Ge VAT2000 fault codes 2

Hi everyone,

General Electric VAT2000 VFD Troubleshooting without a Fault Display

When there's no fault display, here's how to figure out what might be wrong and what to do:


Motor Doesn't Start

- Check the Wiring: Make sure the input/output wiring is correct. There might be a problem with the power supply or a phase might be missing.
- Check the Load: The motor might be stuck, or the load might be too heavy. Try lightening the load.
- Check Settings: Make sure the reverse run interlock function (C09-3) and other settings are correct.
- Check the Voltage: Make sure the VAT2000 is sending out the right voltage to the motor.
- Check Local/Remote Setting: Make sure it's set to the right mode for your setup.
- Check the Encoder Signal: Make sure it's being received correctly.

Motor Runs in the Opposite Direction

- Check the Phase Sequence: Make sure the U, V, and W output terminals are connected in the right order.
- Check the Wiring for Forward/Reverse Run: Make sure the wires are connected to the right terminals. For forward run, connect RUN to RY0. For reverse run, connect PSI1 to RY0 (when the input terminal function setting is C03-0=1, which is the default value).

Motor Runs but Speed Doesn't Change

- Check the Load: It might be too heavy. Try reducing it.
- Check the Frequency Setting: The signal level might be too low. Make sure the circuit and signal level are correct.

Motor Acceleration/Deceleration Isn't Smooth

- Adjust the Time Settings: The acceleration/deceleration time setting (A01-0, 1) might be too low. Try increasing it.

Motor Speed Varies During Constant Speed Operation

- Check the Load: It might be changing too much or be too heavy. Try reducing the load or its fluctuation.
- Check the Inverter-Motor Ratings: Make sure they match the load. If not, select a set that does.

Motor Speed Is Too High or Low

- Check the Motor Specifications: The number of poles or voltage might be wrong.
- Check the Frequency Settings: The maximum frequency (speed) or base frequency might be set incorrectly.
- Check the Terminal Voltage: It might be too low. Try using a thicker output cable.

Overvoltage Limit

- If the output frequency suddenly drops, the DC voltage might rise due to regenerative power. The output frequency automatically adjusts to keep the DC voltage from going above the preset value.

Overload Trip (OL-1)

- The inverter stops and cuts off the output if the overload characteristics set with C22-0, 1, and 2 are exceeded. You can change the setting (usually 150% for 1 minute) based on the motor's characteristics.

Overheat (UOH)

- A thermistor is installed to detect when the heatsink gets too hot.

Self-Diagnosis (IO, dER, CPU)

- The built-in CPU, peripheral circuits, and data are constantly checked for any issues.

Grounding Trip (Grd1 to 9)

- The inverter stops and cuts off the output if a ground fault is detected.

Power Module Fault (PM-1 to 9)

- The inverter stops if a fault is detected in the operation of the main circuit power module protection function.

Emergency Stop (EMS)

- Check the Wiring: The EMS sequence input might have been activated. Also, this fault occurs when C00-4=2.

Power Module (PM-1~PM-9)

- Indicates that the short circuit protection circuit was activated. The sub-codes and solutions are the same as for OC-1~9.

Overcurrent During Various Operations (OC-1 to OC-9)

- OC-1 (During Stop): The power module in the main circuit might be broken.
- OC-2 (During Constant Speed Operation): A sudden change in the load or a short circuit might have occurred. Reduce load fluctuation.
- OC-3 (During Acceleration): Increase the acceleration time setting (A01-0) and reduce the torque boost voltage (A02-2).
- OC-4 (During Deceleration): Increase the deceleration time setting (A01-1).
- OC-5 (During Braking): Reduce the brake voltage setting (A03-0).
- OC-6 (During ACR): A short circuit in the load might have occurred.
- OC-7 (During Pre-excitation): -
- OC-9 (During Automatic Tuning): Increase the acceleration and deceleration time settings.

Overvoltage During Various Operations /OU/ (OV-1 to OV-9)

- OV-1 /ou-1/ (During Stop): The power supply voltage might have risen. Reduce it to within the specified range.
- OV-2 (During Constant Speed Operation): The power supply voltage might have risen, and the speed might be fluctuating.
- OV-3 (During Acceleration): -
- OV-4 (During Deceleration): The load GD2 might be too large, and the power supply voltage might have risen.
- OV-5 (During Braking): The power supply voltage might have risen.
- OV-6 (During ACR): -
- OV-7 (During Pre-excitation): -
- OV-9 (During Automatic Tuning): -

+ Ge VAT2000 VFD User manual >>

+ Ge VAT2000 Fault codes > 

+ Ge VAT2000 Fault Codes 2 >

+ Ge VAT2000 Fault Codes 3 >


+ General Electric 2. Main page >

+ VFD Homepage > 


-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  03.01.2013