Yaskawa A1000 Fault codes 4

oPr (External Digital Operator Connection Fault):

- Cause: The external operator has been disconnected from the drive.
- Possible Solution: Check the connection between the operator and the drive, replace the cable if damaged, turn off the drive input power and disconnect the operator, reconnect the operator and reapply drive input power.

oS (Overspeed for Control Mode with PG):

- Cause: The motor speed feedback exceeded the F1-08 setting.
- Possible Solution: Increase settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1), enable Feed Forward and perform Inertia Auto-Tuning if using Closed Loop Vector mode, set H6-02 to the value of the speed feedback signal frequency at maximum motor speed, adjust the input signal using parameters H6-03 through H6-05, check and correct parameter F1-01, and check the settings for overspeed detection level and time (F1-08 and F1-09).

ov (Overvoltage):

- Cause: Voltage in the DC bus has exceeded the overvoltage detection level.
- Possible Solution: Increase deceleration time, install a dynamic braking resistor or unit, set L3-04 to 1 for stall prevention during deceleration, check if sudden drive acceleration triggers an overvoltage alarm, increase acceleration time, use longer S-curve acceleration and deceleration times, enable Overvoltage Suppression function, install a DC link choke, check for ground faults in the motor wiring, correct grounding shorts, check and adjust Speed Search parameters, check and lower drive input power voltage, check and properly rewire the braking transistor and resistor, reconnect and correct PG cable wiring, separate PG encoder wiring from noise sources, review solutions for controlling noise, check and adjust load inertia settings, connect a braking resistor for OLV/PM, adjust parameters that control hunting, stabilize drive input power or disable phase loss detection, and replace the main circuit capacitors if worn.

PF (Input Phase Loss):

- Cause: Drive input power has an open phase or has a large imbalance of voltage between phases.
- Possible Solution: Check for wiring errors in the main circuit drive input power, ensure the terminals are tightened properly, check the voltage from the drive input power, stabilize drive input power or disable phase loss detection, check the maintenance time for the capacitors and replace if necessary, and if the alarm continues to occur despite normal drive input power, replace either the control board or the entire drive.

Here are explanations for additional Yaskawa A1000 VFD faults related to PG disconnect, braking resistor, dynamic braking transistor, IGBT short circuit or ground fault, speed search restarts, motor pull-out or step-out detection, zero servo fault, thermistor disconnect, undertorque detection, and mechanical weakening detection:

PGo (PG Disconnect):

- Cause: No PG pulses are received for longer than the time set to F1-14.
- Possible Solution: Reconnect the PG cable, correct the PG cable wiring, check the power line to the PG encoder, and ensure the motor brake releases properly.

PGoH (PG Hardware Fault):

- Cause: PG cable is not connected properly.
- Possible Solution: Reconnect the cable and check the setting of F1-20.

rF (Braking Resistor Fault):

- Cause: The resistance of the braking resistor is too low.
- Possible Solution: Select a braking resistor option that fits the drive braking transistor specification, and set L8-55 to 0 to disable the braking transistor protection selection if a regenerative converter, unit, or braking unit is being used.

rH (Braking Resistor Overheat):

- Cause: Braking resistor protection was triggered.
- Possible Solution: Check the load, deceleration time, and speed. Reduce the load inertia, increase deceleration times, replace the dynamic braking option with a larger device, recalculate braking load and power, check the braking operation duty cycle, select the optimal braking resistor, and ensure the braking resistor is not used more frequently than its rating permits.

rr (Dynamic Braking Transistor):

- Cause: The built-in dynamic braking transistor failed.
- Possible Solution: Cycle power to the drive and check for reoccurrence of the fault. Replace either the control board or the entire drive if the problem persists.

SC (IGBT Short Circuit or Ground Fault):

- Cause: IGBT fault or IGBT short circuit detection circuit fault.
- Possible Solution: Check motor wiring, turn off and then turn on the power supply. If the problem continues, contact Yaskawa representative.

SEr (Too Many Speed Search Restarts):

- Cause: The number of Speed Search restarts exceeded the value set to b3-19.
- Possible Solution: Reduce the detection compensation gain during Speed Search, increase the current level and detection time during Speed Search, repeat Auto-Tuning, and set b3-14 to 1 to enable Bi-Directional Speed Search.

STo (Motor Pull Out or Step Out Detection):

- Cause: Motor pull out or step out has occurred.
- Possible Solution: Enter the correct motor code for the PM being used into E5-01, increase the load inertia for PM motor, reduce the load, increase the motor or drive capacity, increase acceleration and deceleration times, and adjust the AFR time constant.

SvE (Zero Servo Fault):

- Cause: Position deviation during zero servo.
- Possible Solution: Set the torque limit to an appropriate value, reduce the amount of load torque, and check the PG signal for noise interference.

THo (Thermistor Disconnect):

- Cause: The thermistor that detects motor temperature has become disconnected.
- Possible Solution: Check the thermistor wiring.

UL3, UL4 (Undertorque Detection):

- Cause: The current has fallen below the minimum value set for torque detection.
- Possible Solution: Check the settings of parameters related to torque detection and check the load for any problems.

UL5 (Mechanical Weakening Detection 2):

- Cause: Undertorque was detected and matched the conditions for mechanical loss detection set to L6-08.
- Possible Solution: Check the load side for any problems.

- UnbC (Current Unbalance)
>- Description: Current flow has become unbalanced.
- - Cause: The internal current sensor has detected a current unbalance situation.
> - Solution:
- Check the wiring for any issues.
- Inspect transistors for damage.
- Look for short circuits or grounding problems on the connected motor.