been set that cannot be used in the motor control method selected.
- Cause: Attempted to use a function that is not valid for the selected control mode, or there are setting errors in OLV, OLV/PM, or AOLV/PM modes.
- - Check the motor control method and the functions available.
- - Adjust parameter values so they are appropriate for the selected control mode.
- - Correct the parameter settings.

oPE09 (PID Control Selection Fault)
- Description: PID control function selection is incorrect. Requires that PID control is enabled.
- Cause: Contradictory settings related to PID sleep function, stopping method, and lower limit for the frequency reference.
- - Set b5-15 to a value other than 0.0.
- - Set the stopping method to coast to stop or ramp to stop.
- - Correct the parameter settings for frequency reference and reverse output.

oPE10 (V/f Data Setting Error)
- Description: One of the setting errors has occurred related to V/f pattern settings.
- Cause: V/f pattern setting error.
- Solution: Correct the settings for E1-04, E1-06, E1-07, E1-09, E1-11, and corresponding parameters for motor 2.

oPE11 (Carrier Frequency Setting Error)
- Description: Incorrect setting for the carrier frequency.
- Cause: Carrier frequency lower limit is greater than the upper limit, or the upper and lower limits are contradictory.
- Solution: Correct the parameter settings for the carrier frequency.

oPE13 (Pulse Monitor Selection Error)
- Description: Incorrect setting of monitor selection for pulse train.
- Cause: Scaling for the pulse train monitor is set to 0 while H6-06 is not set to 101, 102, 105, or 116.
- Solution: Change scaling for the pulse train monitor or set H6-06 to 101, 102, 105, or 116.

oPE15 (Torque Control Setting Error)
- Description: Parameter settings that are not allowed in combination with Torque Control have been set.
- Cause: Torque Control is enabled while certain functions are assigned to digital inputs or other control features are enabled.
- Solution: Correct the parameter settings and ensure they are compatible with Torque Control.

oPE16 (Energy Savings Constants Error)
- Description: In AOLV/PM, the automatically calculated energy saving coefficients are out of the allowable range.
- Cause: Incorrect motor data in E5 parameters.
- Solution: Check and correct the motor data in E5 parameters.

oPE18 (Online Tuning Parameter Setting Error)
- Description: Parameters controlling online tuning are not set correctly.
- Cause: Incorrect settings for online tuning parameters.
- Solution: Correct the settings for online tuning parameters.