Yaskawa 616 G5 fault codes 2
RR Dynamic Brake Transistor
Brake transistor failure
The brake transistor has failed
Replace the inverter
RH Dynamic Brake Resistor
Brake resistor unit overheated
The temperature of the brake resistor unit exceeded the allowable value
Reduce regenerative load
OS Over Speed Detection
Motor speed exceeded the over speed level
PGO PG Open Circuit
PG line is broken
Check the PG line
Check the motor lock or load condition
DEV Speed Deviation
The deviation between the speed reference and speed feedback exceeded the adjustment level
Check the load
OPR Operator Connection Disconnected
Digital operator connection error
The connection with the digital operator was disconnected during operation with the operation command
Check the operator connection
ERR EEPROM R/W Error
EEPROM write error (ERR)
The internal data of the EEPROM did not match the fixed values during initialization
Replace the control board
CALL SerCom Error
SI-B communication error
Control data was not received normally when power was turned on
Check the communication devices
CE Memobus Com Error
Communication error
Control data was not received normally when power was turned on
Check the communication devices
Control Out
Control error
In open-loop vector control, it took 0.8 seconds or more to reach the torque limit during deceleration
Check related to the motor
SVE Zero Servo Error
During the zero-servo operation, the return position deviated by 10000 rpm or more
Make sure the torque limit value is not too low
Make sure the load torque is not excessive
Check the noise of PG signals
EF External Error
Operation reference error (External)
Both FORWARD and REVERSE operation commands remained off for 500 ms or more
Check the sequencing circuit
EF3 External Error 3
External error at terminal 3
EF4 External Error 4
External error at terminal 4
EF5 External Error 5
External error at terminal 5
EF6 External Error 6
External error at terminal 6
An error occurred in the external control circuit
Check the status of the input terminal
If an error is displayed when the terminal is not connected, replace the inverter
OPE01 kVA Selection
kVA selection error (OPE01)
kVA selection error
Check and adjust the fixed data
OPE02 Limit
Fixed setting range error (OPE02)
Fixed data outside the range
Check the fixed data settings
OPE03 Terminal
Multi-function contact input selection error (OPE03)
In settings from HI-01 to HI-06
The same values were set except for F, FF, and from 20 to 2F
Both UP/DOWN and HOLD commands were set
UP and DOWN commands were not set at the same time
Two or more HOLD, UP/DOWN, sample/hold commands were set
Two or more speed search 1, 2, 3 commands were set
In setting B5-01, both PID control and UP/DOWN commands were set
In setting H3-09, terminal 13/14 selection and a value other than "Not used" were set at the same time
Check the constants
OPE05 Sequence Selection
Option reference selection error (OPE05)
In setting B1-01, the frequency reference was selected from the C-option when the C-option was not connected
In setting B1-02, the operation command was selected from the C-option when the C-option was not connected
Check the constants
OPE06 PG Option Missing
Control method selection error (OPE06)
PG was not connected while PG feedback with V/f control was selected
PG-B was not connected while vector control was selected
Check the constants
OPE07 Analog Selection
Multi-function analog input selection error (OPE07)
In settings H3-05 and H3-09, the same values were set other than 0 and 1F
When AI-I4B is connected, "0" was set in F2-01 and the option/inverter selection was set in the multi-function contact input
Check the constants
OPE10 V/f Curve Setting
V/f data setting error (From E1-04 to E1-10)
If the settings from E1-04 to E1-10 do not meet the following conditions
F Max > F A > F_B > F Min
(E1-04)(E1-06)(E1-07)(E1-09)
Check the constants
OPE11 Carrier Frequency/Pre-Delay
Fixed setting error
Carrier frequency upper limit (C6-01) > 15kHz and Carrier frequency lower limit (C6-02) < 5kHz
Carrier frequency proportional gain (C6-M3) > 6 and (C6-01) < 10kHz
Upper/lower limit setting error from C6-01 to C6-03 and C8-1
Check the constants
COM-ERR(OP&INV)
Control circuit error I (CPF00)
(Digital operator communication error)
Communication between the inverter and digital operator could not be established within 5 seconds after power was supplied
MPU peripheral element control error (initialization)
Reconnect the digital operator connector
Check the control circuit wiring
Replace the control board
CPF01 COM-ERR(OP&INV)
Control circuit error 2 (CPF01)
(Digital operator communication error)
Communication between the inverter and digital operator was established once after power was supplied, but then communication error continued for more than 2 seconds
MPU peripheral element control error (online)
Reconnect the digital operator connector
Check the control circuit wiring
Replace the control board
CPF02 BB Circuit Error
Basic block circuit error (CPF02)
Inverter control unit error
Replace the control board
CPF03 EEPROM Error
EEPROM error (CPF03)
CPF04 Internal A/D Error
CPU internal A/D
converter error (CPF04)
CPF05 External A/D Error
CPU external A/D converter error (CPF05)
CPF06
Option Error
Option connection error (CPF06)
Option card not properly installed
Reinstall the option card
CPF20 Option A/D Error
A/D converter error in the analog speed reference card (CPF20)
Option card (AI-I4B) A/D converter error
Replace the option card
This completes the detailed explanation of inverter fault codes and possible solutions. Each fault code specifies a specific problem that can occur in the inverter and how it can be resolved. This information can be helpful in diagnosing and solving inverter problems.