What types of sensors are used in dataloggers?
Start with the measurement, then match the electrical interface
Data loggers can record temperature, humidity, pressure, level, flow, force, vibration, light and electrical measurements. The essential condition is compatibility between the sensor output and the logger input. Knowing what a sensor measures is only half the job: check its signal and power requirements too. A suitable logger may read it directly or through a signal conditioner.
Temperature probes: similar purpose, different inputs
A Pt100 or other RTD needs resistance measurement and suitable excitation. Check support for two-, three- or four-wire connections. A thermocouple produces a small voltage and needs the correct type setting, appropriate wiring and cold-junction compensation. An NTC thermistor requires the correct resistance-to-temperature conversion. These differences between RTDs and thermocouples determine the input hardware you need.
Alternatively, a transmitter can convert temperature to a 4–20 mA signal. The logger then uses a compatible current input rather than a direct probe input. The measured quantity stays the same; the connection method changes.
Humidity and soil moisture answer different questions
Relative-humidity probes usually report air humidity in %RH, often alongside temperature. Outputs may be analog or digital. Soil-moisture sensors use other methods to determine water content or related properties. An air-humidity probe is not a substitute for a soil probe. Condensation, placement and soil-specific conversion can affect measurement accuracy.
Pressure and level need a defined reference
Pressure sensors support gas and liquid measurements. Absolute, gauge and differential pressure are different quantities; port orientation matters for differential measurements. Tank level can be measured using hydrostatic pressure, ultrasonic sensing or another appropriate technology. Converting hydrostatic pressure to liquid depth requires the fluid density and pressure reference. A pressure value in bar cannot simply be relabeled as metres.
Flow and motion may arrive as pulses
A flow meter may provide an analog flow-rate signal or pulses representing accumulated volume, depending on the model. A pulse input must support the electrical levels and maximum pulse frequency. For example, a meter producing 100 pulses per litre that delivers 300 pulses in 60 seconds indicates three litres in total and an average flow of three litres per minute.
Encoders provide position or speed information through outputs the logger must support. An inductive sensor or photoelectric sensor can also supply part-counting events. A slow software scan can miss fast pulses; use suitable hardware counting where required.
Load cells and strain gauges need bridge measurement
Load cells and strain gauges commonly use resistance bridges. Reading a raw bridge requires excitation, low-level differential measurement and the correct bridge configuration. A load cell rated in mV/V does not produce an ordinary 0–10 V signal. A conditioner can instead provide 0–10 V or 4–20 mA, changing the logger interface required. Consider lead resistance, temperature effects and zero adjustment.
Vibration and sound require suitable acquisition speed
Accelerometers can capture machine vibration, while compatible microphones capture sound signals. IEPE sensors require appropriate constant-current excitation and input circuitry. For waveform analysis, check sample rate, bandwidth and anti-alias filtering. A device that logs temperature once per second cannot automatically capture bearing-vibration waveforms using the same arrangement.
Electrical and environmental measurements
Current, voltage and power readings can come from suitable transducers or communicating power analyzers. Do not assume a logger's low-voltage analog input accepts mains voltage directly. Photodiode-based sensors measure light; pyranometers measure solar irradiance. Water-quality applications use pH, conductivity and dissolved-oxygen sensors. Lux and W/m² describe different quantities. A raw pH electrode also requires appropriate measurement circuitry or a transmitter.
These sensors support environmental monitoring and process recording, among other applications. For industrial installations, chemical compatibility, operating temperature and mechanical placement belong in the selection process.
Check the interface, not just the word “digital”
Resistance, mV, mV/V, 0–10 V, 4–20 mA, pulses and communication protocols impose different input requirements. Supported digital sensors may communicate over Modbus or SDI-12. RS485 describes a physical interface; it does not establish protocol compatibility. Modbus RTU needs matching communication settings and register definitions. A wireless sensor likewise needs a compatible receiver or network.
Before connecting anything, check the measurement range, output type, power supply, available channels and sensor response time. Enter the correct units and scaling during configuration; include sensor consumption in the power budget. A maintenance and calibration plan helps identify changes in sensor performance over time.
Technical references: Campbell Scientific — Sensors · NI — Temperature measurements · NI — Strain measurements · NI — Vibration measurements