Hi everyone,


    Overcurrent during Stop (OC-1)
- Description: Overcurrent detected during the stop phase.
- Cause: Possible power module failure or ground fault.
+ Solution: Check and replace the power module if necessary. Restore the grounded point.

    Overcurrent during Constant Speed Operation (OC-2)
- Description: Overcurrent detected during constant speed operation.
- Cause: Sudden load change, power voltage drop, or unstable inverter operation.
+ Solution: Reduce load fluctuation, check power voltage, adjust settings to stabilize operation.

    Overcurrent during Acceleration (OC-3)
- Description: Overcurrent detected during acceleration.
- Cause: Too rapid acceleration or load fluctuation.
+ Solution: Increase acceleration time setting, adjust torque boost voltage, and check load conditions.

    Overcurrent during Deceleration (OC-4)
- Description: Overcurrent detected during deceleration.
- Cause: Short circuit or rapid load fluctuation.
+ Solution: Increase deceleration time setting and adjust settings to stabilize operation.

    Overcurrent during Braking (OC-5)
- Description: Overcurrent detected during braking.
- Cause: Short circuit or rapid load fluctuation.
+ Solution: Reduce brake voltage setting and check for ground faults.

    Overcurrent during ACR (OC-6)
- Description: Overcurrent detected during Automatic Current Regulation (ACR).
- Cause: Load fluctuation or short circuit.
+ Solution: Check load conditions and restore the grounded point.

    Overcurrent during Pre-excitation (OC-7)
- Description: Overcurrent detected during pre-excitation.
- Cause: Short circuit or load fluctuation.
+ Solution: Restore the grounded point and check load conditions.

    Overcurrent during Automatic Tuning (OC-9)
- Description: Overcurrent detected during automatic tuning.
- Cause: Short circuit or load fluctuation.
+ Solution: Increase acceleration and deceleration time settings, adjust torque stabilizing gain, and check for ground faults.

    Overvoltage during Stop (OV-1)
- Description: Overvoltage detected during the stop phase.
- Cause: Power supply voltage rise or surge voltage.
+ Solution: Reduce the voltage to within the specified range and check the power system.

    Overvoltage during Constant Speed Operation (OV-2)
- Description: Overvoltage detected during constant speed operation.
- Cause: Power supply voltage rise or load fluctuation.
+ Solution: Reduce the voltage to within the specified range and check load conditions.

    Overvoltage during Acceleration (OV-3)
- Description: Overvoltage detected during acceleration.
- Cause: Power supply voltage rise or sudden load change.
+ Solution: Reduce the voltage to within the specified range and adjust settings to manage load changes.

    Overvoltage during Deceleration (OV-4)
- Description: Overvoltage detected during deceleration.
- Cause: Large load GD² or power supply voltage rise.
+ Solution: Set the deceleration time according to the load GD² and reduce the voltage to within the specified range.

    Overvoltage during Braking (OV-5)
- Description: Overvoltage detected during braking.
- Cause: Power supply voltage rise or sudden load change.
+ Solution: Reduce the voltage to within the specified range and check load conditions.

    Overvoltage during ACR (OV-6)
- Description: Overvoltage detected during Automatic Current Regulation (ACR).
- Cause: Power supply voltage rise.
+ Solution: Reduce the voltage to within the specified range.

    Overvoltage during Pre-excitation (OV-7)
- Description: Overvoltage detected during pre-excitation.
- Cause: Power supply voltage rise.
+ Solution: Reduce the voltage to within the specified range.

    Overvoltage during Automatic Tuning (OV-9)
- Description: Overvoltage detected during automatic tuning.
- Cause: Power supply voltage rise.
+ Solution: Reduce the voltage to within the specified range.

    Undervoltage (UV-n)
- Description: Undervoltage detected, possibly due to a power voltage drop, input phase failure, or instantaneous power failure.
- Cause: Power supply issues.
+ Solution: Check the power supply system and correct if necessary.


+ Ge VAT300 User manuals >

+ Ge VAT300 Fault Codes 1 >

+ Ge VAT300 Fault Codes 2 >

+ Ge VAT300 Fault Codes 3 >


+ General Electric 2. Main page >

+ VFD Homepage > 


-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  03.01.2013