what is Stator resistance?

Understanding winding losses and the motor model
Stator resistance (Rs) is the ohmic resistance of the conductors forming an electric motor's stator windings. In the stator and rotor arrangement, the stator is stationary and the rotor rotates. Rs is not an additional adjustment component connected in parallel with the winding; it is an inherent property of the winding conductor. Conductor material, length, cross-sectional area and temperature affect this resistance.
In a motor's per-phase equivalent model, Rs is considered alongside the winding's other electrical effects. It matters for voltage drop, copper losses and accurate motor modelling by the drive. However, Rs alone does not determine motor current; inductance, induced voltage, load and operating conditions also matter.
Its relationship with heating
Under Ohm's law, the instantaneous resistive drop is uR = i × Rs. For a balanced three-phase motor with equal phase resistances and RMS phase currents, stator copper loss is approximately Pcu,s = 3 × Iphase² × Rphase. For example, Rphase = 1 Ω and Iphase = 5 A give a total winding copper loss of 75 W. This is not the motor's total loss.
Copper resistance increases with temperature. For annealed copper, an approximate coefficient of 0.00393/°C around 20 °C gives R(T) ≈ R20 × [1 + 0.00393 × (T − 20)]. A winding measuring 1 Ω at 20 °C therefore reaches approximately 1.236 Ω at 80 °C. Compare readings at the same reference temperature; a recently stopped motor's windings must not be assumed to be at ambient temperature.
How the winding interacts with the rotor
The illustration shows one simplified stator phase; it is not a complete motor equivalent circuit or a wiring instruction. Rs and inductance represent two electrical properties of the same winding. In a squirrel-cage induction motor, interaction with the rotor occurs through the magnetic field across the air gap, rather than a direct supply wire from stator to rotor. The moving marker only illustrates reversal of AC current direction; it does not show actual frequency or particle speed.
Does changing Rs control speed and torque?
Torque and speed cannot be adjusted simply by increasing or decreasing Rs. In an induction motor, synchronous speed depends on supply frequency and pole count, while actual speed also depends on slip. The relationship between frequency and rpm must therefore be considered separately from winding resistance. Higher Rs means greater heat loss at the same phase current; it does not, by itself, establish a particular speed or torque.
Measuring winding resistance
Measurement requires safe isolation and verification that the motor is de-energised, with its terminals disconnected from the drive and other circuits. A multimeter may support comparison on some motors, but test lead and contact resistance can significantly affect very low readings. A four-wire Kelvin measurement reduces this error by separating current injection from voltage sensing. With a suitable winding tester, allow the reading to settle and complete the instrument's inductive energy discharge sequence before disconnecting.
For a DC test, R = V/I uses the voltage drop measured across the winding at steady test current. Dividing a running AC motor's supply voltage by its operating current does not give Rs: that ratio also includes inductive and electromechanical effects. Record the measurement points, winding connection and temperature.
The star–delta connection changes the terminal reading. Assuming three equal windings, negligible lead/contact resistance and a steady DC measurement, Rline = 2 × Rphase in star and Rline = (2/3) × Rphase in delta. A 2 Ω reading between two terminals therefore corresponds to 1 Ω per phase in star, or 3 Ω per phase in delta. Where all six winding ends are separately accessible, removing the links permits direct measurement of individual windings; identify the terminals from the manufacturer's diagram.
Editor's note: Winding resistance and insulation resistance are different measurements. Low-ohm winding resistance assesses the conductive path; insulation testing examines insulation to the frame and, with an appropriate test arrangement, between windings. Similar resistance readings on all three phases do not, by themselves, prove sound turn-to-turn insulation.
The stator resistance parameter in a drive
A variable frequency drive may identify Rs during motor identification or autotuning. In vector control, this value is an input to the flux and current model. The voltage drop across Rs becomes particularly significant at low speed. In V/f control, functions such as torque boost or voltage boost can help compensate for that drop; they do not change the physical winding resistance.
Before copying a measured value into a drive parameter, check whether the manual specifies phase resistance or line-to-line resistance, along with the temperature reference and motor connection. An incorrect Rs can degrade the motor model and control behaviour. Changing the number of turns or conductor size is also not a speed adjustment: it is a rewinding change that affects the motor's design.
Distinguishing external resistors
External elements used for resistance starting are series starting resistors in the stator supply, rather than speed-adjustment resistors connected across the winding. They reduce starting voltage, generate losses and affect torque. Resistors connected to a wound-rotor motor's rotor circuit and a VFD's braking resistor are also different from Rs. Increasing Rs is not a power-factor correction or overload protection method; thermal overload protection and appropriate motor protection must be provided separately.
Related topics
Motor electrical and mechanical behaviour: stator and rotor, star–delta connections, torque, torque curves and why torque matters in motor selection.
Related control and measurement topics: variable frequency drives, vector control, multimeters, Ohm's law and braking resistors.
References. External source content checked on 17 October 2026.
ABB ACS250: autotuning and the Rs motor parameter; WEG: motors and voltage drop at low speed.
HIOKI: low resistance measurement and temperature correction; DV Power: four-wire winding tests and discharge.
Megger: winding resistance and insulation test distinctions; SimpleFOC: phase resistance and star–delta measurement relationships.